| | BUILDING REVIEW DENIED: |
| | |
| | FBC B 3107.1, FBC B 1603.1.4, PLEASE PROVIDE THE |
| | WINDLOAD DESIGN, PRESSURES AND ALL OTHER WINDLOAD |
| | RELATED INFORMATION TO SUPPORT THE STRUCTURAL DESIGN |
| | INCLUDING CONNECTIONS. |
| | |
| | |
| | FBC B 107.2.1, PLEASE PROVIDE COMPLETE WELDING |
| | DETAILS/ESSENTIAL VARIABLES OF STRUCTURAL CONNECTIONS |
| | ON PLANS OR AT TIME OF INSPECTION PLEASE PROVIDE: |
| | |
| | AWS D1.1 CLAUSE 5.2 & 6.7: AT TIME OF INSPECTION PLEASE |
| | PROVIDE A WELD PROCEDURE SPECIFICATION; THE W.P.S. |
| | SPECIFIES THE REQUIRED ESSENTIAL VARIABLES INCLUDING: |
| | BASE MATERIALS, JOINTS, PROCESS, AND FILLER METALS TO |
| | BE USED. |
| | AWS D1.1 CLAUSE 6.16: AT TIME OF INSPECTION PLEASE |
| | PROVIDE A WELDER PERFORMANCE QUALIFICATION RECORD; THE |
| | W.P.Q.R. PROVIDES INFORMATION WHICH CAN BE USED TO |
| | VERIFY THE WELDER?S QUALIFICATION AND CERTIFICATION AS |
| | IT RELATES TO THE WELDING REQUIREMENTS OF THE PROJECT. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| | REVIEWED SHEETS DETACHED. |
| | |