| 2020-12-09 11:56:42 | 1ST REVIEW FBC-2017 PLUMBING |
| | PERMIT- 20101298 |
| | 12/9/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET P1: PROVIDE PLUMBING FIXTURE CALCULATIONS IN |
| | ACCORDANCE WITH TABLE 403.1 FBC P. PROVIDE A SCHEDULE |
| | THAT INDICATES THE REQUIRED AND PROVIDE NUMBER OF |
| | FIXTURES. PLEASE NOTE THAT DRINKING FOUNTAINS ARE |
| | REQUIRED FIXTURES FOR MERCANTILE OCCUPANCIES. THE |
| | EXCEPTION ALLOWED FOR RESTAURANTS SERVING DRINKING |
| | WATER TO CUSTOMERS UNDER SECTION 410.4 DOES NOT APPLY. |
| | THE DRINKING FOUNTAINS SHALL BE ACCESSIBLE IN |
| | COMPLIANCE WITH SECTIONS 211.2, & 602.1- 602.6 FBC ACC. |
| | |
| | 2) P1: SHOW THE LOCATIONS OF THE DRINKING FOUNTAINS AND |
| | REVISE THE PLUMBING PIPING PLANS AND ISOMETRIC DRAWINGS |
| | ACCORDINGLY- SECTION 107.3.5.3 WPB. |
| | |
| | 3) PROVIDE DRINKING FOUNTAIN INSTALLATION DETAILS |
| | SHOWING COMPLIANCE WITH SECTIONS 306, 307, AND 602 FBC |
| | ACC INCLUDING ELEVATION VIEWS SHOWING KNEE AND TOE |
| | CLEARANCES, SPOUT HEIGHTS, AND SPOUT LOCATIONS. |
| | INDICATE HOW THE FOUNTAINS WILL BE IN COMPLIANCE WITH |
| | SECTION 307.2- PROTRUDING OBJECTS INTO THE CIRCULATION |
| | PATH. |
| | |
| | 4) P1: PLEASE NOTE THAT SEPARATE PERMITS AND PLAN |
| | SUBMITTALS ARE REQUIRED FOR THE GAS PIPING AND GREASE |
| | INTERCEPTOR INSTALLATIONS- SECTION 105.1 & 107.2.1 WPB. |
| | A COMPLETE REVIEW OF THESE SYSTEMS HAS NOT BEEN |
| | PERFORMED AT THIS TIME. |
| | |
| | 5) P1: THE ISOMETRIC DRAWINGS AT THE LEFT SIDE OF THE |
| | PLAN SHEET APPEAR TO BE CUT OFF AND INCOMPLETE. PLEASE |
| | PROVIDE CLEAR AND COMPLETE SANITARY AND WATER RISERS- |
| | SECTIONS 107.2.1 & 107.3.5.3 WPB. |
| | |
| | 6) P1: IN ACCORDANCE WITH SECTION 1003.3.1 FBC P THE |
| | MOP SINK SHALL DRAIN INTO THE SANITARY AND NOT INTO THE |
| | GREASE WASTE LINE. PLEASE REVISE THE PLANS, SCHEDULE, |
| | AND CALCULATIONS ACCORDINGLY. |
| | |
| | 7) P1: PLEASE PLACE A NOTE TO REQUIRE A COVER FOR THE |
| | MOP SINK WHEN NOT IN USE TO PREVENT RAINWATER AND OTHER |
| | FLUIDS AND WASTES FROM DRAINING INTO THE CITY SANITARY |
| | SYSTEM- SEC. 90-126 WPB CODE OF ORDINANCES. |
| | |
| | 8) A2, P1, & P2: FLOOR SINKS ARE SPECIFIED IN THE |
| | DETAILS TO RECEIVE INDIRECT DRAINAGE FROM THE SODA |
| | DISPENSER AND ICE MACHINE. PLEASE ADD THE RECEPTORS AND |
| | PLUMBING PIPING TO THE DRAWINGS- SECTION 802.1 FBC P. |
| | PLEASE NOTE THAT CLEAR WATER WASTES FROM THESE |
| | RECEPTORS SHALL NOT DRAIN INTO THE GREASE INTERCEPTOR- |
| | SECTION 1003.3.1 FBC P. |
| | |
| | 9) D-1: IT APPEARS THE SLAB CUT SHOWN WILL NOT PROVIDE |
| | A MEANS FOR THE DRAIN LINES FROM THE HAND SINK AND |
| | FLOOR SINKS IN THE KITCHEN TO CONNECT TO THE GREASE |
| | WASTE AND SANITARY DRAIN LINES. PLEASE PROVIDE THE SLAB |
| | CUTS AND SLAB REPAIR DETAILS- SECTION 107.2.1 WPB. |
| | |
| | 10) P1 & P2: PLEASE PROVIDE A WATER RISER AND A WATER |
| | DISTRIBUTION LAYOUT PLAN: |
| | |
| | A) SHOW THE POINTS OF CONNECTIONS TO THE EXISTING WATER |
| | DISTRIBUTION LINES OR MAIN SERVICE LINE- SECTION 604.3 |
| | FBC P. |
| | |
| | B) SHOW THE SOURCE OF THE HOT WATER TO THE NEW AND |
| | EXISTING FIXTURES AND THE TEMPERATURE OF THE WATER- |
| | SECTION 607.1. |
| | |
| | C) SHOW LOCATIONS OF SHUT OFF VALVES TO FIXTURES AND |
| | EQUIPMENT- SECTION 606.2. |
| | |
| | D) SHOW THE LOCATIONS OF WATER HAMMER ARRESTORS- |
| | SECTION 604.9. |
| | |
| | E) SHOW THE LOCATIONS OF REQUIRED BACKFLOW PREVENTERS |
| | TO THE ICE MAKER, WATER FILTER, SODA DISPENSER, COFFEE |
| | AND CAPPUCCINO MACHINES- SECTION 608.3 AND TABLE 608.1 |
| | FBC P. |
| | |
| | F) SHOW HOW TEMPERED WATER IS BEING PROVIDED TO THE |
| | LAVATORY IN THE RESTROOM- SECTIONS 416.5 & 607.1.2. |
| | |
| | 11) P1 & P2: PROVIDE TRAP PRIMERS FOR THE FLOOR DRAINS |
| | AND FLOOR SINKS AND SHOW LOCATIONS AND PIPING IN THE |
| | ISOMETRIC DRAWING- SECTION 1002.4.1 FBC P. |
| | |
| | 12) P1 & P2: PROVIDE A COMPLETE PLUMBING FIXTURE |
| | SCHEDULE THAT INCLUDES THE MOP SINK, 3-COMPARTMENT |
| | SINK, HAND SINK, DRINKING FOUNTAIN, FAUCETS, FLOOR |
| | DRAINS, FLOOR SINKS, DOME DRAIN- SECTION 107.2.1 WPB. |
| | |
| | 13) PROVIDE A PLUMBING DEVICE SCHEDULE INCLUDING THE |
| | WATER HAMMER ARRESTORS, MIXING VALVE, BACKFLOW |
| | PREVENTERS, AND TRAP PRIMERS- SECTION 107.2.1 WPB. |
| | |
| | 14) PROVIDE A PLUMBING SUB-PERMIT APPLICATION- SECTION |
| | 105.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |
| 2020-12-09 11:56:20 | 1ST REVIEW FBC-2017 PLUMBING |
| | PERMIT- 20101298 |
| | 12/9/2020 |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | PLAN REVIEW RESULTS: DENIED. |
| | 1) SHEET P1: PROVIDE PLUMBING FIXTURE CALCULATIONS IN |
| | ACCORDANCE WITH TABLE 403.1 FBC P. PROVIDE A SCHEDULE |
| | THAT INDICATES THE REQUIRED AND PROVIDE NUMBER OF |
| | FIXTURES. PLEASE NOTE THAT DRINKING FOUNTAINS ARE |
| | REQUIRED FIXTURES FOR MERCANTILE OCCUPANCIES. THE |
| | EXCEPTION ALLOWED FOR RESTAURANTS SERVING DRINKING |
| | WATER TO CUSTOMERS UNDER SECTION 410.4 DOES NOT APPLY. |
| | THE DRINKING FOUNTAINS SHALL BE ACCESSIBLE IN |
| | COMPLIANCE WITH SECTIONS 211.2, & 602.1- 602.6 FBC ACC. |
| | 2) P1: SHOW THE LOCATIONS OF THE DRINKING FOUNTAINS AND |
| | REVISE THE PLUMBING PIPING PLANS AND ISOMETRIC DRAWINGS |
| | ACCORDINGLY- SECTION 107.3.5.3 WPB. |
| | 3) PROVIDE DRINKING FOUNTAIN INSTALLATION DETAILS |
| | SHOWING COMPLIANCE WITH SECTIONS 306, 307, AND 602 FBC |
| | ACC INCLUDING ELEVATION VIEWS SHOWING KNEE AND TOE |
| | CLEARANCES, SPOUT HEIGHTS, AND SPOUT LOCATIONS. |
| | INDICATE HOW THE FOUNTAINS WILL BE IN COMPLIANCE WITH |
| | SECTION 307.2- PROTRUDING OBJECTS INTO THE CIRCULATION |
| | PATH. |
| | 4) P1: PLEASE NOTE THAT SEPARATE PERMITS AND PLAN |
| | SUBMITTALS ARE REQUIRED FOR THE GAS PIPING AND GREASE |
| | INTERCEPTOR INSTALLATIONS- SECTION 105.1 & 107.2.1 WPB. |
| | A COMPLETE REVIEW OF THESE SYSTEMS HAS NOT BEEN |
| | PERFORMED AT THIS TIME. |
| | 5) P1: THE ISOMETRIC DRAWINGS AT THE LEFT SIDE OF THE |
| | PLAN SHEET APPEAR TO BE CUT OFF AND INCOMPLETE. PLEASE |
| | PROVIDE CLEAR AND COMPLETE SANITARY AND WATER RISERS- |
| | SECTIONS 107.2.1 & 107.3.5.3 WPB. |
| | 6) P1: IN ACCORDANCE WITH SECTION 1003.3.1 FBC P THE |
| | MOP SINK SHALL DRAIN INTO THE SANITARY AND NOT INTO THE |
| | GREASE WASTE LINE. PLEASE REVISE THE PLANS, SCHEDULE, |
| | AND CALCULATIONS ACCORDINGLY. |
| | 7) P1: PLEASE PLACE A NOTE TO REQUIRE A COVER FOR THE |
| | MOP SINK WHEN NOT IN USE TO PREVENT RAINWATER AND OTHER |
| | FLUIDS AND WASTES FROM DRAINING INTO THE CITY SANITARY |
| | SYSTEM- SEC. 90-126 WPB CODE OF ORDINANCES. |
| | 8) A2, P1, & P2: FLOOR SINKS ARE SPECIFIED IN THE |
| | DETAILS TO RECEIVE INDIRECT DRAINAGE FROM THE SODA |
| | DISPENSER AND ICE MACHINE. PLEASE ADD THE RECEPTORS AND |
| | PLUMBING PIPING TO THE DRAWINGS- SECTION 802.1 FBC P. |
| | PLEASE NOTE THAT CLEAR WATER WASTES FROM THESE |
| | RECEPTORS SHALL NOT DRAIN INTO THE GREASE INTERCEPTOR- |
| | SECTION 1003.3.1 FBC P. |
| | 9) D-1: IT APPEARS THE SLAB CUT SHOWN WILL NOT PROVIDE |
| | A MEANS FOR THE DRAIN LINES FROM THE HAND SINK AND |
| | FLOOR SINKS IN THE KITCHEN TO CONNECT TO THE GREASE |
| | WASTE AND SANITARY DRAIN LINES- SECTION 107.2.1 WPB. |
| | 10) P1 & P2: PLEASE PROVIDE A WATER RISER AND A WATER |
| | DISTRIBUTION LAYOUT PLAN: |
| | A) SHOW THE POINTS OF CONNECTIONS TO THE EXISTING WATER |
| | DISTRIBUTION LINES OR MAIN SERVICE LINE- SECTION 604.3 |
| | FBC P. |
| | B) SHOW THE SOURCE OF THE HOT WATER TO THE NEW AND |
| | EXISTING FIXTURES AND THE TEMPERATURE OF THE WATER- |
| | SECTION 607.1. |
| | C) SHOW LOCATIONS OF SHUT OFF VALVES TO FIXTURES AND |
| | EQUIPMENT- SECTION 606.2. |
| | D) SHOW THE LOCATIONS OF WATER HAMMER ARRESTORS- |
| | SECTION 604.9. |
| | E) SHOW THE LOCATIONS OF REQUIRED BACKFLOW PREVENTERS |
| | TO THE ICE MAKER, WATER FILTER, SODA DISPENSER, COFFEE |
| | AND CAPPUCCINO MACHINES- SECTION 608.3 AND TABLE 608.1 |
| | FBC P. |
| | F) SHOW HOW TEMPERED WATER IS BEING PROVIDED TO THE |
| | LAVATORY IN THE RESTROOM- SECTIONS 416.5 & 607.1.2. |
| | 11) P1 & P2: PROVIDE TRAP PRIMERS FOR THE FLOOR DRAINS |
| | AND FLOOR SINKS AND SHOW LOCATIONS AND PIPING IN THE |
| | ISOMETRIC DRAWING- SECTION 1002.4.1 FBC P. |
| | 12) P1 & P2: PROVIDE A COMPLETE PLUMBING FIXTURE |
| | SCHEDULE THAT INCLUDES THE MOP SINK, 3-COMPARTMENT |
| | SINK, HAND SINK, DRINKING FOUNTAIN, FAUCETS, FLOOR |
| | DRAINS, FLOOR SINKS, DOME DRAIN- SECTION 107.2.1 WPB. |
| | 13) PROVIDE A PLUMBING DEVICE SCHEDULE INCLUDING THE |
| | WATER HAMMER ARRESTORS, MIXING VALVE, BACKFLOW |
| | PREVENTERS, AND TRAP PRIMERS- SECTION 107.2.1 WPB. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |