2020-12-21 13:46:06FAILED
  
 1) THE PLANS SHOW POWER BEING RUN UNDER PRIVATE
 PROPERTY FROM THE FPL POLE TO THE 40TH STREET
 RIGHT-OF-WAY. PROVIDE A SURVEY, PREPARED BY A FLORIDA
 LICENSED SURVEYOR, CLEARLY SHOWING THAT THIS WORK IS
 BEING DONE IN A GENERAL UTILITY EASEMENT OR IN THE
 ALLEY ADJACENT TO THE PARCEL. IF IT IS NOT IN AN
 EASEMENT OR THE ALLEY, THEN IT MAY NOT BE INSTALLED IN
 THE LOCATION SHOWN.
  
 2) IF THE INSTALLATION IS SHOWN BY THE SURVEY TO BE IN
 THE ALLEY, THEN YOU MUST SUBMIT AND HAVE APPROVED A
 COMMUNICATIONS FACILITIES PLACEMENT PERMIT APPLICATION
 FOR CITY RIGHTS-OF-WAY FOR THE FIBER INSTALLATION IN
 BOTH THE ALLEY AND THE 40TH STREET RIGHT-OF-WAY. THE
 SURVEY WOULD ALSO NEED TO INCLUDE THE 40TH STREET
 RIGHT-OF-WAY LINE AND THE SIDEWALK LOCATION SO THAT
 STAFF CAN VERIFY THAT THE FIBER INSTALL IS WITHIN THE
 RIGHT-OF-WAY AND NOT ON PRIVATE PROPERTY AS WELL AS THE
 UTILITY LOCATES AND TREES.
  
 3) PROVIDE A COPY OF THE FDOT APPROVAL FOR THE WORK
 WITHIN THE BROADWAY AVENUE RIGHT-OF-WAY.
  
 4) THE PROPOSED WIRELESS FACILITY (POLE WITH EXTERIOR
 MOUNTED EQUIPMENT) DOES NOT MEET THE CITY OF WEST PALM
 BEACH CONCEALMENT (STEALTH), STYLE OR HEIGHT
 REQUIREMENTS LISTED IN SECTIONS 78-411(E), 78-411(F)
 AND 78-411(G) OF THE CITY CODE. PROVIDE A POLE THAT
 MEETS THE CITY CODE REQUIREMENTS. NOTE: VERIZON HAS
 SHOWN POLES ON OTHER APPLICATIONS FOR OTHER LOCATIONS
 WITHIN THE CITY THAT MEET THE CITY CODE REQUIREMENTS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  