Plan Review Notes
Plan Review Notes For Permit 20101298
Permit Number 20101298
Review Stop G
Sequence Number 1
Notes
Date Text
2021-01-15 11:51:231ST REVIEW FBC-2017 FUEL GAS
 PERMIT- 20101298
 1/15/2021
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS P3 & A2: THE EQUIPMENT LIST ON A2 SHOWS GAS
 STOVE, DOUBLE FRYER AND FLAT GRILL. P3 SHOWS A COOKTOP,
 FRYER AND GRIDDLE. PLEASE SUBMIT MANUFACTURER?S
 SPECIFICATIONS FOR THE APPLIANCES SHOWING GAS BTUH
 LOADS AND INPUT PRESSURES- SECTION 305.1 FBC FG.
  
 2) P3: INDICATE HOW COMBUSTION AIR WILL BE PROVIDED FOR
 THE COOKING APPLIANCES AND PROVIDE CALCULATIONS-
 SECTION 304.1 FBC FG.
  
 3) P3: SHOW THE LOCATION OF THE AUTOMATIC GAS SHUTOFF
 VALVE WHICH IS REQUIRED TO BE CONNECTED TO THE HOOD
 FIRE SUPPRESSION SYSTEM- SECTION 10.4.1 NFPA 96.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB
  