| Plan Review Notes For Permit 20101096 |
| Permit Number |
20101096 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2020-12-16 08:20:21 | ELEVATION CERTIFICATE | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | ELEVATION CERTIFICATE ( UNDER CONSTRUCTION) | | | | | | 1) THE ELEVATION FOR THE ATTACHED GARAGE IS SPECIFIED | | | AS 13.8' NAVD 88 IN C2 (D). THIS IS AN ISSUE BECAUSE | | | THE GARAGE IS BELOW THE REQUIRED 14.1' DFE. THE | | | PRE-CONSTRUCTION EC AND THE PLANS SPECIFY THE FINISH | | | FLOOR ELEVATION AS 14.1' NAVD 88. THIS ISSUE WILL NEED | | | TO BE CORRECTED BEFORE THE EC WILL BE APPROVED. | | | POSSIBLE SOLUTIONS ARE RAISING THE FLOOR OF THE GARAGE | | | OR THE INSTALLATION OF FLOOD VENTS. |
|