| Plan Review Notes For Permit 20101190 |
| Permit Number |
20101190 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-11-02 08:20:12 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) FAULT CURRENT CALCULATION REQUIRED PER 110.9, 110.10 | | | AND LABEL REQUIRED BY 110.24 | | | | | | 2) SERVICE FEED BY OTHERS, TO BE INCLUDED WITH THE | | | VALUE OF PROJECT. | | | | | | |
|