| 2020-11-19 11:13:07 | 1ST REVIEW FBC-2017 FUEL GAS |
| | PERMIT- 20101143 |
| | 11/19/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET P1.0: KEY NOTES AND GAS LOADS MISSING AT SHUT |
| | OFF VALVE LOCATIONS IN THE EQUIPMENT ROOM AND MODEL |
| | ROOM- SECTION 107.2.1 WPB. |
| | |
| | 2) P1.0 & P3.0: CORRECT THE TOTAL LOAD IN THE FUEL/GAS |
| | SCHEDULE ON P1.0 TO INDICATE 2424.2 MBTU/H TO MATCH THE |
| | RISER DRAWING- SECTION 107.2.1 WPB. |
| | |
| | 3) P1.0, P2.0, P3.0: CORRECT THE TOTAL LOADS INDICATED |
| | IN FUEL/GAS/SCHEDULE ON P2.0 TO MATCH THE TOTAL LOADS |
| | SPECIFIED IN THE OTHER DRAWINGS AND LOAD SUMMARIES- |
| | SECTION 107.2.1 WPB. |
| | |
| | 4) P3.0: SHOW THE TOTAL MBTU/H LOAD AT THE METER AND |
| | THE LOAD AT THE GENERATOR. CORRECT THE TOTAL LOAD IN |
| | THE FUEL/GAS SCHEDULE- SECTION 107.2.1 WPB. |
| | |
| | 5) P3.0: CORRECT THE NFPA 58 REFERENCE IN THE GAS |
| | NOTES. NFPA 58 IS THE LIQUIFIED PETROLEUM GAS CODE- SEE |
| | FBC FG REFERENCED STANDARDS. |
| | |
| | 6) P3.0: CORRECT THE NOTE SPECIFYING THE ASPHALT PAINT |
| | ON THE UG GAS LINE- SECTION 404.17 FBC FG. |
| | |
| | 7) P3.0: CORRECT OR REMOVE NOTE #4 AT THE GENERATOR |
| | RISER. IT APPEARS NOTE #5 SHOULD BE PROVIDED TO |
| | INDICATE 2ND STAGE REGULATOR. SHOW THE REQUIRED PIPE |
| | UNIONS WITHIN 1 FT. OF EITHER SIDE OF THE REGULATOR- |
| | SECTIONS 410.1 & 410.2(7) FBC FG, AND SECTION 107.2.1 |
| | WPB. PLEASE SHOW OR NOTE THE REQUIRED PIPE UNIONS AT |
| | THE REGULATOR LOCATED ON THE EXTERIOR WALL. |
| | |
| | 8) P3.0: INDICATE A FLEXIBLE GAS SUPPLY LINE WILL BE |
| | INSTALLED AT THE GENERATOR AND PROVIDE THE LENGTH AND |
| | SIZE- SECTION 411.1 FBC FG. |
| | |
| | 9) P1.0 & P3.0: SINGLE DEDICATED AND ACCESSIBLE SHUT |
| | OFF VALVES FOR THE EQUIPMENT IN THE MAIN LAB ROOM AND |
| | IN THE EQUIPMENT/COMPRESSOR ROOM SHALL BE PROVIDED. THE |
| | VALVES SHALL SERVE AS MAIN SHUTOFFS FOR ALL EQUIPMENT |
| | IN EACH ROOM AND SHALL BE LOCATED ADJACENT TO THE |
| | EGRESS DOOR FROM THE ROOM OR SPACE, AND SHALL BE |
| | IDENTIFIED BY APPROVED SIGNAGE STATING "GAS SHUTOFF"- |
| | SECTION 409.6 FBC FG. |
| | |
| | 10) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | GENERATOR AND INTERIOR GAS-FIRED EQUIPMENT. THE SPECS |
| | SHALL BE HIGHLIGHTED OR MARKED UP TO SHOW THE MBTU/H |
| | LOADS, INPUT PRESSURES, AND LISTING STANDARDS- SECTIONS |
| | 301.3, 301.5, & 305.1 FBC FG. |
| | |
| | 11) CLARIFY IF THE INTERIOR EQUIPMENT WILL BE DIRECTLY |
| | CONNECTED VIA THE RIGID PIPING OR IF APPLIANCE |
| | CONNECTORS OR QUICK DISCONNECT DEVICES WILL BE |
| | INSTALLED. SUBMIT SPECS FOR ALL MANUFACTURED CONNECTORS |
| | HIGHLIGHTED OR MARKED UP TO SHOW LISTINGS- SECTION |
| | 411.1 FBC FG. |
| | |
| | 12) PROVIDE COMBUSTION AIR CALCULATIONS FOR THE |
| | INTERIOR GAS-FIRED EQUIPMENT AND INDICATE HOW THE AIR |
| | WILL BE PROVIDED- SECTION 304.1 & 305.1 FBC FG. |
| | |
| | 13) PLEASE REFER TO SECTION 501.8 ITEMS #10 & 11 FBC |
| | FG: VENTING SYSTEMS APPEAR NOT TO BE REQUIRED FOR THE |
| | GAS BURNERS BECAUSE THE TOTAL GAS LOAD IN EACH ROOM |
| | DOES NOT EXCEED 20 MBTU/H, HOWEVER PLEASE SUBMIT |
| | MANUFACTURER'S SPECIFICATIONS AND INSTALLATION MANUALS |
| | FOR THE EQUIPMENT TO CONFIRM COMPLIANCE- SECTION 305.1 |
| | FBC FG. |
| | |
| | 14) REFER TO SECTION 307.2 FBC FG AND PROVIDE |
| | CONDENSATE DISPOSAL PLANS FOR EQUIPMENT PRODUCING |
| | LIQUID COMBUSTION BY PRODUCTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |