Plan Review Notes
Plan Review Notes For Permit 20101163
Permit Number 20101163
Review Stop G
Sequence Number 2
Notes
Date Text
2020-11-17 12:41:442ND REVIEW FBC-2017 RES. FUEL GAS
 PERMIT- 20101163
 11/17/20
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) 2ND REQUEST FOR A GAS PIPING RISER DRAWING. PLEASE
 NOTE A GAS PLAN AND RISER DRAWING WERE NOT SUBMITTED
 UNDER THE RENOVATION PERMIT 19041280. THE PLAN REVIEWER
 FOR THE PROJECT NOTED IN HIS COMMENTS THAT GAS WAS TO
 BE UNDER A SEPARATE PERMIT. PLEASE SUBMIT A COMPLETE
 RISER DRAWING AND APPLIANCE SPECIFICATIONS- SECTIONS
 107.2.1 & 107.3.5.3 WPB. INDICATE HOW MAKEUP AIR WILL
 BE PROVIDED TO THE DRYER AND COMBUSTION AIR FOR THE
 RANGE- SECTION G2407.1 FBC RES. THE RISER SHALL
 INCLUDE:
  
 A) THE DELIVERY PRESSURE AT THE METER- G2413.1 &
 G2413.2 FBC RES.
  
 B) THE TYPES AND SIZES OF GAS PIPING SECTIONS G2412.3,
 G2412.4, & G2413.3 FBC RES.
  
 C) THE TOTAL LOAD AND THE INDIVIDUAL LOADS OF THE
 SYSTEM- SECTIONS G2412.3, G2412.4, & G2413.2 FBC RES.
  
 D) THE TOTAL LENGTH DEVELOPED LENGTH OF THE PIPING FROM
 THE METER TO THE MOST REMOTE OUTLET, AND THE INDIVIDUAL
 BRANCH AND CUT LENGTHS- SECTIONS G2413.4.1 AND
 G2413.4.2 FBC RES.
  
 E) LOCATIONS OF SHUT OFF VALVES AND PIPE UNIONS-
 SECTIONS G2420.5 & G2422.1.4.
  
 F) LOCATIONS OF NEW AND EXISTING REGULATORS, MAKE AND
 MODEL NUMBERS, INLET AND OUTLET PRESSURES- SECTIONS
 G2421.1 & G2421.2. SUBMIT MARKED UP OR HIGHLIGHTED
 SPECS SHOWING THE SELECTED MODELS, THE MAX INLET AND
 OUTLET SIZES AND PRESSURES, SPRING DATA, AND ORIFICE
 SIZES.
  
 2) PLEASE NOTE THE CONTRACTOR OR QUALIFIER WHO PREPARES
 THE GAS RISER DRAWING SHALL PROVIDE HIS/HER SIGNATURE
 ON IT- SECTION 107.2.1 WPB, AND FLORIDA STATUTES
 471.003(2)(H) & 471.025.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  