Plan Review Notes
Plan Review Notes For Permit 20101298
Permit Number 20101298
Review Stop P
Sequence Number 2
Notes
Date Text
2021-01-15 11:55:502ND REVIEW FBC-2017 PLUMBING
 PERMIT- 20101298
 1/15/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 COMMENTS FROM THE 1ST REVIEW LISTED BELOW WILL BE
 MARKED AS PASSED OR FAILED. NOTES HAVE BEEN ADDED TO
 FAILED COMMENTS. PLEASE NOTE THE REQUESTED RESPONSE
 NARRATIVE FROM THE DESIGN PROFESSIONALS WHICH HELPS
 EXPEDITE THE REVIEW PROCESS WAS NOT SUBMITTED. IT
 APPEARS THAT CORRECTED PLUMBING PLANS BASED ON 1ST
 REVIEW COMMENTS WERE NOT PROVIDED.
  
 1) FAILED. SHEET P1: PROVIDE PLUMBING FIXTURE
 CALCULATIONS IN ACCORDANCE WITH TABLE 403.1 FBC P.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDE NUMBER OF FIXTURES. PLEASE NOTE THAT DRINKING
 FOUNTAINS ARE REQUIRED FIXTURES FOR MERCANTILE
 OCCUPANCIES. THE EXCEPTION ALLOWED FOR RESTAURANTS
 SERVING DRINKING WATER TO CUSTOMERS UNDER SECTION 410.4
 DOES NOT APPLY. THE DRINKING FOUNTAINS SHALL BE
 ACCESSIBLE IN COMPLIANCE WITH SECTIONS 211.2, & 602.1-
 602.6 FBC ACC.
  
 2) FAILED. P1: SHOW THE LOCATIONS OF THE DRINKING
 FOUNTAINS AND REVISE THE PLUMBING PIPING PLANS AND
 ISOMETRIC DRAWINGS ACCORDINGLY- SECTION 107.3.5.3 WPB.
  
 3) FAILED. PROVIDE DRINKING FOUNTAIN INSTALLATION
 DETAILS SHOWING COMPLIANCE WITH SECTIONS 306, 307, AND
 602 FBC ACC INCLUDING ELEVATION VIEWS SHOWING KNEE AND
 TOE CLEARANCES, SPOUT HEIGHTS, AND SPOUT LOCATIONS.
 INDICATE HOW THE FOUNTAINS WILL BE IN COMPLIANCE WITH
 SECTION 307.2- PROTRUDING OBJECTS INTO THE CIRCULATION
 PATH.
  
 4) PASSED. GAS ISOMETRIC SUBMITTED WILL BE REVIEWED
 UNDER THIS PERMIT- A GAS SUB-PERMIT WILL BE REQUIRED.
 GREASE INTERCEPTOR INFORMATION PROVIDED WILL BE
 REVIEWED, HOWEVER A SEPARATE PRIMARY PERMIT IS REQUIRED
 FOR INSTALLATION. PLEASE NOTE THAT SUB-PERMITS
 SUBMITTED WITH MAIN PERMITS ARE ?NO-FEE?. A FEE WILL BE
 CHARGED FOR SUB-PERMITS APPLIED FOR AFTER MAIN PERMIT
 ISSUANCE. FINAL APPROVAL OF THE GAS PLANS HOWEVER WILL
 NOT REQUIRE SUBMITTAL OF THE APPLICATION. P1: PLEASE
 NOTE THAT SEPARATE PERMITS AND PLAN SUBMITTALS ARE
 REQUIRED FOR THE GAS PIPING AND GREASE INTERCEPTOR
 INSTALLATIONS- SECTION 105.1 & 107.2.1 WPB. A COMPLETE
 REVIEW OF THESE SYSTEMS HAS NOT BEEN PERFORMED AT THIS
 TIME.
  
 5) FAILED. P1: THE ISOMETRIC DRAWINGS AT THE LEFT SIDE
 OF THE PLAN SHEET APPEAR TO BE CUT OFF AND INCOMPLETE.
 PLEASE PROVIDE CLEAR AND COMPLETE SANITARY AND WATER
 RISERS- SECTIONS 107.2.1 & 107.3.5.3 WPB. THE CORRECTED
 RISER SHALL IDENTIFY THE FIXTURES AND SHOW THE TYPE OF
 DRAIN CONNECTIONS- DIRECT OR INDIRECT, AND ALSO SHOW
 POINTS OF CONNECTIONS TO THE EXISTING SANITARY AND VENT
 SYSTEMS. A MINIMUM OF ONE VENT FOR THE BUILDING DRAIN
 SHALL EXTEND TO THE OUTDOORS- SECTION 904.1 FBC P.
  
 6) FAILED. P1: IN ACCORDANCE WITH SECTION 1003.3.1 FBC
 P THE MOP SINK SHALL DRAIN INTO THE SANITARY AND NOT
 INTO THE GREASE WASTE LINE. PLEASE REVISE THE PLANS,
 SCHEDULE, AND CALCULATIONS ACCORDINGLY.
  
 7) FAILED. P1: PLEASE PLACE A NOTE TO REQUIRE A COVER
 FOR THE MOP SINK WHEN NOT IN USE TO PREVENT RAINWATER
 AND OTHER FLUIDS AND WASTES FROM DRAINING INTO THE CITY
 SANITARY SYSTEM- SEC. 90-126 WPB CODE OF ORDINANCES.
  
 8) FAILED. A2, P1, & P2: FLOOR SINKS ARE SPECIFIED IN
 THE DETAILS TO RECEIVE INDIRECT DRAINAGE FROM THE SODA
 DISPENSER AND ICE MACHINE. PLEASE ADD THE RECEPTORS AND
 PLUMBING PIPING TO THE DRAWINGS- SECTION 802.1 FBC P.
 PLEASE NOTE THAT CLEAR WATER WASTES FROM THESE
 RECEPTORS SHALL NOT DRAIN INTO THE GREASE INTERCEPTOR-
 SECTION 1003.3.1 FBC P.
  
 9) FAILED. D-1: IT APPEARS THE SLAB CUT SHOWN WILL NOT
 PROVIDE A MEANS FOR THE DRAIN LINES FROM THE HAND SINK
 AND FLOOR SINKS IN THE KITCHEN TO CONNECT TO THE GREASE
 WASTE AND SANITARY DRAIN LINES. PLEASE PROVIDE THE SLAB
 CUTS AND SLAB REPAIR DETAILS- SECTION 107.2.1 WPB.
 PLEASE REVIEW THE PLUMBING PLANS AND REVISE D-1 TO SHOW
 THE SLAB CUTS RELATIVE TO THE UNDERSLAB DRAIN LINES.
  
 10) P1 & P2: FAILED 10A-F. PLEASE PROVIDE A WATER RISER
 AND A WATER DISTRIBUTION LAYOUT PLAN:
  
 A) SHOW THE POINTS OF CONNECTIONS TO THE EXISTING WATER
 DISTRIBUTION LINES OR MAIN SERVICE LINE- SECTION 604.3
 FBC P.
  
 B) SHOW THE SOURCE OF THE HOT WATER TO THE NEW AND
 EXISTING FIXTURES AND THE TEMPERATURE OF THE WATER-
 SECTION 607.1.
  
 C) SHOW LOCATIONS OF SHUT OFF VALVES TO FIXTURES AND
 EQUIPMENT- SECTION 606.2.
  
 D) SHOW THE LOCATIONS OF WATER HAMMER ARRESTORS-
 SECTION 604.9.
  
 E) SHOW THE LOCATIONS OF REQUIRED BACKFLOW PREVENTERS
 TO THE ICE MAKER, WATER FILTER, SODA DISPENSER, COFFEE
 AND CAPPUCCINO MACHINES- SECTION 608.3 AND TABLE 608.1
 FBC P.
  
 F) SHOW HOW TEMPERED WATER IS BEING PROVIDED TO THE
 LAVATORY IN THE RESTROOM- SECTIONS 416.5 & 607.1.2.
  
 11) FAILED. P1 & P2: PROVIDE TRAP PRIMERS FOR THE FLOOR
 DRAINS AND FLOOR SINKS AND SHOW LOCATIONS AND PIPING IN
 THE ISOMETRIC DRAWING- SECTION 1002.4.1 FBC P.
  
 12) FAILED. P1 & P2: PROVIDE A COMPLETE PLUMBING
 FIXTURE SCHEDULE THAT INCLUDES THE MOP SINK,
 3-COMPARTMENT SINK, HAND SINK, DRINKING FOUNTAIN,
 FAUCETS, FLOOR DRAINS, FLOOR SINKS- SECTION 107.2.1
 WPB.
  
 13) FAILED. PROVIDE A PLUMBING DEVICE SCHEDULE
 INCLUDING THE WATER HAMMER ARRESTORS, MIXING VALVE,
 BACKFLOW PREVENTERS, AND TRAP PRIMERS- SECTION 107.2.1
 WPB.
  
 14) PASSED. PROVIDE A PLUMBING SUB-PERMIT APPLICATION-
 SECTION 105.1 WPB. PLEASE NOTE THAT SUB-PERMITS
 SUBMITTED WITH MAIN PERMITS ARE "NO-FEE". A FEE WILL BE
 CHARGED FOR SUB-PERMITS APPLIED FOR AFTER MAIN PERMIT
 ISSUANCE. FINAL APPROVAL OF THE PLUMBING PLANS HOWEVER
 WILL NOT REQUIRE SUBMITTAL OF THE APPLICATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  