| Plan Review Notes For Permit 20100983 |
| Permit Number |
20100983 |
|
| Review Stop |
FIRE |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2021-04-22 13:09:48 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | 1) THERE ARE TWO EXIT SIGNS WITHIN THE MAIN CORRIDOR | | | CENTERED OVER A DOUBLE SWING DOOR. | | | | | | PLEASE RELOCATE THE EXIT SIGNS OVER THE CENTER OF THE | | | DOOR IN THE PATH OF TRAVEL; AS INDICATED. | | | | | | | | | 2) ALL FIRE LINE UNDERGROUND SHALL BE INSTALLED, TESTED | | | & INSPECTED PER NFPA 24 UNDER SEPARATE PERMIT AND SHOP | | | DRAWINGS | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] |
|