| 2020-11-03 15:28:56 | 11/03/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS | | | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | | | 1. PLEASE SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS FOR | | | THE MAXIMUM SYSTEM FLOW. THE TDH CALCULATIONS MUST | | | INCLUDE ALL THE SYSTEM COMPONENTS INCLUDING SUCTION AND | | | RETURN PIPING, FITTINGS, VALVES, HEATER, FILTER, AND | | | CHLORINATOR. ALL SYSTEM COMPONENTS EXCEPT THE PUMP PER | | | THE ANSI/APSP/ICC 7 - 2013 SECS. 4.4.9, 4.4.9.1. | | | | | | 2. IDENTIFY ON THE PUMP CURVE WHICH CURVE KEY IS | | | SPECIFIC TO THE PUMP BEING INSTALLED ON THIS POOL. THIS | | | IS NEEDED TO CONFIRM THE MAXIMUM SYSTEM FLOW FROM THE | | | TDH CALCULATIONS PER THE ANSI/APSP/ICC 7 - 2013 SECS. | | | 4.4.9, 4.4.9.1. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | LUIS A. CRESPO | | | PLUMBING PLAN EXAMINER / INSPECTOR | | | EMAIL: [email protected] OFFICE: 561 805-6720 | | | |
|