| Date |
Text |
| 2020-10-30 11:13:58 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) THERE ARE EXISTING FIRE RATED WALLS THAT ARE BEING |
| | REPLACED, HOWEVER, THERE ARE NO INDICATIONS OF A LISTED |
| | RATED WALL CALL-OUT TO ENSURE PROPER CONSTRUCTION. |
| | |
| | PER NFPA 1 CH 8 |
| | |
| | 8.3.1.3 WALLS USED AS FIRE BARRIERS SHALL COMPLY WITH |
| | CHAPTER 7 OF |
| | NFPA 221, STANDARD FOR HIGH CHALLENGE FIRE WALLS, FIRE |
| | WALLS, AND |
| | FIRE BARRIER WALLS. THE NFPA 221 LIMITATION ON |
| | PERCENTAGE WIDTH OF |
| | OPENINGS SHALL NOT APPLY. |
| | |
| | 8.3.2 WALLS. |
| | 8.3.2.1 THE FIRE-RESISTIVE MATERIALS, ASSEMBLIES, AND |
| | SYSTEMS USED SHALL |
| | BE LIMITED TO THOSE PERMITTED IN THIS CODE AND THIS |
| | CHAPTER. |
| | |
| | 8.3.2.2 THE CONSTRUCTION MATERIALS AND DETAILS FOR |
| | FIRE-RESISTIVE |
| | ASSEMBLIES AND SYSTEMS FOR WALLS DESCRIBED SHALL COMPLY |
| | WITH ALL |
| | OTHER PROVISIONS OF THIS CODE, EXCEPT AS MODIFIED |
| | HEREIN. |
| | |
| | NFPA 221 |
| | |
| | 4.3 FIRE RESISTANCE RATINGS |
| | 4.3.1 THE FIRE RESISTANCE RATING OF ASSEMBLIES SHALL BE |
| | DETERMINED |
| | IN ACCORDANCE, ASTM E 119, STANDARD TEST METHODS FOR |
| | FIRE |
| | TESTS OF BUILDING CONSTRUCTION AND MATERIALS, OR |
| | ANSI/UL 263, STANDARD |
| | FOR FIRE TESTS OF BUILDING CONSTRUCTION AND MATERIALS, |
| | OR OTHER |
| | APPROVED TEST METHODS OR ANALYTICAL METHODS IN |
| | ACCORDANCE WITH |
| | 4.3.2. |
| | |
| | PLEASE PROVIDE A DETAILED LISTED FIRE RATED WALL |
| | CALL-OUT. |
| | |
| | |
| | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |