Plan Review Notes
Plan Review Notes For Permit 20101298
Permit Number 20101298
Review Stop E
Sequence Number 1
Notes
Date Text
2020-12-10 09:52:49CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 REVIEW STATUS: FAILED.
  
 1) IT SEEMS THAT ONLY HALF OF THE PANEL SCHEDULE IS
 SHOWN ON DRAWINGS. FBC 107
 2) ALL RECEPTACLES IN FOOD PREPARATION AREAS MUST BE
 GFCI PROTECTED NEC 210.8(B)
 3) PLEASE SHOW CIRCUITS FOR AHU 1 AND AHU 2 ON POWER
 LAYOUT AND PANEL SCHEDULE FBC 107
 4) EXISTING GROUNDING ELECTRODE CONDUCTOR SHOWN IS SIZE
 #2 CU. PLEASE SPECIFY TYPE OF GROUNDING ELECTRODE
 SYSTEM USED TO DETERMINE COMPLIANCE WITH NEC 250-66
 5) GFCI, WP RECEPTACLES REQUIRED FOR ALL AC, CU, AHU
 UNITS AS PER NEC 210-63
 6) PLEASE SUBMIT LOAD CALCULATION FOR EXISTING PANEL A
 FBC 107
  
 END OF COMMENTS.
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 SINCERELY,
  
 ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved