| 2021-01-11 11:08:45 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 20101339 |
| | ADD:7459 RIVERWALK CIR. BLDG.# 205 |
| | CONT: PALM BEACH COUNTY CONTRACTOR CORP. |
| | TEL: 561-257-3706 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: MON. JAN. 11TH/ 2021 |
| | ACTION: DENIED |
| | |
| | 1) SHEET A-1: UNDER THE HEADING PROJECT DATA THE PLANS |
| | INDICATE THIS ADDITION IS CONSTRUCTION TYPE 5B, |
| | UNPROTECTED, UNSPRINKLERED. |
| | 1A) 2ND REQUEST. THE MAXIMUM DEAD END IS GIVEN= W/ |
| | SPRINKLERS 25 FEET. STATED ABOVE A NON-SPRINKLERED |
| | BUILDING. FBC SECTION 1020.4 STATES NON-SPRINKLERED |
| | BUILDINGS THE DEAD END MAXIMUM DISTANCE IS 20 FEET. |
| | 107.2.1.2 ADDITIONAL INFORMATION REQUIRED, DISCREPANCY. |
| | |
| | 1B) COMPLIED. |
| | |
| | 1C) 2ND REQUEST. THE PLAN STATES LEVEL 2.. PLEASE NOTE |
| | THE SUBMITTED PLAN SHOULD BE DESIGNED UNDER THE 2017 |
| | FBC-EXISTING BUILDING CODE CHAPTER 11 ADDITIONS. |
| | |
| | 2) SHEET A-1 TOILET ROOM ELEVATIONS AND EXIST. TOILET |
| | ROOM ACCESSORY SCHEDULE. THIS IS A NEW ADDITION WHY |
| | WOULD THE TOILET ACCESSORIES BE EXISTING? 107.2.1.2. |
| | ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 2A) 2ND REQUEST. CHANGE DETAILS. IN BOTH THE ELEVATIONS |
| | AND ACCESSORY SCHEDULE THE SIDE AND BACK GRAB BAR ARE |
| | SHOWN MEASURED FROM FLOOR TO THE CENTERLINE OF THE GRAB |
| | BAR. 2017 FBC-ACCESSIBILITY CODE SECTION 609.4 POSITION |
| | OF GRAB BARS. GRAB BARS SHALL BE INSTALLED IN A |
| | HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF |
| | THE GRIPPING SURFACE, NOT CENTERLINE. |
| | |
| | 2B) 2ND REQUEST. CHANGE DETAILS. THE TOILET PAPER |
| | DISPENSER IS MEASURED FROM THE BACK WALL TO CENTER LINE |
| | OF THE DISPENSER MAX. 3 FEET. PLEASE SHOW COMPLIANCE |
| | WITH THE 2017 ACCESS. CODE SECTION TOILET PAPER |
| | DISPENSERS. 604.7. THE TOILET PAPER DISPENSER SHALL |
| | COMPLY WITH 309.4 AND SHALL BE 7 INCHES MINIMUM TO 9 |
| | INCHES MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO |
| | THE CENTERLINE OF THE DISPENSER. |
| | |
| | 2C) THE PLANS ARE SILENT AS TO THE PROTECTION OF THE |
| | WATER SUPPLY AND DRAINAGE PIPE UNDER THE LAV. 2017 |
| | FBC-ACCESS. CODE 606.5 EXPOSED PIPES AND SURFACES. |
| | WATER SUPPLY & DRAINPIPES UNDER LAVATORIES AND SINKS |
| | SHALL BE INSULATED OR OTHERWISE CONFIGURED TO PROTECT |
| | AGAINST CONTACT. |
| | |
| | 3) 2ND REQUEST. SHEET A-1: UNDER THE HEADING OF WALL |
| | FINISHES THE PLANS INDICATE GYPSUM BOARD. 2017 FBC-B |
| | 1210.2.2. WALLS & PARTITIONS. THIS COMMENT IS A RESULT |
| | OF THE BUILDING OFFICIAL INTERPRETATION. IN RESTROOMS |
| | EPOXY PAINT IS NO LONGER CONSIDERED A SMOOTH HARD, |
| | NON-ABSORBENT SURFACE. |
| | WALLS & PARTITIONS WITHIN 2 FEET OF SERVICE SINKS, |
| | URINALS, AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD, |
| | NON-ABSORBENT SURFACE TO A HEIGHT OF NOT LESS THAN 4 |
| | FEET ABOVE THE FLOOR, EXCEPT FOR STRUCTURAL ELEMENTS, |
| | THE MATERIAL USED IN SUCH WALLS SHALL BE OF A TYPE THAT |
| | IS NOT ADVERSELY AFFECTED BY MOISTURE. |
| | 2017 FBC-B 2509.1. WET AREAS. SHOWERS AND PUBLIC TOILET |
| | WALLS SHALL COMPLY WITH 1210.2. |
| | 2017 FBC-B 1210.2. FINISH MATERIALS. WALLS, BASE, |
| | FLOORS AND PARTITIONS IN TOILET AND BATHROOMS SHALL |
| | COMPLY WITH SECTIONS 1210.1 THROUGH 1210.4. |
| | |
| | 4-6) COMPLIED. |
| | |
| | 7) 2ND REQUEST. PLEASE NOTE 3 PRODUCT APPROVALS WERE |
| | SUBMITTED FOR THE ROOFING MATERIALS. NONE OF THE 3 |
| | ROOFING PRODUCT APPROVALS WERE HIGHLIGHTED/ CIRCLED AS |
| | FAR AS TYPE OF MATERIALS, TYPE OF FASTENER AND |
| | ALLOWABLE UPLIFT. 2017 WEST PALM BEACH AMENDMENTS TO |
| | THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATIVE |
| | CODE 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE |
| | CODE, THE CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, |
| | DESCRIBE AND DELINEATE THE TYPE OF ROOFING SYSTEM, |
| | MATERIALS, VENTING, FASTENING REQUIREMENTS, FLASHING |
| | REQUIREMENTS AND WIND RESISTANCE RATING THAT ARE |
| | REQUIRED TO BE INSTALLED. PRODUCT EVALUATION AND |
| | INSTALLATION SHALL INDICATE COMPLIANCE WITH THE WIND |
| | CRITERIA REQUIRED FOR THE SPECIFIC SITE. |
| | NOA # 18-0509.18 EAGLE ROOFING MEDIUM PROFILE CONCRETE |
| | TILE. |
| | FL6332-R8 ICP ADHESIVES AND SEALANT, |
| | FL5259 POLY ROOF UNDERLAYMENT. DOES THIS PRODUCT ALLOW |
| | DIRECT DECK ATTACHMENT? |
| | |
| | 8A)COMPLIED EXTERIOR DOOR PRODUCT APPROVAL |
| | |
| | 8B) SEMI-COMPLIED, DESIGNER OF RECORD NOR CONTRACTOR |
| | HAS NOT SHOWN COMPLIANCE WITH COMMENT # 7. FL |
| | 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | PRODUCT APPROVALS, SHOP DRAWINGS ETC. |
| | |
| | 9) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| | 19 |
| | IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| | 561-718-9724. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |