| Plan Review Notes For Permit 20101025 |
| Permit Number |
20101025 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-10-22 15:59:10 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THE SUBMIITED PLAN SHEET DO NOT INDICATE A FLOOR NOR | | | CEILING/ROOF PLAN INDICATING EXACT LOCATIONS, | | | PENETRATION SIZE AND AREA, SUPPORT BRACING, | | | CLEARENCES/PROTECTION FROMCOMBUSTIBLES. OTHER EXISTING | | | ROOF EQUIPMENT LIKE A/C. | | | | | | PLEASE PROVIDE DETAILS. | | | | | | | | | 2) I DID NOT IDENTIFY WORDING THAT STATES THE FIRE | | | SUPPRESSION SYSTEM SAHLL BE INSTALLED BY OTHER UNDER | | | SEPARATE PERMIT AND SHOP DRAWINGS. | | | | | | PLEASE PROVIDE AN APPLICABLE STATMENT OF | | | ACKNOWLEDGEMENT | | | | | | | | | | | | 3) I DID NOT IDENTIFY AN ADDRESS IN THE TITLE BLOCK, | | | ONLY ROCK AND CRAB. | | | | | | PLEASE PPROVIDE THE EXACT ADDRESS OF THE PROJECT | | | | | | | | | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|