Plan Review Notes
Plan Review Notes For Permit 20101294
Permit Number 20101294
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2020-11-05 10:51:07THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE PLAN SHEET INDICATES AN OPENING INTO AND THROUGH
 THE KITCHEN.
  
 HOW WILL CHILDREN BE CONTROLLED/SEPARATED FROM ENTERING
 THE REMAING AREA OF THE HOME?
  
 ARE YOU PROPOSING TO USE THE ENTIRE HOUSE?
  
 PLEASE PROVIDE DETAILS.
  
  
 2) THERE ARE NO INDICATIONS OF THE TYPE OF INTERIOR
 FINISHES ARE ON THE WALL, CEILING AND FLOOR.
  
 PER NFPA 101 CH 16,
  
 16.6.3.3 INTERIOR FINISH.
 16.6.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN
 ACCORDANCE WITH
 SECTION 10.2.
 16.6.3.3.3 INTERIOR FLOOR FINISH.
 16.6.3.3.3.1 INTERIOR FLOOR FINISH SHALL COMPLY WITH
 SECTION 10.2.
  
 10.2.1* GENERAL.
 10.2.1.1 CLASSIFICATION OF INTERIOR FINISH MATERIALS
 SHALL BE IN
 ACCORDANCE WITH TESTS MADE UNDER CONDITIONS SIMULATING
 ACTUAL
 INSTALLATIONS, PROVIDED THAT THE AUTHORITY HAVING
 JURISDICTION IS
 PERMITTED TO ESTABLISH THE CLASSIFICATION OF ANY
 MATERIAL FOR WHICH
 CLASSIFICATION BY A STANDARD TEST IS NOT AVAILABLE,
 UNLESS OTHERWISE
 PROVIDED IN 10.2.1.2 OR 10.2.1.4.
 10.2.1.2 THE PROVISIONS OF 10.2.1.1 SHALL NOT APPLY TO
 MATERIALS HAVING
 A TOTAL THICKNESS OF LESS THAN 1?28 IN. (0.9 MM) THAT
 ARE APPLIED DIRECTLY
 TO THE SURFACE OF WALLS AND CEILINGS WHERE BOTH OF THE
 FOLLOWING
 CONDITIONS ARE MET:
 (1) THE WALL OR CEILING SURFACE IS A NONCOMBUSTIBLE OR
 LIMITEDCOMBUSTIBLE
 MATERIAL.
 (2) THE MATERIALS APPLIED MEET THE REQUIREMENTS OF
 CLASS A INTERIOR
 WALL OR CEILING FINISH WHEN TESTED IN ACCORDANCE WITH
 10.2.3,
 USING FIBER CEMENT BOARD AS THE SUBSTRATE MATERIAL.
 10.2.1.3 IF A MATERIAL HAVING A TOTAL THICKNESS OF LESS
 THAN 1?28 IN. (0.9
 MM) IS APPLIED TO A SURFACE THAT IS NOT NONCOMBUSTIBLE
 OR NOT LIMITEDCOMBUSTIBLE,
 THE PROVISIONS OF 10.2.1.1 SHALL APPLY.
  
 10.2.2.2* INTERIOR FLOOR FINISH SHALL COMPLY WITH
 10.2.7 UNDER ANY OF
 THE FOLLOWING CONDITIONS:
 (1) WHERE FLOOR FINISH REQUIREMENTS ARE SPECIFIED
 ELSEWHERE IN THE
 CODE
 (2) WHERE THE FIRE PERFORMANCE OF THE FLOOR FINISH
 CANNOT BE
 DEMONSTRATED TO BE EQUIVALENT TO FLOOR FINISHES WITH A
 CRITICAL
 RADIANT FLUX OF AT LEAST 0.1 W/CM2
  
 PLEASE PROVIDE DETAILS ON THE TYPE OF FINISHES.
  
  
 3) THERE ARE NO INDICATIONS OF SMOKE ALARMS.
  
 16.6.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS.
 16.6.3.4.1 SMOKE ALARMS SHALL BE INSTALLED WITHIN
 DAY-CARE HOMES
 IN ACCORDANCE WITH 9.6.2.10.
  
 NFPA 101, CH 9
 9.6.2.10 SMOKE ALARMS.
 9.6.2.10.1 WHERE REQUIRED BY ANOTHER SECTION OF THIS
 CODE, SINGLESTATION
 AND MULTIPLE-STATION SMOKE ALARMS SHALL BE IN
 ACCORDANCE
 WITH NFPA 72, NATIONAL FIRE ALARM AND SIGNALING CODE,
 UNLESS
 OTHERWISE PROVIDED IN 9.6.2.10.3, 9.6.2.10.4,
 9.6.2.10.5, OR
 9.6.2.10.6.
  
 NFPA 72, CH 29
  
 29.5.1* REQUIRED DETECTION.
 29.5.1.1* WHERE REQUIRED BY OTHER GOVERNING LAWS,
 CODES, OR
 STANDARDS FOR A SPECIFIC TYPE OF OCCUPANCY, APPROVED
 SINGLEAND
 MULTIPLE-STATION SMOKE ALARMS SHALL BE INSTALLED AS
 FOLLOWS:
 (1)*IN ALL SLEEPING ROOMS AND GUEST ROOMS
 (2)*OUTSIDE OF EACH SEPARATE DWELLING UNIT SLEEPING
 AREA,
 WITHIN 21 FT (6.4 M) OF ANY DOOR TO A SLEEPING ROOM,
 WITH
 THE DISTANCE MEASURED ALONG A PATH OF TRAVEL
 (3) ON EVERY LEVEL OF A DWELLING UNIT, INCLUDING
 BASEMENTS
 (4) ON EVERY LEVEL OF A RESIDENTIAL BOARD AND CARE
 OCCUPANCY
 (SMALL FACILITY), INCLUDING BASEMENTS AND EXCLUDING
 CRAWL
 SPACES AND UNFINISHED ATTICS
 (5)*IN THE LIVING AREA(S) OF A GUEST SUITE
 (6) IN THE LIVING AREA(S) OF A RESIDENTIAL BOARD AND
 CARE OCCUPANCY
 (SMALL FACILITY)
  
 PLEASE PROVIDE DETAILS ON SA LOCATIONS.
  
  
 4) HOW WILL THE PROPOSED ROOM BE USED FOR?
  
 16.6.3.4.3 SINGLE-STATION OR MULTIPLE-STATION SMOKE
 ALARMS OR
 SMOKE DETECTORS SHALL BE PROVIDED IN ALL ROOMS USED FOR
 SLEEPING
 IN ACCORDANCE WITH 9.6.2.10.
  
 IF THE ROOM WILL BE USED FOR SLEEPING/NAPPING PLEASE
 PROVIDE A SA.
  
 PLEASE PROVIDE DETAILS.
  
 5) THERE ARE NO INDICATIONS OF LIGHTING ALONG THE PATH
 OF EXITING.
  
 16.6.2.8 ILLUMINATION OF MEANS OF EGRESS. MEANS OF
 EGRESS SHALL
 BE ILLUMINATED IN ACCORDANCE WITH SECTION 7.8.
  
 7.8 ILLUMINATION OF MEANS OF EGRESS.
 7.8.1 GENERAL.
 7.8.1.1* ILLUMINATION OF MEANS OF EGRESS SHALL BE
 PROVIDED IN
 ACCORDANCE WITH SECTION 7.8 FOR EVERY BUILDING AND
 STRUCTURE WHERE
 REQUIRED IN CHAPTERS 11 THROUGH 43. FOR THE PURPOSES OF
 THIS
 REQUIREMENT, EXIT ACCESS SHALL INCLUDE ONLY DESIGNATED
 STAIRS, AISLES,
 CORRIDORS, RAMPS, ESCALATORS, AND PASSAGEWAYS LEADING
 TO AN EXIT. FOR THE
 PURPOSES OF THIS REQUIREMENT, EXIT DISCHARGE SHALL
 INCLUDE ONLY
 DESIGNATED STAIRS, AISLES, CORRIDORS, RAMPS,
 ESCALATORS, WALKWAYS, AND EXIT
 PASSAGEWAYS LEADING TO A PUBLIC WAY.
  
 7.8.2 SOURCES OF ILLUMINATION.
 7.8.2.1 ILLUMINATION OF MEANS OF EGRESS SHALL BE FROM A
 SOURCE
 CONSIDERED RELIABLE BY THE AUTHORITY HAVING
 JURISDICTION.
 7.8.2.2 BATTERY-OPERATED ELECTRIC LIGHTS AND OTHER
 TYPES OF PORTABLE LAMPS
 OR LANTERNS SHALL NOT BE USED FOR PRIMARY ILLUMINATION
 OF MEANS OF EGRESS.
 BATTERY-OPERATED ELECTRIC LIGHTS SHALL BE PERMITTED TO
 BE USED AS AN
 EMERGENCY SOURCE TO THE EXTENT PERMITTED UNDER SECTION
 7.9.
  
 PLEASE PROVIDE LIGHTING DETAILS.
  
  
 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  