| Date |
Text |
| 2020-10-27 11:31:18 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT-20101027 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE PROVIDE REFRIGERATION DETAILS FOR THE WALK IN |
| | COOLER AND FREEZER INCLUDING THE CONDENSING UNITS AND |
| | LOCATIONS. FBC 107.2 |
| | |
| | 2) PLEASE PROVIDE SYSTEM REQUIREMENT DETAILS BASED ON |
| | FBC M 1102.1 |
| | |
| | THE SYSTEM CLASSIFICATION, ALLOWABLE REFRIGERANTS, |
| | MAXIMUM QUANTITY, ENCLOSURE REQUIREMENTS, LOCATION |
| | LIMITATIONS, AND FIELD PRESSURE TEST REQUIREMENTS SHALL |
| | BE DETERMINED AS FOLLOWS: |
| | 1. 1.DETERMINE THE REFRIGERATION SYSTEM'S |
| | CLASSIFICATION, IN ACCORDANCE WITH SECTION 1103.3. |
| | 2. 2.DETERMINE THE REFRIGERANT CLASSIFICATION IN |
| | ACCORDANCE WITH SECTION 1103.1. |
| | 3. 3.DETERMINE THE MAXIMUM ALLOWABLE QUANTITY OF |
| | REFRIGERANT IN ACCORDANCE WITH SECTION 1104, BASED ON |
| | TYPE OF REFRIGERANT, SYSTEM CLASSIFICATION AND |
| | OCCUPANCY. |
| | 4. 4.DETERMINE THE SYSTEM ENCLOSURE REQUIREMENTS IN |
| | ACCORDANCE WITH SECTION 1104. |
| | 5. 5.REFRIGERATION EQUIPMENT AND APPLIANCE LOCATION AND |
| | INSTALLATION SHALL BE SUBJECT TO THE LIMITATIONS OF |
| | CHAPTER 3. |
| | 6. 6.NONFACTORY-TESTED, FIELD-ERECTED EQUIPMENT AND |
| | APPLIANCES SHALL BE PRESSURE TESTED IN ACCORDANCE WITH |
| | SECTION 1108. |
| | |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | MICHAEL EDWARDS |
| | MECHANICAL EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL. 33401 |
| | 561-805-6728 |
| | |