| 2020-11-04 10:39:44 | 1ST REVIEW FBC-2017 RES. FUEL GAS |
| | PERMIT- 20101221 |
| | 11/4/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE GAS RISER DOES NOT INCLUDE THE 40,000 BTUH RANGE |
| | INSTALLED UNDER PERMIT 13020524. PLEASE REVISE THE |
| | RISER, AND ADD THE GAS LOAD TO THE TOTAL LOAD SHOWN ON |
| | THE DRAWING- SECTIONS G2412.3, G2412.4, G2412.3, & |
| | G2412.4 FBC RES. |
| | |
| | 2) THE SPECS FOR THE GENERATOR SUBMITTED UNDER PERMIT- |
| | 20071265 INDICATE A FULL LOAD CAPACITY OF 306,000 BTUH |
| | AND A GAS INPUT PRESSURE OF 3.5- 7 IN. W.C. PLEASE |
| | CORRECT THE RISER AND LOAD TOTAL, AND SUBMIT SPECS FOR |
| | THE NEW REGULATORS MARKED-UP OR HIGHLIGHTED TO SHOW THE |
| | SELECTED MODEL, THE MAX INLET AND OUTLET SIZE AND |
| | PRESSURES, SPRING DATA, AND ORIFICE SIZE- SECTION |
| | G2421.1 FBC RES. |
| | |
| | 3) LIST THE PIPE SIZING TABLES ON THE DRAWING- SECTION |
| | G2413.3 & G2413.4 FBC RES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |