| 2020-10-29 07:25:21 | 1ST REVIEW FBC-2017 RES. FUEL GAS | | | PERMIT- 20101163 | | | 10/29/20 | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | | EDITION 2017 | | | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | PLAN REVIEW RESULTS: DENIED. | | | 1) THE PERMIT INDICATES GAS PIPING WORK FOR APPLIANCES | | | HOWEVER THE SUBMITTED PLAN APPEARS TO SHOW IRRIGATION | | | SYSTEM WORK. PLEASE SUBMIT A GAS PIPING RISER DRAWING, | | | APPLIANCE SPECIFICATIONS, AND COMBUSTION AIR, MAKEUP | | | AIR AND VENTING PLANS- SECTION 107.2.1 WPB. | | | 2) PLEASE NOTE THE CONTRACTOR OR QUALIFIER WHO PREPARES | | | THE GAS RISER DRAWING SHALL PROVIDE HIS/HER SIGNATURE | | | ON IT- SECTION 107.2.1 WPB, AND FLORIDA STATUTES | | | 471.003(2)(H) & 471.025. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|