Plan Review Notes
Plan Review Notes For Permit 20101232
Permit Number 20101232
Review Stop B
Sequence Number 1
Notes
Date Text
2021-03-24 09:49:26PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT THE MANUFACTURER'S SPECIFICATIONS AND CUT
 SHEETS FOR THE GENERATOR THAT WILL BE INSTALLED. FBC
 107.2.1
  
 2) SUBMIT THE SITE SPECIFIC ENGINEERING FOR THE
 PREFABRICATED GENERATOR PAD. FBC 107.2.1 & FBC-R301