| Plan Review Notes For Permit 20101175 |
| Permit Number |
20101175 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-12-07 16:15:24 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | | | | 1) THERE APPEARS TO BE DOOR CONTACTS ON EXIT DOORS | | | THROUGHOUT THE OCCUPANCY. | | | | | | WHAT IS/ARE THE PURPOSE(S)/FUNCTION OF EACH DOOR | | | CONTACT? | | | | | | | | | | | | 1A) THERE IS NO SEQUENCE OF OPERATION (SOO) | | | | | | PLEASE PROVIDE A DETAILED SEQUENCE OF OPERATION. | | | | | | | | | 2) THERE DOES NOT APPEAR TO BE ANY CONTROL MODULE | | | WITHIN THE COMMAND ROOM. | | | | | | SHOULD THERE BE A SOO INVOLVING FIRE ALARM/EMERGENCY | | | POWER/EMERGENCY EVACAUTION, THE COMMAND ROOM MAY | | | REQUIRE A DOOR CONTROL MODULE/INDICATOR. | | | | | | | | | 3) ANY ACCESS CONTROL IS REQUIRED TO COMPLY WITH THE | | | REQUIRMENTS OF NFPA 101, CH 7 MEANS OF EGRESS AS | | | APPLICABLE. | | | | | | PLEASE REVIEW AND ENSURE COMPLAINCE AS APPLICABLE. | | | | | | PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT. | | | | | | | | | | | | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|