Plan Review Notes
Plan Review Notes For Permit 20101175
Permit Number 20101175
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2020-12-07 16:15:24THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) THERE APPEARS TO BE DOOR CONTACTS ON EXIT DOORS
 THROUGHOUT THE OCCUPANCY.
  
 WHAT IS/ARE THE PURPOSE(S)/FUNCTION OF EACH DOOR
 CONTACT?
  
  
  
 1A) THERE IS NO SEQUENCE OF OPERATION (SOO)
  
 PLEASE PROVIDE A DETAILED SEQUENCE OF OPERATION.
  
  
 2) THERE DOES NOT APPEAR TO BE ANY CONTROL MODULE
 WITHIN THE COMMAND ROOM.
  
 SHOULD THERE BE A SOO INVOLVING FIRE ALARM/EMERGENCY
 POWER/EMERGENCY EVACAUTION, THE COMMAND ROOM MAY
 REQUIRE A DOOR CONTROL MODULE/INDICATOR.
  
  
 3) ANY ACCESS CONTROL IS REQUIRED TO COMPLY WITH THE
 REQUIRMENTS OF NFPA 101, CH 7 MEANS OF EGRESS AS
 APPLICABLE.
  
 PLEASE REVIEW AND ENSURE COMPLAINCE AS APPLICABLE.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  