| 2020-11-16 16:00:16 | CODES IN EFFECT |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | REVIEW STATUS: FAILED. PLEASE SEE COMMENTS BELOW: |
| | |
| | 1) SHEET NUMBER E-3.0 KEYNOTE NUMBER 2 STATES THAT |
| | GENERATOR IS NOT A SEPARATELY DERIVED SYSTEM. RISER |
| | DIAGRAMS SHOWS A #6 GROUND AT THE GENERATOR. FOR |
| | GENERATORS INSTALLED AS NOT SEPARATELY DERIVED SYSTEM |
| | NORMALLY THE EQUIPMENT GROUNDING CONDUCTOR THAT IS PART |
| | OF THE FIVE WIRE FEEDER FROM THE GENERATOR TO THE |
| | TRANSFER EQUIPMENT WILL GROUND AND BOND ALL OF THE |
| | NON-CURRENT CARRYING METAL PARTS OF THE GENERATOR |
| | THROUGH THE TRANSFER EQUIPMENT TO THE GROUNDING |
| | ELECTRODE SYSTEM BACK AT THE SERVICE. NEC 250.35. ONLY |
| | ONE FAULT RETURN PATH SHOULD EXIST. |
| | 2) PROVIDE NOTE REQUIRING WARNING LABEL TO COMPLY WITH |
| | NEC 702.7 |
| | 3) SEE SIGNATURE COMMENTS. |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | |