| 2021-01-15 11:55:50 | 2ND REVIEW FBC-2017 PLUMBING |
| | PERMIT- 20101298 |
| | 1/15/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | COMMENTS FROM THE 1ST REVIEW LISTED BELOW WILL BE |
| | MARKED AS PASSED OR FAILED. NOTES HAVE BEEN ADDED TO |
| | FAILED COMMENTS. PLEASE NOTE THE REQUESTED RESPONSE |
| | NARRATIVE FROM THE DESIGN PROFESSIONALS WHICH HELPS |
| | EXPEDITE THE REVIEW PROCESS WAS NOT SUBMITTED. IT |
| | APPEARS THAT CORRECTED PLUMBING PLANS BASED ON 1ST |
| | REVIEW COMMENTS WERE NOT PROVIDED. |
| | |
| | 1) FAILED. SHEET P1: PROVIDE PLUMBING FIXTURE |
| | CALCULATIONS IN ACCORDANCE WITH TABLE 403.1 FBC P. |
| | PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND |
| | PROVIDE NUMBER OF FIXTURES. PLEASE NOTE THAT DRINKING |
| | FOUNTAINS ARE REQUIRED FIXTURES FOR MERCANTILE |
| | OCCUPANCIES. THE EXCEPTION ALLOWED FOR RESTAURANTS |
| | SERVING DRINKING WATER TO CUSTOMERS UNDER SECTION 410.4 |
| | DOES NOT APPLY. THE DRINKING FOUNTAINS SHALL BE |
| | ACCESSIBLE IN COMPLIANCE WITH SECTIONS 211.2, & 602.1- |
| | 602.6 FBC ACC. |
| | |
| | 2) FAILED. P1: SHOW THE LOCATIONS OF THE DRINKING |
| | FOUNTAINS AND REVISE THE PLUMBING PIPING PLANS AND |
| | ISOMETRIC DRAWINGS ACCORDINGLY- SECTION 107.3.5.3 WPB. |
| | |
| | 3) FAILED. PROVIDE DRINKING FOUNTAIN INSTALLATION |
| | DETAILS SHOWING COMPLIANCE WITH SECTIONS 306, 307, AND |
| | 602 FBC ACC INCLUDING ELEVATION VIEWS SHOWING KNEE AND |
| | TOE CLEARANCES, SPOUT HEIGHTS, AND SPOUT LOCATIONS. |
| | INDICATE HOW THE FOUNTAINS WILL BE IN COMPLIANCE WITH |
| | SECTION 307.2- PROTRUDING OBJECTS INTO THE CIRCULATION |
| | PATH. |
| | |
| | 4) PASSED. GAS ISOMETRIC SUBMITTED WILL BE REVIEWED |
| | UNDER THIS PERMIT- A GAS SUB-PERMIT WILL BE REQUIRED. |
| | GREASE INTERCEPTOR INFORMATION PROVIDED WILL BE |
| | REVIEWED, HOWEVER A SEPARATE PRIMARY PERMIT IS REQUIRED |
| | FOR INSTALLATION. PLEASE NOTE THAT SUB-PERMITS |
| | SUBMITTED WITH MAIN PERMITS ARE ?NO-FEE?. A FEE WILL BE |
| | CHARGED FOR SUB-PERMITS APPLIED FOR AFTER MAIN PERMIT |
| | ISSUANCE. FINAL APPROVAL OF THE GAS PLANS HOWEVER WILL |
| | NOT REQUIRE SUBMITTAL OF THE APPLICATION. P1: PLEASE |
| | NOTE THAT SEPARATE PERMITS AND PLAN SUBMITTALS ARE |
| | REQUIRED FOR THE GAS PIPING AND GREASE INTERCEPTOR |
| | INSTALLATIONS- SECTION 105.1 & 107.2.1 WPB. A COMPLETE |
| | REVIEW OF THESE SYSTEMS HAS NOT BEEN PERFORMED AT THIS |
| | TIME. |
| | |
| | 5) FAILED. P1: THE ISOMETRIC DRAWINGS AT THE LEFT SIDE |
| | OF THE PLAN SHEET APPEAR TO BE CUT OFF AND INCOMPLETE. |
| | PLEASE PROVIDE CLEAR AND COMPLETE SANITARY AND WATER |
| | RISERS- SECTIONS 107.2.1 & 107.3.5.3 WPB. THE CORRECTED |
| | RISER SHALL IDENTIFY THE FIXTURES AND SHOW THE TYPE OF |
| | DRAIN CONNECTIONS- DIRECT OR INDIRECT, AND ALSO SHOW |
| | POINTS OF CONNECTIONS TO THE EXISTING SANITARY AND VENT |
| | SYSTEMS. A MINIMUM OF ONE VENT FOR THE BUILDING DRAIN |
| | SHALL EXTEND TO THE OUTDOORS- SECTION 904.1 FBC P. |
| | |
| | 6) FAILED. P1: IN ACCORDANCE WITH SECTION 1003.3.1 FBC |
| | P THE MOP SINK SHALL DRAIN INTO THE SANITARY AND NOT |
| | INTO THE GREASE WASTE LINE. PLEASE REVISE THE PLANS, |
| | SCHEDULE, AND CALCULATIONS ACCORDINGLY. |
| | |
| | 7) FAILED. P1: PLEASE PLACE A NOTE TO REQUIRE A COVER |
| | FOR THE MOP SINK WHEN NOT IN USE TO PREVENT RAINWATER |
| | AND OTHER FLUIDS AND WASTES FROM DRAINING INTO THE CITY |
| | SANITARY SYSTEM- SEC. 90-126 WPB CODE OF ORDINANCES. |
| | |
| | 8) FAILED. A2, P1, & P2: FLOOR SINKS ARE SPECIFIED IN |
| | THE DETAILS TO RECEIVE INDIRECT DRAINAGE FROM THE SODA |
| | DISPENSER AND ICE MACHINE. PLEASE ADD THE RECEPTORS AND |
| | PLUMBING PIPING TO THE DRAWINGS- SECTION 802.1 FBC P. |
| | PLEASE NOTE THAT CLEAR WATER WASTES FROM THESE |
| | RECEPTORS SHALL NOT DRAIN INTO THE GREASE INTERCEPTOR- |
| | SECTION 1003.3.1 FBC P. |
| | |
| | 9) FAILED. D-1: IT APPEARS THE SLAB CUT SHOWN WILL NOT |
| | PROVIDE A MEANS FOR THE DRAIN LINES FROM THE HAND SINK |
| | AND FLOOR SINKS IN THE KITCHEN TO CONNECT TO THE GREASE |
| | WASTE AND SANITARY DRAIN LINES. PLEASE PROVIDE THE SLAB |
| | CUTS AND SLAB REPAIR DETAILS- SECTION 107.2.1 WPB. |
| | PLEASE REVIEW THE PLUMBING PLANS AND REVISE D-1 TO SHOW |
| | THE SLAB CUTS RELATIVE TO THE UNDERSLAB DRAIN LINES. |
| | |
| | 10) P1 & P2: FAILED 10A-F. PLEASE PROVIDE A WATER RISER |
| | AND A WATER DISTRIBUTION LAYOUT PLAN: |
| | |
| | A) SHOW THE POINTS OF CONNECTIONS TO THE EXISTING WATER |
| | DISTRIBUTION LINES OR MAIN SERVICE LINE- SECTION 604.3 |
| | FBC P. |
| | |
| | B) SHOW THE SOURCE OF THE HOT WATER TO THE NEW AND |
| | EXISTING FIXTURES AND THE TEMPERATURE OF THE WATER- |
| | SECTION 607.1. |
| | |
| | C) SHOW LOCATIONS OF SHUT OFF VALVES TO FIXTURES AND |
| | EQUIPMENT- SECTION 606.2. |
| | |
| | D) SHOW THE LOCATIONS OF WATER HAMMER ARRESTORS- |
| | SECTION 604.9. |
| | |
| | E) SHOW THE LOCATIONS OF REQUIRED BACKFLOW PREVENTERS |
| | TO THE ICE MAKER, WATER FILTER, SODA DISPENSER, COFFEE |
| | AND CAPPUCCINO MACHINES- SECTION 608.3 AND TABLE 608.1 |
| | FBC P. |
| | |
| | F) SHOW HOW TEMPERED WATER IS BEING PROVIDED TO THE |
| | LAVATORY IN THE RESTROOM- SECTIONS 416.5 & 607.1.2. |
| | |
| | 11) FAILED. P1 & P2: PROVIDE TRAP PRIMERS FOR THE FLOOR |
| | DRAINS AND FLOOR SINKS AND SHOW LOCATIONS AND PIPING IN |
| | THE ISOMETRIC DRAWING- SECTION 1002.4.1 FBC P. |
| | |
| | 12) FAILED. P1 & P2: PROVIDE A COMPLETE PLUMBING |
| | FIXTURE SCHEDULE THAT INCLUDES THE MOP SINK, |
| | 3-COMPARTMENT SINK, HAND SINK, DRINKING FOUNTAIN, |
| | FAUCETS, FLOOR DRAINS, FLOOR SINKS- SECTION 107.2.1 |
| | WPB. |
| | |
| | 13) FAILED. PROVIDE A PLUMBING DEVICE SCHEDULE |
| | INCLUDING THE WATER HAMMER ARRESTORS, MIXING VALVE, |
| | BACKFLOW PREVENTERS, AND TRAP PRIMERS- SECTION 107.2.1 |
| | WPB. |
| | |
| | 14) PASSED. PROVIDE A PLUMBING SUB-PERMIT APPLICATION- |
| | SECTION 105.1 WPB. PLEASE NOTE THAT SUB-PERMITS |
| | SUBMITTED WITH MAIN PERMITS ARE "NO-FEE". A FEE WILL BE |
| | CHARGED FOR SUB-PERMITS APPLIED FOR AFTER MAIN PERMIT |
| | ISSUANCE. FINAL APPROVAL OF THE PLUMBING PLANS HOWEVER |
| | WILL NOT REQUIRE SUBMITTAL OF THE APPLICATION. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |