Plan Review Notes
Plan Review Notes For Permit 20101298
Permit Number 20101298
Review Stop P
Sequence Number 1
Notes
Date Text
2020-12-09 11:56:421ST REVIEW FBC-2017 PLUMBING
 PERMIT- 20101298
 12/9/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P1: PROVIDE PLUMBING FIXTURE CALCULATIONS IN
 ACCORDANCE WITH TABLE 403.1 FBC P. PROVIDE A SCHEDULE
 THAT INDICATES THE REQUIRED AND PROVIDE NUMBER OF
 FIXTURES. PLEASE NOTE THAT DRINKING FOUNTAINS ARE
 REQUIRED FIXTURES FOR MERCANTILE OCCUPANCIES. THE
 EXCEPTION ALLOWED FOR RESTAURANTS SERVING DRINKING
 WATER TO CUSTOMERS UNDER SECTION 410.4 DOES NOT APPLY.
 THE DRINKING FOUNTAINS SHALL BE ACCESSIBLE IN
 COMPLIANCE WITH SECTIONS 211.2, & 602.1- 602.6 FBC ACC.
  
 2) P1: SHOW THE LOCATIONS OF THE DRINKING FOUNTAINS AND
 REVISE THE PLUMBING PIPING PLANS AND ISOMETRIC DRAWINGS
 ACCORDINGLY- SECTION 107.3.5.3 WPB.
  
 3) PROVIDE DRINKING FOUNTAIN INSTALLATION DETAILS
 SHOWING COMPLIANCE WITH SECTIONS 306, 307, AND 602 FBC
 ACC INCLUDING ELEVATION VIEWS SHOWING KNEE AND TOE
 CLEARANCES, SPOUT HEIGHTS, AND SPOUT LOCATIONS.
 INDICATE HOW THE FOUNTAINS WILL BE IN COMPLIANCE WITH
 SECTION 307.2- PROTRUDING OBJECTS INTO THE CIRCULATION
 PATH.
  
 4) P1: PLEASE NOTE THAT SEPARATE PERMITS AND PLAN
 SUBMITTALS ARE REQUIRED FOR THE GAS PIPING AND GREASE
 INTERCEPTOR INSTALLATIONS- SECTION 105.1 & 107.2.1 WPB.
 A COMPLETE REVIEW OF THESE SYSTEMS HAS NOT BEEN
 PERFORMED AT THIS TIME.
  
 5) P1: THE ISOMETRIC DRAWINGS AT THE LEFT SIDE OF THE
 PLAN SHEET APPEAR TO BE CUT OFF AND INCOMPLETE. PLEASE
 PROVIDE CLEAR AND COMPLETE SANITARY AND WATER RISERS-
 SECTIONS 107.2.1 & 107.3.5.3 WPB.
  
 6) P1: IN ACCORDANCE WITH SECTION 1003.3.1 FBC P THE
 MOP SINK SHALL DRAIN INTO THE SANITARY AND NOT INTO THE
 GREASE WASTE LINE. PLEASE REVISE THE PLANS, SCHEDULE,
 AND CALCULATIONS ACCORDINGLY.
  
 7) P1: PLEASE PLACE A NOTE TO REQUIRE A COVER FOR THE
 MOP SINK WHEN NOT IN USE TO PREVENT RAINWATER AND OTHER
 FLUIDS AND WASTES FROM DRAINING INTO THE CITY SANITARY
 SYSTEM- SEC. 90-126 WPB CODE OF ORDINANCES.
  
 8) A2, P1, & P2: FLOOR SINKS ARE SPECIFIED IN THE
 DETAILS TO RECEIVE INDIRECT DRAINAGE FROM THE SODA
 DISPENSER AND ICE MACHINE. PLEASE ADD THE RECEPTORS AND
 PLUMBING PIPING TO THE DRAWINGS- SECTION 802.1 FBC P.
 PLEASE NOTE THAT CLEAR WATER WASTES FROM THESE
 RECEPTORS SHALL NOT DRAIN INTO THE GREASE INTERCEPTOR-
 SECTION 1003.3.1 FBC P.
  
 9) D-1: IT APPEARS THE SLAB CUT SHOWN WILL NOT PROVIDE
 A MEANS FOR THE DRAIN LINES FROM THE HAND SINK AND
 FLOOR SINKS IN THE KITCHEN TO CONNECT TO THE GREASE
 WASTE AND SANITARY DRAIN LINES. PLEASE PROVIDE THE SLAB
 CUTS AND SLAB REPAIR DETAILS- SECTION 107.2.1 WPB.
  
 10) P1 & P2: PLEASE PROVIDE A WATER RISER AND A WATER
 DISTRIBUTION LAYOUT PLAN:
  
 A) SHOW THE POINTS OF CONNECTIONS TO THE EXISTING WATER
 DISTRIBUTION LINES OR MAIN SERVICE LINE- SECTION 604.3
 FBC P.
  
 B) SHOW THE SOURCE OF THE HOT WATER TO THE NEW AND
 EXISTING FIXTURES AND THE TEMPERATURE OF THE WATER-
 SECTION 607.1.
  
 C) SHOW LOCATIONS OF SHUT OFF VALVES TO FIXTURES AND
 EQUIPMENT- SECTION 606.2.
  
 D) SHOW THE LOCATIONS OF WATER HAMMER ARRESTORS-
 SECTION 604.9.
  
 E) SHOW THE LOCATIONS OF REQUIRED BACKFLOW PREVENTERS
 TO THE ICE MAKER, WATER FILTER, SODA DISPENSER, COFFEE
 AND CAPPUCCINO MACHINES- SECTION 608.3 AND TABLE 608.1
 FBC P.
  
 F) SHOW HOW TEMPERED WATER IS BEING PROVIDED TO THE
 LAVATORY IN THE RESTROOM- SECTIONS 416.5 & 607.1.2.
  
 11) P1 & P2: PROVIDE TRAP PRIMERS FOR THE FLOOR DRAINS
 AND FLOOR SINKS AND SHOW LOCATIONS AND PIPING IN THE
 ISOMETRIC DRAWING- SECTION 1002.4.1 FBC P.
  
 12) P1 & P2: PROVIDE A COMPLETE PLUMBING FIXTURE
 SCHEDULE THAT INCLUDES THE MOP SINK, 3-COMPARTMENT
 SINK, HAND SINK, DRINKING FOUNTAIN, FAUCETS, FLOOR
 DRAINS, FLOOR SINKS, DOME DRAIN- SECTION 107.2.1 WPB.
  
 13) PROVIDE A PLUMBING DEVICE SCHEDULE INCLUDING THE
 WATER HAMMER ARRESTORS, MIXING VALVE, BACKFLOW
 PREVENTERS, AND TRAP PRIMERS- SECTION 107.2.1 WPB.
  
 14) PROVIDE A PLUMBING SUB-PERMIT APPLICATION- SECTION
 105.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
2020-12-09 11:56:201ST REVIEW FBC-2017 PLUMBING
 PERMIT- 20101298
 12/9/2020
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
 PLAN REVIEW RESULTS: DENIED.
 1) SHEET P1: PROVIDE PLUMBING FIXTURE CALCULATIONS IN
 ACCORDANCE WITH TABLE 403.1 FBC P. PROVIDE A SCHEDULE
 THAT INDICATES THE REQUIRED AND PROVIDE NUMBER OF
 FIXTURES. PLEASE NOTE THAT DRINKING FOUNTAINS ARE
 REQUIRED FIXTURES FOR MERCANTILE OCCUPANCIES. THE
 EXCEPTION ALLOWED FOR RESTAURANTS SERVING DRINKING
 WATER TO CUSTOMERS UNDER SECTION 410.4 DOES NOT APPLY.
 THE DRINKING FOUNTAINS SHALL BE ACCESSIBLE IN
 COMPLIANCE WITH SECTIONS 211.2, & 602.1- 602.6 FBC ACC.
 2) P1: SHOW THE LOCATIONS OF THE DRINKING FOUNTAINS AND
 REVISE THE PLUMBING PIPING PLANS AND ISOMETRIC DRAWINGS
 ACCORDINGLY- SECTION 107.3.5.3 WPB.
 3) PROVIDE DRINKING FOUNTAIN INSTALLATION DETAILS
 SHOWING COMPLIANCE WITH SECTIONS 306, 307, AND 602 FBC
 ACC INCLUDING ELEVATION VIEWS SHOWING KNEE AND TOE
 CLEARANCES, SPOUT HEIGHTS, AND SPOUT LOCATIONS.
 INDICATE HOW THE FOUNTAINS WILL BE IN COMPLIANCE WITH
 SECTION 307.2- PROTRUDING OBJECTS INTO THE CIRCULATION
 PATH.
 4) P1: PLEASE NOTE THAT SEPARATE PERMITS AND PLAN
 SUBMITTALS ARE REQUIRED FOR THE GAS PIPING AND GREASE
 INTERCEPTOR INSTALLATIONS- SECTION 105.1 & 107.2.1 WPB.
 A COMPLETE REVIEW OF THESE SYSTEMS HAS NOT BEEN
 PERFORMED AT THIS TIME.
 5) P1: THE ISOMETRIC DRAWINGS AT THE LEFT SIDE OF THE
 PLAN SHEET APPEAR TO BE CUT OFF AND INCOMPLETE. PLEASE
 PROVIDE CLEAR AND COMPLETE SANITARY AND WATER RISERS-
 SECTIONS 107.2.1 & 107.3.5.3 WPB.
 6) P1: IN ACCORDANCE WITH SECTION 1003.3.1 FBC P THE
 MOP SINK SHALL DRAIN INTO THE SANITARY AND NOT INTO THE
 GREASE WASTE LINE. PLEASE REVISE THE PLANS, SCHEDULE,
 AND CALCULATIONS ACCORDINGLY.
 7) P1: PLEASE PLACE A NOTE TO REQUIRE A COVER FOR THE
 MOP SINK WHEN NOT IN USE TO PREVENT RAINWATER AND OTHER
 FLUIDS AND WASTES FROM DRAINING INTO THE CITY SANITARY
 SYSTEM- SEC. 90-126 WPB CODE OF ORDINANCES.
 8) A2, P1, & P2: FLOOR SINKS ARE SPECIFIED IN THE
 DETAILS TO RECEIVE INDIRECT DRAINAGE FROM THE SODA
 DISPENSER AND ICE MACHINE. PLEASE ADD THE RECEPTORS AND
 PLUMBING PIPING TO THE DRAWINGS- SECTION 802.1 FBC P.
 PLEASE NOTE THAT CLEAR WATER WASTES FROM THESE
 RECEPTORS SHALL NOT DRAIN INTO THE GREASE INTERCEPTOR-
 SECTION 1003.3.1 FBC P.
 9) D-1: IT APPEARS THE SLAB CUT SHOWN WILL NOT PROVIDE
 A MEANS FOR THE DRAIN LINES FROM THE HAND SINK AND
 FLOOR SINKS IN THE KITCHEN TO CONNECT TO THE GREASE
 WASTE AND SANITARY DRAIN LINES- SECTION 107.2.1 WPB.
 10) P1 & P2: PLEASE PROVIDE A WATER RISER AND A WATER
 DISTRIBUTION LAYOUT PLAN:
 A) SHOW THE POINTS OF CONNECTIONS TO THE EXISTING WATER
 DISTRIBUTION LINES OR MAIN SERVICE LINE- SECTION 604.3
 FBC P.
 B) SHOW THE SOURCE OF THE HOT WATER TO THE NEW AND
 EXISTING FIXTURES AND THE TEMPERATURE OF THE WATER-
 SECTION 607.1.
 C) SHOW LOCATIONS OF SHUT OFF VALVES TO FIXTURES AND
 EQUIPMENT- SECTION 606.2.
 D) SHOW THE LOCATIONS OF WATER HAMMER ARRESTORS-
 SECTION 604.9.
 E) SHOW THE LOCATIONS OF REQUIRED BACKFLOW PREVENTERS
 TO THE ICE MAKER, WATER FILTER, SODA DISPENSER, COFFEE
 AND CAPPUCCINO MACHINES- SECTION 608.3 AND TABLE 608.1
 FBC P.
 F) SHOW HOW TEMPERED WATER IS BEING PROVIDED TO THE
 LAVATORY IN THE RESTROOM- SECTIONS 416.5 & 607.1.2.
 11) P1 & P2: PROVIDE TRAP PRIMERS FOR THE FLOOR DRAINS
 AND FLOOR SINKS AND SHOW LOCATIONS AND PIPING IN THE
 ISOMETRIC DRAWING- SECTION 1002.4.1 FBC P.
 12) P1 & P2: PROVIDE A COMPLETE PLUMBING FIXTURE
 SCHEDULE THAT INCLUDES THE MOP SINK, 3-COMPARTMENT
 SINK, HAND SINK, DRINKING FOUNTAIN, FAUCETS, FLOOR
 DRAINS, FLOOR SINKS, DOME DRAIN- SECTION 107.2.1 WPB.
 13) PROVIDE A PLUMBING DEVICE SCHEDULE INCLUDING THE
 WATER HAMMER ARRESTORS, MIXING VALVE, BACKFLOW
 PREVENTERS, AND TRAP PRIMERS- SECTION 107.2.1 WPB.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER