| 2020-12-03 13:15:07 | RESIDENTIAL (R3) THIRD BUILDING REVIEW COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK |
| | SHALL COMPLY WITH THE MATERIALS AND METHODS |
| | REQUIREMENTS IN THE FLORIDA BUILDING CODE. |
| | |
| | ORIGINAL COMMENT: |
| | 1-UNABLE TO PERFORM BUILDING REVIEW. THERE IS NOT |
| | INFORMATION TO REVIEW. PROVIDE COMPLETE SET OF |
| | DRAWINGS/SPECIFICATIONS SHOWING ALL THE SCOPE OF WORK |
| | TO BE PERFORMED. |
| | SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | RESPONSE: |
| | COMMENTS TO DRAWING CVR SUBMITTED: |
| | 1)DRAWING WAS NOT SIGNED AND SEALED BY THE ARCHITECT OF |
| | RECORD. ARCHITECT TO SIGN AND SEAL DRAWING AS REQUIRED |
| | BY 61G1-16.001FAC AND CHAPTER 481 F.S. WHEN SUBMITTING |
| | DRAWINGS/DOCUMENTS FOR PUBLIC RECORDS. |
| | |
| | 2) DRAWING HAS A NOTE ACROSS ENTIRE SHEET STATING THAT |
| | THIS IS NOT FOR CONSTRUCTION. NEED TO PROVIDE DRAWING |
| | WITHOUT THIS NOTE. DRAWING IS SUBMITTED FOR |
| | CONSTRUCTION. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 3) CONSTRUCTION DRAWINGS ARE NOT CLEAR AND ARE |
| | INCOMPLETE: |
| | A)PROVIDE DETAIL SHOWING HOW ARE THE 2X4 STUDS |
| | INSTALLED UNDER THE EXISTING PRECAST CONCRETE DOUBLE |
| | TEE FLOORING AND SPECIFY FASTENER TYPE, SIZE AND |
| | SPACING. |
| | SEC. R703.1.2.1 FBC-RESIDENTIAL. |
| | |
| | B)FASTENING OF THE PLYWOOD IS NOT CLEAR. WHERE ARE THE |
| | (2)3" TAPCONS PLACED. SPECIFY SPACING, ETC. COORDINATE |
| | WITH ITEM #3. ABOVE. |
| | SEC. R703.1.2.1 FBC-RESIDENTIAL. |
| | |
| | C)DRAWINGS DON'T PROVIDE ANY INFORMATION ABOUT THE |
| | FINISH MATERIALS ON THIS SOFFIT. IS IT STUCCO?. SPECIFY |
| | THICKNESS ( TABLE R702.1(1). FBC-RESIDENTIAL). |
| | |
| | D) NEED TO SPECIFY 2 LAYERS OF WATER RESISTIVE BARRIERS |
| | AS REQUIRED BY SEC. R703.7.3 FBC-RESIDENTIAL. |
| | |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |