| 2020-11-03 12:53:34 | 1ST REVIEW FBC-2017 PLUMBING |
| | PERMIT- 20101294 |
| | 11/3/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THERE ARE NO PLUMBING PLANS TO REVIEW HOWEVER SINCE |
| | THIS IS A CHANGE OF OCCUPANCY TO A DAYCARE COMPLIANCE |
| | WITH SECTION 1010. FBC-17 EXISTING BUILDING CODE FOR |
| | INCREASED PLUMBING FIXTURES MAY BE REQUIRED. THE |
| | SUBMITTED FLOOR PLAN DOES NOT PROVIDE SUFFICIENT |
| | INFORMATION TO DETERMINE THE OCCUPANCY CLASSIFICATION |
| | OF THE FACILITY AND WHAT FIXTURES ARE REQUIRED PER |
| | TABLE 403.3 FBC-P. PLEASE REVIEW SECTION 1010 ( PRINTED |
| | BELOW). AND SECTION 305.2 GROUP E, DAY CARE FACILITIES |
| | FBC B. |
| | |
| | SECTION 1010: WHERE THE OCCUPANCY OF AN EXISTING |
| | BUILDING OR PART OF AN EXISTING BUILDING IS CHANGED |
| | SUCH THAT THE NEW OCCUPANCY IS SUBJECT TO INCREASED OR |
| | DIFFERENT PLUMBING FIXTURE REQUIREMENTS OR TO INCREASED |
| | WATER SUPPLY REQUIREMENTS IN ACCORDANCE WITH THE |
| | FLORIDA BUILDING CODE, PLUMBING, THE NEW OCCUPANCY |
| | SHALL COMPLY WITH THE INTENT OF THE RESPECTIVE FLORIDA |
| | BUILDING CODE, PLUMBING PROVISIONS. |
| | |
| | IF IT IS DETERMINE THAT THE THE DAYCARE IS CLASSIFIED |
| | AS AN EDUCATIONAL (E) OCCUPANCY PLEASE SEE TABLE 403.3 |
| | FBC-17 PLUMBING AND PROVIDE PLUMBING FIXTURE |
| | CALCULATIONS. INDICATE ON THE PLAN THE REQUIRED AND |
| | PROVIDED PLUMBING FIXTURES FOR THE PROPOSED OCCUPANCY. |
| | PLEASE NOTE THAT SANITARY AND WATER RISER DRAWINGS WILL |
| | BE REQUIRED FOR NEW FIXTURE INSTALLATIONS- SECTION |
| | 107.3.5.1.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |