| 2020-11-02 16:44:27 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT-20101176 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) HVAC LOAD CALCULATIONS ARE FOR 1,257 SQ. FT. BUT |
| | SHEET M-1 INDICATES THAT THERE IS 1,362 SQ.FT. UNDER |
| | A/C. PLEASE MAKE SURE THEY MATCH. FBC 107.2 |
| | |
| | 2) SHEET M-1: NOTE 1- PLEASE SHOW THE BATH EXHAUST FANS |
| | AND THE TERMINATION LOCATIONS ON THE DRAWING. FBC 107.2 |
| | |
| | 3) SHEET M-1: NOTE 2- PLEASE SHOW THE MICROWAVE EXHAUST |
| | TERMINATION LOCATION ON THE DRAWING. FBC 107.2 |
| | |
| | 4) SHEET M-1: NOTE 5 PLEASE SHOW THE DRYER EXHAUST |
| | TERMINATION LOCATION ON THE DRAWING. FBC 107.2 |
| | |
| | 5) PLEASE LABEL THE AIR CONDENSING UNIT LOCATION AND |
| | PROVIDE ANCHORAGE DETAILS. FBC RES M1307.2 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |