| 2020-11-03 14:58:11 | SFR REMODEL |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected]. |
| | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 |
| | AMENDMENTS |
| | |
| | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 |
| | 1) PLEASE SHOW THE REQUIRED SMOKE ALARMS PER FBC |
| | R314.2.2 ALTERATIONS, REPAIRS AND ADDITIONS. |
| | WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A |
| | PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE |
| | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL |
| | DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS |
| | LOCATED AS REQUIRED FOR NEW DWELLINGS. |
| | 2) WORK IS A SUBSTANTIAL IMPROVEMENT FBC EXISTING |
| | BUILDING 201 SUBSTANTIAL IMPROVEMENT. FOR THE PURPOSE |
| | OF DETERMINING COMPLIANCE WITH THE FLOOD PROVISIONS OF |
| | THIS CODE, ANY REPAIR, ALTERATION, ADDITION, OR |
| | IMPROVEMENT OF A BUILDING OR STRUCTURE, THE COST OF |
| | WHICH EQUALS OR EXCEEDS 50 PERCENT OF THE MARKET VALUE |
| | OF THE STRUCTURE, BEFORE THE IMPROVEMENT OR REPAIR IS |
| | STARTED. |
| | 3) FLOOD HAZARD AREA (AE 6). THE EXISTING FINISHED |
| | FLOOR ELEVATION WILL NEED TO BE (8.00 NAVD) PLEASE |
| | PROVIDE A SIGNED AND SEALED SURVEY BASED ON THE LATEST |
| | FIRM SHOWING THE FINISHED FLOOR ELEVATION (LOWEST FLOOR |
| | ELEVATION) TO COMPLY WITH CITY ORDINANCE NO. 4729-17 |
| | SEC. 18-33 AND FBC R322.1 GENERAL. |
| | BUILDINGS AND STRUCTURES CONSTRUCTED IN WHOLE OR IN |
| | PART IN FLOOD HAZARD AREAS, INCLUDING A OR V ZONES AND |
| | COASTAL A ZONES, AS ESTABLISHED IN TABLE R301.2(1), AND |
| | SUBSTANTIAL IMPROVEMENT AND RESTORATION OF SUBSTANTIAL |
| | DAMAGE OF BUILDINGS AND STRUCTURES IN FLOOD HAZARD |
| | AREAS, SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE |
| | WITH THE PROVISIONS CONTAINED IN THIS SECTION. |
| | |