| Plan Review Notes For Permit 20100984 |
| Permit Number |
20100984 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-10-28 14:27:46 | CONCRETE FENCE WALL | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) PLEASE PROVIDE A SURVEY SHOWING THE FENCE LOCATION | | | AND HEIGHT. | | | 2) THE FENCE WALL IS SUBJECT TO WIND LOADS PER FBC | | | R301.1 PLEASE PROVIDE THE STRUCTURAL CALCULATIONS | | | REQUIRED FOR THESE LOADS OR HAVE THE DETAILS PREPARED | | | AND SIGNED AND SEALED BY AN ARCHITECT OR ENGINEER FBC | | | R301.1.3 (WIND DESIGN CRITERIA WILL NEED TO BE SHOWN ON | | | THE DRAWINGS 1603.1.4) | | | | | | FYI = SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO | | | BE DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR | | | ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW - OR - | | | IF YOUR ARCHITECT OR ENGINEER DOES NOT HAVE AN | | | ELECTRONIC OR DIGITAL SIGNATURE - PLEASE DROP OFF (CITY | | | HALL DROP BOX) THE ORIGINAL SIGNED AND SEALED | | | DRAWINGS/DOCUMENTS ALONG WITH A "PLAN REVIEW REQUEST | | | FORM" EXPLAINING THE REASON FOR SUBMITTING THE DOCUMENT | | | OR DRAWINGS. PLAN REVIEW REQUEST FORM CAN BE OBTAINED | | | BY E MAILING [email protected] AND ASKING FOR THE FORM. | | | |
|