| Date |
Text |
| 2020-11-03 13:51:38 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT-20101294 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE PROVIDE MORE INFORMATION, WHAT ARE THE AGES |
| | OF THE CHILDREN? HOW MANY ROOMS WILL BE USED FOR THE |
| | DAYCARE? PLEASE SHOW CALCULATIONS SHOWING THE EXISTING |
| | A/C WILL HANDLE THE ADDITIONAL LOAD OF PEOPLE. FBC |
| | 107.2 |
| | |
| | 2) PLEASE SHOW THE REQUIRED OUTDOOR AIR CALCULATIONS |
| | FOR THE ROOMS USED FOR THIS DAYCARE. FBC M TABLE |
| | 403.3.1.1 |
| | |
| | 3) PLEASE SHOW HOW THE OUTDOOR AIR WILL BE DUCTED INTO |
| | THE MECHANICAL SYSTEM. FBC M 601 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | MICHAEL EDWARDS |
| | MECHANICAL EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL. 33401 |
| | 561-805-6728 |
| | [email protected] |
| | |