Plan Review Notes
Plan Review Notes For Permit 20101339
Permit Number 20101339
Review Stop B
Sequence Number 1
Notes
Date Text
2020-11-04 14:11:00WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20101339
 ADD:7459 RIVERWALK CIR. BLDG.# 205
 CONT: PALM BEACH COUNTY CONTRACTOR CORP.
 TEL: 561-257-3706
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. NOV. 04TH/2020
 ACTION: DENIED
  
 1) SHEET A-1: UNDER THE HEADING PROJECT DATA THE PLANS
 INDICATE THIS ADDITION IS CONSTRUCTION TYPE 5B,
 UNPROTECTED, UNSPRINKLERED.
 1A) THE MAXIMUM DEAD END IS GIVEN= W/ SPRINKLERS 25
 FEET. STATED ABOVE A NON-SPRINKLERED BUILDING.
 107.2.1.2 ADDITIONAL INFORMATION REQUIRED, DISCREPANCY.
  
 1B) THE MAXIMUM TRAVEL = W SPRINKLERS 150 FEET PER
 TABLE 1006. PLEASE NOTE THE TABLES 1006 ALL (3) ARE
 COMMON PATH OF TRAVEL, TABLE 1006.2.1 IS FOR THE 1ST
 FLOOR STORAGE OCCUPANCY < THAN OR EQUAL TO 30 100 FEET
 GREATER OCCUPANT LOAD THAN 30 THEN 75 FEET.
  
 1C) THE PLAN ALSO STATES THAT IT WAS DEVELOPED IN
 COMPLIANCE WITH THE PRESCRIPTIVE COMPLIANCE METHOD.
 LEVEL 2. PLEASE NOTE THE PRESCRIPTIVE COMPLIANCE METHOD
 IS ONE OF 3 COMPLIANCE METHODS. THE WORK AREA METHOD
 (LEVEL 1, 2 & 3) AND THE PERFORMANCE COMPLIANCE METHOD.
 PLEASE NOTE THE SUBMITTED PLAN SHOULD BE DESIGNED UNDER
 THE 2017 FBC-EXISTING BUILDING CODE CHAPTER 11
 ADDITIONS.
  
 2) SHEET A-1 TOILET ROOM ELEVATIONS AND EXIST. TOILET
 ROOM ACCESSORY SCHEDULE. THIS IS A NEW ADDITION WHY
 WOULD THE TOILET ACCESSORIES BE EXISTING? 107.2.1.2.
 ADDITIONAL INFORMATION IS REQUIRED.
  
 2A) IN BOTH THE ELEVATIONS AND ACCESSORY SCHEDULE THE
 SIDE AND BACK GRAB BAR ARE SHOWN MEASURED FROM FLOOR TO
 THE CENTERLINE OF THE GRAB BAR. 2017 FBC-ACCESSIBILITY
 CODE SECTION 609.4 POSITION OF GRAB BARS. GRAB BARS
 SHALL BE INSTALLED IN A HORIZONTAL POSITION, 33 INCHES
 MINIMUM AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR
 MEASURED TO THE TOP OF THE GRIPPING SURFACE, NOT
 CENTERLINE.
  
 2B) THE TOILET PAPER DISPENSER IS MEASURED FROM THE
 BACK WALL TO CENTER LINE OF THE DISPENSER MAX. 3 FEET.
 PLEASE SHOW COMPLIANCE WITH THE 2017 ACCESS. CODE
 SECTION TOILET PAPER DISPENSERS. 604.7. THE TOILET
 PAPER DISPENSER SHALL COMPLY WITH 309.4 AND SHALL BE 7
 INCHES MINIMUM TO 9 INCHES MAXIMUM IN FRONT OF THE
 WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER.
  
 2C) THE PLANS ARE SILENT AS TO THE PROTECTION OF THE
 WATER SUPPLY AND DRAINAGE PIPE UNDER THE LAV. 2017
 FBC-ACCESS. CODE 606.5 EXPOSED PIPES AND SURFACES.
 WATER SUPPLY & DRAINPIPES UNDER LAVATORIES AND SINKS
 SHALL BE INSULATED OR OTHERWISE CONFIGURED TO PROTECT
 AGAINST CONTACT.
  
 3) SHEET A-1: UNDER THE HEADING OF WALL FINISHES THE
 PLANS INDICATE GYPSUM BOARD. 2017 FBC-B 1210.2.2. WALLS
 & PARTITIONS. THIS COMMENT IS A RESULT OF THE BUILDING
 OFFICIAL INTERPRETATION. IN RESTROOMS EPOXY PAINT IS NO
 LONGER CONSIDERED A SMOOTH HARD, NON-ABSORBENT SURFACE.
 WALLS & PARTITIONS WITHIN 2 FEET OF SERVICE SINKS,
 URINALS, AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD,
 NON-ABSORBENT SURFACE TO A HEIGHT OF NOT LESS THAN 4
 FEET ABOVE THE FLOOR, EXCEPT FOR STRUCTURAL ELEMENTS,
 THE MATERIAL USED IN SUCH WALLS SHALL BE OF A TYPE THAT
 IS NOT ADVERSELY AFFECTED BY MOISTURE.
 2017 FBC-B 2509.1. WET AREAS. SHOWERS AND PUBLIC TOILET
 WALLS SHALL COMPLY WITH 1210.2.
 2017 FBC-B 1210.2. FINISH MATERIALS. WALLS, BASE,
 FLOORS AND PARTITIONS IN TOILET AND BATHROOMS SHALL
 COMPLY WITH SECTIONS 1210.1 THROUGH 1210.4.
  
 4) SHEET A-1 UNDER THE FOUNDATION LEGEND INDICATES NEW
 8-INCH CMU WALL FILLED CELLS AT 48 INCHES ON CENTER.
 THE SIZE OF THE VERTICAL BARS IS NOT SPECIFIED. THE
 NOTE IS FOR THE BOND BEAM AND DOES NOT MENTION THE
 REBAR FOR THE BOND BEAM? 107.2.1.2 ADDITIONAL
 INFORMATION IS REQUIRED. SHEET A-2 SHOWS LINTEL
 SCHEDULES.
  
 5) SHEET A-2 PROVIDES THE ROOF PRESSURES FOR ZONES 1-3
 BUT DOES NOT PROVIDE THE WIND DESIGN CRITERIA. NOR ARE
 THE PERUSES GIVEN FOR THE WALL OPENINGS (DOORS).
 2017 FBC-B 1603.1.4 WIND DESIGN DATA. THE FOLLOWING
 INFORMATION RELATED TO WIND LOADS SHALL BE SHOWN,
 REGARDLESS OF WHETHER WIND LOADS GOVERN THE DESIGN OF
 THE LATERAL FORCE-RESISTING SYSTEM OF THE STRUCTURE:
  
 5.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS
 DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1.
  
 5.2. RISK CATEGORY.
  
 5.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE. ASCE 7-10 TABLE 30.3.1.
  
 5.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 5.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED
 BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR
 THE DESIGN OF THE STRUCTURE, PSF.
  
 5.6. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING. ASCE 7-10 TABLE 30.3.1. 1609.3.1 WIND SPEED
 CONVERSION VULT TO VASD.
  
 6) THE PLANS ARE SILENT AS TO ATTIC ACCESS. WITH A 4/12
 PITCH AND 20 SPAN, 10 FEET TO CENTERLINE OR 40-INCH
 RISE IN ROOF HEIGHT. PLEASE HOW COMPLIANCE WITH ATTIC
 ACCESS 1209.2 OF THE 2017 FBC-B.
  
 7) PLEASE NOTE 3 PRODUCT APPROVALS WERE SUBMITTED FOR
 THE ROOFING MATERIALS. NONE OF THE 3 ROOFING PRODUCT
 APPROVALS WERE HIGHLIGHTED/ CIRCLED AS FAR AS TYPE OF
 MATERIALS, TYPE OF FASTENER AND ALLOWABLE UPLIFT. 2017
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATIVE CODE 107.2.1.2 FOR ROOF
 ASSEMBLIES REQUIRED BY THE CODE, THE CONSTRUCTION
 DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND DELINEATE THE
 TYPE OF ROOFING SYSTEM, MATERIALS, VENTING, FASTENING
 REQUIREMENTS, FLASHING REQUIREMENTS AND WIND RESISTANCE
 RATING THAT ARE REQUIRED TO BE INSTALLED. PRODUCT
 EVALUATION AND INSTALLATION SHALL INDICATE COMPLIANCE
 WITH THE WIND CRITERIA REQUIRED FOR THE SPECIFIC SITE.
 NOA # 18-0509.18 EAGLE ROOFING MEDIUM PROFILE CONCRETE
 TILE.
 FL6332-R8 ICP ADHESIVES AND SEALANT,
 FL5259 POLY ROOF UNDERLAYMENT. DOES THIS PRODUCT ALLOW
 DIRECT DECK ATTACHMENT?
  
 8A) PLEASE NOTE NO PRODUCT APPROVAL WAS SUBMITTED FOR
 THE NEW EXTERIOR RESTROOM DOORS.
 COMPONENTS & CLADDING. 2017 FBC-B 1609.1.2 PROTECTION
 OF OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE
 CODE 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS: (31)(A) EXTERIOR DOORS.
  
 8B) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP
 DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD
 PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
  
 9) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  