| 2021-01-15 11:51:23 | 1ST REVIEW FBC-2017 FUEL GAS |
| | PERMIT- 20101298 |
| | 1/15/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS P3 & A2: THE EQUIPMENT LIST ON A2 SHOWS GAS |
| | STOVE, DOUBLE FRYER AND FLAT GRILL. P3 SHOWS A COOKTOP, |
| | FRYER AND GRIDDLE. PLEASE SUBMIT MANUFACTURER?S |
| | SPECIFICATIONS FOR THE APPLIANCES SHOWING GAS BTUH |
| | LOADS AND INPUT PRESSURES- SECTION 305.1 FBC FG. |
| | |
| | 2) P3: INDICATE HOW COMBUSTION AIR WILL BE PROVIDED FOR |
| | THE COOKING APPLIANCES AND PROVIDE CALCULATIONS- |
| | SECTION 304.1 FBC FG. |
| | |
| | 3) P3: SHOW THE LOCATION OF THE AUTOMATIC GAS SHUTOFF |
| | VALVE WHICH IS REQUIRED TO BE CONNECTED TO THE HOOD |
| | FIRE SUPPRESSION SYSTEM- SECTION 10.4.1 NFPA 96. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |