| Plan Review Notes For Permit 20101143 |
| Permit Number |
20101143 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-11-17 13:27:45 | GENERATOR | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) PLEASE SHOW CONCRETE GENERATOR PAD THICKNESS AND ANY | | | REQUIRED REINFORCEMENT. FBC 1901.2 | | | 2) PLEASE PROVIDE SIGNED AND SEALED GENERATOR TIEDOWN | | | REQUIREMENTS SHOWING THE WIND DESIGN DATA USED FROM AN | | | ARCHITECT OR ENGINEER PER FBC 1603.1 TO COMPLY WITH THE | | | REQUIRED WIND LOADS PER FBC 1609 | | | 3) PLEASE SHOW THE CONCRETE PAD SETBACKS FROM THE | | | PROPERTY LINES AND THE WATER RUN OFF TO BE MAINTAINED | | | ON THIS PROPERTY. | | | |
|