| 2020-11-19 11:17:05 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) SHEET # 3.0 INDICATES THE FUEL TYPE AS NATURAL GAS; |
| | HOWEVER, THERE IS NO INDICATIONS OF A FUEL LINE TO THE |
| | GENERATOR. |
| | |
| | PLEASE PROVIDE DETAILS OF THE LOCATION AND SIZE OF THE |
| | FUEL LINE IN COMPLAINCE WITH THE REQUIRMENTS OF NFPA |
| | 54. |
| | |
| | 5.1 PIPING PLAN. |
| | 5.1.1 INSTALLATION OF PIPING SYSTEM. WHERE REQUIRED BY |
| | THE |
| | AUTHORITY HAVING JURISDICTION, A PIPING SKETCH OR PLAN |
| | SHALL BE |
| | PREPARED BEFORE PROCEEDING WITH THE INSTALLATION. THE |
| | PLAN |
| | SHALL SHOW THE PROPOSED LOCATION OF PIPING, THE SIZE OF |
| | DIFFERENT |
| | BRANCHES, THE VARIOUS LOAD DEMANDS, AND THE LOCATION OF |
| | THE POINT OF DELIVERY. |
| | |
| | CHAPTER 7 GAS PIPING INSTALLATION |
| | 7.1 PIPING UNDERGROUND. |
| | 7.1.1 CLEARANCES. UNDERGROUND GAS PIPING SHALL BE |
| | INSTALLED |
| | WITH SUFFICIENT CLEARANCE FROM ANY OTHER UNDERGROUND |
| | STRUCTURE |
| | TO AVOID CONTACT THEREWITH, TO ALLOW MAINTENANCE, AND |
| | TO PROTECT |
| | AGAINST DAMAGE FROM PROXIMITY TO OTHER STRUCTURES. IN |
| | ADDITION, |
| | UNDERGROUND PLASTIC PIPING SHALL BE INSTALLED WITH |
| | SUFFICIENT |
| | CLEARANCE OR SHALL BE INSULATED FROM ANY SOURCE OF HEAT |
| | SO AS TO |
| | PREVENT THE HEAT FROM IMPAIRING THE SERVICEABILITY OF |
| | THE PIPE. |
| | 7.1.2 PROTECTION AGAINST DAMAGE. MEANS SHALL BE |
| | PROVIDED TO |
| | PREVENT EXCESSIVE STRESSING OF THE PIPING WHERE |
| | VEHICULAR TRAFFIC IS |
| | HEAVY OR SOIL CONDITIONS ARE UNSTABLE AND SETTLING OF |
| | PIPING OR |
| | FOUNDATION WALLS COULD OCCUR. PIPING SHALL BE BURIED OR |
| | COVERED |
| | IN A MANNER SO AS TO PROTECT THE PIPING FROM PHYSICAL |
| | DAMAGE. |
| | PIPING SHALL BE PROTECTED FROM PHYSICAL DAMAGE WHERE IT |
| | PASSES |
| | THROUGH FLOWER BEDS, SHRUB BEDS, AND OTHER SUCH |
| | CULTIVATED AREAS |
| | WHERE SUCH DAMAGE IS REASONABLY EXPECTED. |
| | 7.1.2.1 COVER REQUIREMENTS. UNDERGROUND PIPING SYSTEMS |
| | SHALL BE INSTALLED WITH A MINIMUM OF 12 IN. (300 MM) OF |
| | COVER. |
| | |
| | (A) THE MINIMUM COVER SHALL BE INCREASED TO 18 IN. |
| | (460MM)IF |
| | EXTERNAL DAMAGE TO THE PIPE OR TUBING FROM EXTERNAL |
| | FORCES IS |
| | LIKELY TO RESULT.*******LIKE A UNDER A PARKING |
| | LOT******** |
| | |
| | |
| | |
| | 2) SHEET E 1.0 - THERE ARE NO DIMENSIONS INDICATED |
| | AROUND THE LOCATION OF THE GENERATOR. |
| | |
| | 7.2.6 THE EPS EQUIPMENT SHALL BE INSTALLED IN A |
| | LOCATION THAT |
| | PERMITS READY ACCESSIBILITY AND A MINIMUM OF 0.9M(36 |
| | IN.) FROM |
| | THE SKID RAILS? OUTERMOST POINT IN THE DIRECTION OF |
| | ACCESS FOR INSPECTION, |
| | REPAIR, MAINTENANCE, CLEANING, OR REPLACEMENT. THIS |
| | REQUIREMENT |
| | SHALL NOT APPLY TO UNITS IN OUTDOOR HOUSINGS. |
| | |
| | |
| | PLEASE PROVIDE DETAILED DIMENSION FROM PROPERTY LINES, |
| | PAVEMENT EDGES AND BUIDLINGS OR PROVIDE THE SPECIFIC |
| | MANUFACTURES SPEC SHEETS INDICATING OUTDOOR HOUSING. |
| | |
| | |
| | |
| | 3) SHEET E 1.0 & E 2.0 - THERE ARE NO ELEVATION |
| | DIMENSIONS OF THE FOUNDATION. |
| | |
| | PER NFPA 110 |
| | |
| | 7.4.1.1 SUCH FOUNDATIONS OR STRUCTURAL BASES SHALL |
| | RAISE THE |
| | ENGINE AT LEAST 150 MM (6 IN.) ABOVE THE FLOOR OR GRADE |
| | LEVEL |
| | AND BE OF SUFFICIENT ELEVATION TO FACILITATE |
| | LUBRICATING-OIL DRAINAGE |
| | AND EASE OF MAINTENANCE. |
| | |
| | |
| | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |