Plan Review Notes
Plan Review Notes For Permit 20101298
Permit Number 20101298
Review Stop B
Sequence Number 1
Notes
Date Text
2020-11-19 09:58:50WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20101298
 ADD: 701 BELVEDERE RD.
 CONT: TORNADO ROOFING AND CONTRACTING, INC.
 TEL: 954-968-8155
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. NOV. 19TH/2020
 ACTION: DENIED
  
 1) SHEET T-1 THE COVERSHEET/ CODE RESEARCH:
 1A) THE PLANS STATE THE GOVERNING CODES ARE THE 2010
 EDITION OF THE FLORIDA BUILDING CODE AND EXISTING
 BUILDING CODE (CHAPTER 3401.1). PLEASE NOTE THE 6TH
 EDITION (2017) OF THE FLORIDA BUILDING CODE WENT INTO
 EFFECT ON DEC. 31,2017. PLEASE UPDATE THE CODE EDITION
 AND YEAR.
  
 1B) CONSTRUCTION TYPE STATES IIIA UNPROTECTED: FULLY
 SPRINKLERED. PLEASE REFER TO THE 2017 FBC-B TABLE 601.
 IN ALL 5 BUILDING CATEGORY TYPES THE TYPE (A) BUILDING
 HAS AT LEAST A 1-HOUR PROTECTION SO THE BUILDING IS
 PROTECTED. THE PLANS ALSO STATE THIS BUILDING IS FIRE
 SPRINKLERED BUT NO FIRE SPRINKLER PLAN WAS INCLUDED IN
 THE SET OF DOCUMENTS? 107.2.1.2. ADDITIONAL INFORMATION
 IS REQUIRED.
  
 1C) THE DESIGNER OF RECORD INDICATES UNDER THE EXISTING
 BUILDING CODE THIS BUILDING IS A LEVEL III ALTERATION.
 PLEASE REVIEW THE DEFINITION FOR LEVEL III ALTERATIONS.
 505.1 OF THE EXIST. BLDG. CODE. SCOPE. LEVEL 3
 ALTERATIONS APPLY WHERE THE WORK AREA EXCEEDS 50 PER
 CENT OF THE BUILDING AREA. 2017 EXIST. BUILDING CODE
 907.4.2. SUBSTANTIAL STRUCTURAL ALTERATIONS IS WHERE 30
 PERCENT OF THE TOTAL FLOOR AND ROOF AREA OF THE
 BUILDING HAS BEEN OR PROPOSED TO BE INVOLVED IN
 STRUCTURAL ALTERATIONS WITHIN A 5 YEAR PERIOD. THIS IS
 A LEVEL II ALTERATION.
  
 2) SHEET A-3 DETAIL 9 SHOWS BUILT-IN BASE MILLWORK AT A
 HEIGHT OF 3-0 FEET FROM FINISH FLOOR TO THE TOP OF THE
 COUNTER. PLEASE SHOW COMPLIANCE WITH THE 2017
 FBC-ACCESSIBILITY CODE SECTIONS:
 902.1 .WORK SURFACES SHALL COMPLY WITH 902.2 AND 902.3.
 ADVISORY 902.1 GENERAL. EXAMPLES OF WORK SURFACES
 INCLUDE WRITING SURFACES, STUDY CARRELS, STUDENT
 LABORATORY STATIONS, BABY CHANGING AND OTHER TABLES OR
 FIXTURES FOR PERSONAL GROOMING, COUPON COUNTERS, AND
 WHERE COVERED BY THE ADA SCOPING PROVISIONS, EMPLOYEE
 WORKSTATIONS.
 CHECK WRITING SURFACES. 2017 ACCESS. CODE 904.3.3 CHECK
 WRITING SURFACES. WHERE PROVIDED, CHECK WRITING
 SURFACES SHALL COMPLY WITH 902.3. 902.3HEIGHT.
 THE TOPS OF WORK SURFACES SHALL BE 28 INCHES (710 MM)
 MINIMUM AND 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 SHOW COMPLIANCE WITH THE ACCESS. CODE 305.5 POSITION.
 UNLESS OTHERWISE SPECIFIED, CLEAR FLOOR OR GROUND SPACE
 SHALL BE POSITIONED FOR EITHER A FORWARD OR PARALLEL
 APPROACH TO AN ELEMENT.
  
 904.4 SALES AND SERVICE COUNTERS. SALES COUNTERS AND
 SERVICE COUNTERS SHALL COMPLY WITH 904.4.1 OR 904.4.2.
 THE ACCESSIBLE PORTION OF THE COUNTERTOP SHALL EXTEND
 THE SAME DEPTH AS THE SALES OR SERVICE COUNTERTOP.
  
 3) SHEETS D-1 AND A-2 SHOW THE REMOVAL OF ONE EXTERIOR
 DOOR AND CLOSING UP THE OPENING, BUT THERE ARE NO
 DETAILS FOR THE BLOCKING UP OF THE OPENING AND TIE INS
 REQUIRED FOR THE BLOCKWORK. 107.2.1.2. ADDITIONAL
 INFORMATION IS REQUIRED. 2017 FBC-B 2103.4 METAL
 REINFORCEMENT AND ACCESSORIES.
  
 4A) SHEET M-3 SHOW A ROOF TOP CONDENSING UNIT ON A
 STAND. THIS SAME DETAIL INDICATES A NOA 18-0828.09.
 PLEASE SUBMIT THIS PRODUCT APPROVAL. 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(G) PRE-ENGINEERED A/C STANDS/ CURBS/ EXHAUST FANS
  
 4B) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP
 DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD
 PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
  
 4C) 2017 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL
 EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING.FBC-B-1609.6.4.4.1 COMPONENTS
 AND CLADDING. WIND PRESSURE FOR EACH COMPONENT OR
 CLADDING ELEMENT IS TO BE DESIGNED FOR WIND PRESSURES
 COMPONENTS AND ATTACHMENTS.
  
 4D) LATERAL FORCE-RESISTING SYSTEM. FOR ALL ROOF TOP
 EQUIPMENT, CURBS, FANS OR A/C STANDS, AND OR VENTS,
 DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL
 AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE.
 2017 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
  
 4E) THE ROOF TOP A/C STAND PRODUCT APPROVALS, TO BE
 REVIEWED BY THE DESIGNER OF RECORD. PLEASE IDENTIFY THE
 FOLLOWING REQUIREMENTS CALCULATING THE AREA (SIDE VIEW)
 OF THE ROOF TOP COMPRESSORS, CONFIGURATION ON STAND,
 THE MEAN ROOF HEIGHT OF THE STAND AND COMPRESSORS,
 WEIGHT, CIRCLED THE DESIGN PARAMETERS IN THE TABLES,
 ANCHORS AND UPLIFT VERSES MOMENT FOR THE UNIT TO THE
 STAND AND THE STAND TO THE ROOF. THE PRODUCT APPROVAL
 IS TO BE REVIEWED BY THE DESIGNER OF RECORD, APPROVED
 BEFORE SUBMISSION TO THE BUILDING DEPARTMENT.
  
 5) NO WIND DESIGN CRITERIA WERE FOUND IN EITHER THE
 ARCHITECTURAL NOR MECHANICAL SHEETS FOR THE NEW ROOF
 TOP EQUIPMENT,
 2017 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 5.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS
 DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1.
  
 5.2. RISK CATEGORY.
  
 5.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE. ASCE 7-10 TABLE 30.3.1.
  
 5.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 5.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED
 BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR
 THE DESIGN OF THE STRUCTURE, PSF.
  
 5.6. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING... ASCE 7-10 TABLE 30.3.1. 1609.3.1 WIND SPEED
 CONVERSION VULT TO VASD.
  
 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  