| 2020-10-26 14:33:09 | FIRE PROVISO COMMENTS |
| | |
| | |
| | |
| | 1) PULL STATIONS ARE INDICATED AT EACH EXIT (3). PER |
| | NFPA 101 CH 12 AND CH 9 PULL STATIONS ARE NOT REQUIRED. |
| | |
| | IN AN EFFORT TO REDUCE FALSE FIRE ALARMS THESE PULL |
| | STATIONS CAN BE REMOVED. |
| | |
| | 12.3.4.2 INITIATION. |
| | 12.3.4.2.1 INITIATION OF THE REQUIRED FIRE ALARM SYSTEM |
| | SHALL BE BY |
| | BOTH OF THE FOLLOWING MEANS: |
| | (1) MANUAL MEANS IN ACCORDANCE WITH 9.6.2.1(1), UNLESS |
| | OTHERWISE |
| | PERMITTED BY ONE OF THE FOLLOWING: |
| | (A) THE REQUIREMENT OF 12.3.4.2.1(1) SHALL NOT APPLY |
| | WHERE |
| | INITIATION IS BY MEANS OF AN APPROVED AUTOMATIC FIRE |
| | DETECTION SYSTEM IN ACCORDANCE WITH 9.6.2.1(2) THAT |
| | PROVIDES FIRE DETECTION THROUGHOUT THE BUILDING. |
| | (B) THE REQUIREMENT OF 12.3.4.2.1(1) SHALL NOT APPLY |
| | WHERE |
| | INITIATION IS BY MEANS OF AN APPROVED AUTOMATIC |
| | SPRINKLER SYSTEM IN ACCORDANCE WITH 9.6.2.1(3) THAT |
| | PROVIDES FIRE DETECTION AND PROTECTION THROUGHOUT THE |
| | BUILDING. |
| | (2) WHERE AUTOMATIC SPRINKLERS ARE PROVIDED, INITIATION |
| | OF THE |
| | FIRE ALARM SYSTEM BY SPRINKLER SYSTEM WATERFLOW, EVEN |
| | WHERE |
| | MANUAL FIRE ALARM BOXES ARE PROVIDED IN ACCORDANCE WITH |
| | 12.3.4.2.1(1) |
| | |
| | |
| | 2) DUCT DETECTORS ARE INDICATED. |
| | |
| | 1) THERE ARE INDICATIONS THAT A DUCT DETECTOR WILL |
| | CAUSE A FULL FIRE ALARM ACTIVATION. NFPA PROVIDES CODE |
| | REFERENCES FOR SUPERVISORY SIGNAL ACTIVATION. |
| | |
| | PER NFPA 90A, 2015 ED. |
| | |
| | 6.4.3* FUNCTION. |
| | 6.4.3.1 SMOKE DETECTORS PROVIDED AS REQUIRED BY 6.4.2 |
| | SHALL AUTOMATICALLY STOP THEIR RESPECTIVE FAN(S) ON |
| | DETECTING THE PRESENCE OF SMOKE. |
| | |
| | 6.4.4.2 IN ADDITION TO THE REQUIREMENTS OF 6.4.3, WHERE |
| | AN APPROVED FIRE ALARM SYSTEM IS INSTALLED IN A |
| | BUILDING, THE SMOKE DETECTORS REQUIRED BY THE |
| | PROVISIONS OF SECTION 6.4 SHALL BE CONNECTED TO THE |
| | FIRE ALARM SYSTEM IN ACCORDANCE WITH THE REQUIREMENTS |
| | OF NFPA 72, NATIONAL FIRE ALARM AND SIGNALING |
| | CODE. |
| | |
| | 6.4.4.2.1 SMOKE DETECTORS USED SOLELY FOR CLOSING |
| | DAMPERS OR FOR HEATING, VENTILATING, AND |
| | AIR-CONDITIONING SYSTEM SHUTDOWN SHALL NOT BE REQUIRED |
| | TO ACTIVATE THE BUILDING EVACUATION ALARM. |
| | |
| | 6.4.4.3 WHERE SMOKE DETECTORS REQUIRED BY SECTION 6.4 |
| | ARE INSTALLED IN A BUILDING NOT EQUIPPED WITH AN |
| | APPROVED FIRE ALARM SYSTEM AS SPECIFIED BY 6.4.4.2, THE |
| | FOLLOWING SHALL OCCUR: |
| | (1) SMOKE DETECTOR ACTIVATION REQUIRED BY SECTION 6.4 |
| | SHALL CAUSE A VISUAL SIGNAL AND AN AUDIBLE SIGNAL IN A |
| | NORMALLY OCCUPIED AREA. |
| | (2) SMOKE DETECTOR TROUBLE CONDITIONS SHALL BE |
| | INDICATED VISUALLY OR AUDIBLY IN A NORMALLY OCCUPIED |
| | AREA AND SHALL BE IDENTIFIED AS AIR DUCT DETECTOR |
| | TROUBLE. |
| | |
| | PER NFPA 72, 2013 ED |
| | 23.8.5.4.6 SIGNAL INITIATION ? DUCT SMOKE DETECTORS. |
| | 23.8.5.4.6.1 WHERE DUCT SMOKE DETECTORS ARE REQUIRED TO |
| | BE MONITORED AND A BUILDING FIRE ALARM SYSTEM IS |
| | INSTALLED, A DUCT DETECTOR ACTIVATION SIGNAL SHALL MEET |
| | THE REQUIREMENTS OF 21.7.4. |
| | 21.7.4 SMOKE DETECTORS MOUNTED IN THE AIR DUCTS OF HVAC |
| | SYSTEMS SHALL INITIATE A SUPERVISORY SIGNAL. |
| | 21.7.4.1 SMOKE DETECTORS MOUNTED IN THE AIR DUCTS OF |
| | HVAC SYSTEMS IN A FIRE ALARM SYSTEM WITHOUT A |
| | CONSTANTLY ATTENDED LOCATION OR SUPERVISING STATION |
| | SHALL BE PERMITTED TO INITIATE AN ALARM SIGNAL. |
| | 21.7.4.2 SMOKE DETECTORS MOUNTED IN THE AIR DUCTS OF |
| | HVAC SYSTEMS SHALL BE PERMITTED TO INITIATE AN ALARM |
| | SIGNAL WHERE REQUIRED BY OTHER GOVERNING LAWS, CODES, |
| | OR STANDARDS. |
| | |
| | PLEASE PROGRAM ACCORDINGLY FOR SUPERVISORY ACTIVATION. |
| | |
| | |