| 2021-02-24 11:13:12 | 3RD REVIEW FBC-2017 PLUMBING |
| | PERMIT- 20101298 |
| | 2/23/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | REMAINING FAILED COMMENTS FROM THE 1ST AND 2ND REVIEW |
| | ARE LISTED BELOW. PLEASE NOTE THE REQUESTED RESPONSE |
| | NARRATIVE FROM THE DESIGN PROFESSIONALS WHICH HELPS |
| | EXPEDITE THE REVIEW PROCESS WAS NOT SUBMITTED. |
| | |
| | 1) FAILED. SHEET P1: PROVIDE PLUMBING FIXTURE |
| | CALCULATIONS IN ACCORDANCE WITH TABLE 403.1 FBC P. |
| | PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND |
| | PROVIDE NUMBER OF FIXTURES. PLEASE NOTE THAT DRINKING |
| | FOUNTAINS ARE REQUIRED FIXTURES FOR MERCANTILE |
| | OCCUPANCIES. THE EXCEPTION ALLOWED FOR RESTAURANTS |
| | SERVING DRINKING WATER TO CUSTOMERS UNDER SECTION 410.4 |
| | DOES NOT APPLY. THE DRINKING FOUNTAINS SHALL BE |
| | ACCESSIBLE IN COMPLIANCE WITH SECTIONS 211.2, & 602.1- |
| | 602.6 FBC ACC. THE ARCHITECT OF RECORD INDICATES AN |
| | OCCUPANT LOAD OF 33 ON SHEET A2 WHICH CONTRADICTS HIS |
| | LOAD OF 15 SHOWN IN THE FIXTURE CALCULATIONS. PLEASE |
| | PROVIDE THE REQUIRED DRINKING FOUNTAINS- SEE SECTION |
| | 410.2 FBC P. |
| | |
| | 2) FAILED. P1: SHOW THE LOCATIONS OF THE DRINKING |
| | FOUNTAINS AND REVISE THE PLUMBING PIPING PLANS AND |
| | ISOMETRIC DRAWINGS ACCORDINGLY- SECTION 107.3.5.3 WPB. |
| | SEE FAILED COMMENT #1 ABOVE. |
| | |
| | 3) FAILED. PROVIDE DRINKING FOUNTAIN INSTALLATION |
| | DETAILS SHOWING COMPLIANCE WITH SECTIONS 306, 307, AND |
| | 602 FBC ACC INCLUDING ELEVATION VIEWS SHOWING KNEE AND |
| | TOE CLEARANCES, SPOUT HEIGHTS, AND SPOUT LOCATIONS. |
| | INDICATE HOW THE FOUNTAINS WILL BE IN COMPLIANCE WITH |
| | SECTION 307.2- PROTRUDING OBJECTS INTO THE CIRCULATION |
| | PATH. SEE FAILED COMMENT #1 ABOVE. |
| | |
| | 5) FAILED. P1: THE ISOMETRIC DRAWINGS AT THE LEFT SIDE |
| | OF THE PLAN SHEET APPEAR TO BE CUT OFF AND INCOMPLETE. |
| | PLEASE PROVIDE CLEAR AND COMPLETE SANITARY AND WATER |
| | RISERS- SECTIONS 107.2.1 & 107.3.5.3 WPB. PLEASE NOTE |
| | THAT THE CHIEF PLUMBING INSPECTOR TIMOTHY LARGE IS NOW |
| | REQUIRING ALL MOP SINKS IN RESTAURANTS, OR OTHER |
| | FACILITIES WITH COOKING APPLIANCES, TO DRAIN INTO A |
| | GREASE INTERCEPTOR. THE HAND SINK SHALL DRAIN INTO THE |
| | SANITARY AND NOT INTO THE GREASE INTERCEPTOR. PLEASE |
| | DISREGARD PREVIOUS COMMENT AND CORRECT THE PLUMBING |
| | PLANS. IF YOU HAVE QUESTIONS PLEASE CONTACT MR. LARGE |
| | AT [email protected], 561-805-6692. |
| | |
| | 10) FAILED. P1 & P2: PLEASE PROVIDE A WATER RISER AND A |
| | WATER DISTRIBUTION LAYOUT PLAN. CONNECTION TO THE SODA |
| | FILTERING SYSTEM NOT SHOWN- SEE SCHEMATIC ON P-2. |
| | |
| | 10B) FAILED. SHOW THE SOURCE OF THE HOT WATER TO THE |
| | NEW AND EXISTING FIXTURES AND THE TEMPERATURE OF THE |
| | WATER- SECTION 607.1. PLEASE LABEL THE WATER HEATER AS |
| | NEW OR EXISTING ON THE PLANS. |
| | FOR NEW WATER HEATER INSTALLATIONS: PROVIDE AN |
| | EQUIPMENT SCHEDULE ON THE PLAN INDICATING MAKE, MODEL, |
| | GALLON SIZE, AND EFFICIENCY RATING. PLEASE NOTE THAT |
| | MANUFACTURER'S SPECIFICATIONS AND INSTALLATION MANUAL |
| | SHALL BE ONSITE AT TIME OF INSPECTION. PROVIDE PLUMBING |
| | PIPING DETAILS- COLD WATER FEED, SHUTOFF VALVE, CHECK |
| | VALVE, THERMAL EXPANSION TANK, RECIRCULATION PUMP, |
| | RELIEF VALVE, RELIEF VALVE DISCHARGE PIPING, DRAIN PAN, |
| | DRAIN PAN LINE, HW PIPE INSULATION- SEE SECTIONS 502 & |
| | 607 FBC P. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |