| Date |
Text |
| 2020-11-05 10:51:07 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) THE PLAN SHEET INDICATES AN OPENING INTO AND THROUGH |
| | THE KITCHEN. |
| | |
| | HOW WILL CHILDREN BE CONTROLLED/SEPARATED FROM ENTERING |
| | THE REMAING AREA OF THE HOME? |
| | |
| | ARE YOU PROPOSING TO USE THE ENTIRE HOUSE? |
| | |
| | PLEASE PROVIDE DETAILS. |
| | |
| | |
| | 2) THERE ARE NO INDICATIONS OF THE TYPE OF INTERIOR |
| | FINISHES ARE ON THE WALL, CEILING AND FLOOR. |
| | |
| | PER NFPA 101 CH 16, |
| | |
| | 16.6.3.3 INTERIOR FINISH. |
| | 16.6.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN |
| | ACCORDANCE WITH |
| | SECTION 10.2. |
| | 16.6.3.3.3 INTERIOR FLOOR FINISH. |
| | 16.6.3.3.3.1 INTERIOR FLOOR FINISH SHALL COMPLY WITH |
| | SECTION 10.2. |
| | |
| | 10.2.1* GENERAL. |
| | 10.2.1.1 CLASSIFICATION OF INTERIOR FINISH MATERIALS |
| | SHALL BE IN |
| | ACCORDANCE WITH TESTS MADE UNDER CONDITIONS SIMULATING |
| | ACTUAL |
| | INSTALLATIONS, PROVIDED THAT THE AUTHORITY HAVING |
| | JURISDICTION IS |
| | PERMITTED TO ESTABLISH THE CLASSIFICATION OF ANY |
| | MATERIAL FOR WHICH |
| | CLASSIFICATION BY A STANDARD TEST IS NOT AVAILABLE, |
| | UNLESS OTHERWISE |
| | PROVIDED IN 10.2.1.2 OR 10.2.1.4. |
| | 10.2.1.2 THE PROVISIONS OF 10.2.1.1 SHALL NOT APPLY TO |
| | MATERIALS HAVING |
| | A TOTAL THICKNESS OF LESS THAN 1?28 IN. (0.9 MM) THAT |
| | ARE APPLIED DIRECTLY |
| | TO THE SURFACE OF WALLS AND CEILINGS WHERE BOTH OF THE |
| | FOLLOWING |
| | CONDITIONS ARE MET: |
| | (1) THE WALL OR CEILING SURFACE IS A NONCOMBUSTIBLE OR |
| | LIMITEDCOMBUSTIBLE |
| | MATERIAL. |
| | (2) THE MATERIALS APPLIED MEET THE REQUIREMENTS OF |
| | CLASS A INTERIOR |
| | WALL OR CEILING FINISH WHEN TESTED IN ACCORDANCE WITH |
| | 10.2.3, |
| | USING FIBER CEMENT BOARD AS THE SUBSTRATE MATERIAL. |
| | 10.2.1.3 IF A MATERIAL HAVING A TOTAL THICKNESS OF LESS |
| | THAN 1?28 IN. (0.9 |
| | MM) IS APPLIED TO A SURFACE THAT IS NOT NONCOMBUSTIBLE |
| | OR NOT LIMITEDCOMBUSTIBLE, |
| | THE PROVISIONS OF 10.2.1.1 SHALL APPLY. |
| | |
| | 10.2.2.2* INTERIOR FLOOR FINISH SHALL COMPLY WITH |
| | 10.2.7 UNDER ANY OF |
| | THE FOLLOWING CONDITIONS: |
| | (1) WHERE FLOOR FINISH REQUIREMENTS ARE SPECIFIED |
| | ELSEWHERE IN THE |
| | CODE |
| | (2) WHERE THE FIRE PERFORMANCE OF THE FLOOR FINISH |
| | CANNOT BE |
| | DEMONSTRATED TO BE EQUIVALENT TO FLOOR FINISHES WITH A |
| | CRITICAL |
| | RADIANT FLUX OF AT LEAST 0.1 W/CM2 |
| | |
| | PLEASE PROVIDE DETAILS ON THE TYPE OF FINISHES. |
| | |
| | |
| | 3) THERE ARE NO INDICATIONS OF SMOKE ALARMS. |
| | |
| | 16.6.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS. |
| | 16.6.3.4.1 SMOKE ALARMS SHALL BE INSTALLED WITHIN |
| | DAY-CARE HOMES |
| | IN ACCORDANCE WITH 9.6.2.10. |
| | |
| | NFPA 101, CH 9 |
| | 9.6.2.10 SMOKE ALARMS. |
| | 9.6.2.10.1 WHERE REQUIRED BY ANOTHER SECTION OF THIS |
| | CODE, SINGLESTATION |
| | AND MULTIPLE-STATION SMOKE ALARMS SHALL BE IN |
| | ACCORDANCE |
| | WITH NFPA 72, NATIONAL FIRE ALARM AND SIGNALING CODE, |
| | UNLESS |
| | OTHERWISE PROVIDED IN 9.6.2.10.3, 9.6.2.10.4, |
| | 9.6.2.10.5, OR |
| | 9.6.2.10.6. |
| | |
| | NFPA 72, CH 29 |
| | |
| | 29.5.1* REQUIRED DETECTION. |
| | 29.5.1.1* WHERE REQUIRED BY OTHER GOVERNING LAWS, |
| | CODES, OR |
| | STANDARDS FOR A SPECIFIC TYPE OF OCCUPANCY, APPROVED |
| | SINGLEAND |
| | MULTIPLE-STATION SMOKE ALARMS SHALL BE INSTALLED AS |
| | FOLLOWS: |
| | (1)*IN ALL SLEEPING ROOMS AND GUEST ROOMS |
| | (2)*OUTSIDE OF EACH SEPARATE DWELLING UNIT SLEEPING |
| | AREA, |
| | WITHIN 21 FT (6.4 M) OF ANY DOOR TO A SLEEPING ROOM, |
| | WITH |
| | THE DISTANCE MEASURED ALONG A PATH OF TRAVEL |
| | (3) ON EVERY LEVEL OF A DWELLING UNIT, INCLUDING |
| | BASEMENTS |
| | (4) ON EVERY LEVEL OF A RESIDENTIAL BOARD AND CARE |
| | OCCUPANCY |
| | (SMALL FACILITY), INCLUDING BASEMENTS AND EXCLUDING |
| | CRAWL |
| | SPACES AND UNFINISHED ATTICS |
| | (5)*IN THE LIVING AREA(S) OF A GUEST SUITE |
| | (6) IN THE LIVING AREA(S) OF A RESIDENTIAL BOARD AND |
| | CARE OCCUPANCY |
| | (SMALL FACILITY) |
| | |
| | PLEASE PROVIDE DETAILS ON SA LOCATIONS. |
| | |
| | |
| | 4) HOW WILL THE PROPOSED ROOM BE USED FOR? |
| | |
| | 16.6.3.4.3 SINGLE-STATION OR MULTIPLE-STATION SMOKE |
| | ALARMS OR |
| | SMOKE DETECTORS SHALL BE PROVIDED IN ALL ROOMS USED FOR |
| | SLEEPING |
| | IN ACCORDANCE WITH 9.6.2.10. |
| | |
| | IF THE ROOM WILL BE USED FOR SLEEPING/NAPPING PLEASE |
| | PROVIDE A SA. |
| | |
| | PLEASE PROVIDE DETAILS. |
| | |
| | 5) THERE ARE NO INDICATIONS OF LIGHTING ALONG THE PATH |
| | OF EXITING. |
| | |
| | 16.6.2.8 ILLUMINATION OF MEANS OF EGRESS. MEANS OF |
| | EGRESS SHALL |
| | BE ILLUMINATED IN ACCORDANCE WITH SECTION 7.8. |
| | |
| | 7.8 ILLUMINATION OF MEANS OF EGRESS. |
| | 7.8.1 GENERAL. |
| | 7.8.1.1* ILLUMINATION OF MEANS OF EGRESS SHALL BE |
| | PROVIDED IN |
| | ACCORDANCE WITH SECTION 7.8 FOR EVERY BUILDING AND |
| | STRUCTURE WHERE |
| | REQUIRED IN CHAPTERS 11 THROUGH 43. FOR THE PURPOSES OF |
| | THIS |
| | REQUIREMENT, EXIT ACCESS SHALL INCLUDE ONLY DESIGNATED |
| | STAIRS, AISLES, |
| | CORRIDORS, RAMPS, ESCALATORS, AND PASSAGEWAYS LEADING |
| | TO AN EXIT. FOR THE |
| | PURPOSES OF THIS REQUIREMENT, EXIT DISCHARGE SHALL |
| | INCLUDE ONLY |
| | DESIGNATED STAIRS, AISLES, CORRIDORS, RAMPS, |
| | ESCALATORS, WALKWAYS, AND EXIT |
| | PASSAGEWAYS LEADING TO A PUBLIC WAY. |
| | |
| | 7.8.2 SOURCES OF ILLUMINATION. |
| | 7.8.2.1 ILLUMINATION OF MEANS OF EGRESS SHALL BE FROM A |
| | SOURCE |
| | CONSIDERED RELIABLE BY THE AUTHORITY HAVING |
| | JURISDICTION. |
| | 7.8.2.2 BATTERY-OPERATED ELECTRIC LIGHTS AND OTHER |
| | TYPES OF PORTABLE LAMPS |
| | OR LANTERNS SHALL NOT BE USED FOR PRIMARY ILLUMINATION |
| | OF MEANS OF EGRESS. |
| | BATTERY-OPERATED ELECTRIC LIGHTS SHALL BE PERMITTED TO |
| | BE USED AS AN |
| | EMERGENCY SOURCE TO THE EXTENT PERMITTED UNDER SECTION |
| | 7.9. |
| | |
| | PLEASE PROVIDE LIGHTING DETAILS. |
| | |
| | |
| | 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |