| Plan Review Notes For Permit 20100983 |
| Permit Number |
20100983 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2021-03-08 10:12:51 | NEW COMMERCIAL BUILDING | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) DRAWING A7.0.1 HAS NOT BEEN REVISED TO SHOW THE | | | GLAZING FOR THE WINDOWS IN THE FIRE RATED WALLS TO BE | | | FIRE RATED. PLEASE SHOW FIRE RATED GLAZING IN FIRE | | | RATED CORRIDOR WALLS AND DOORS TO COMPLY WITH FBC 716.5 | | | 2) DRAWING A10.0.4 NEEDS TO SHOW THE DIMENSIONS FROM | | | THE KITCHEN ISLAND TO THE REFRIGERATOR. PLEASE SHOW THE | | | CLEAR SPACE DIMENSION BETWEEN KITCHEN COUNTER AND | | | COUNTER OR APPLIANCES TO COMPLY WITH FBC FHA - | | | REQUIREMENT 7 - USABLE KITCHENS AND BATHROOMS. (B) | | | CLEARANCE BETWEEN COUNTERS AND ALL OPPOSING BASE | | | CABINETS, COUNTERTOPS, APPLIANCES OR WALLS IS AT LEAST | | | 40 INCHES. | | | | | | TO BE DEFERRED - ROOFING SYSTEMS, PRODUCT APPROVALS FOR | | | EXTERIOR WINDOWS, DOORS AND LOUVERS. | | | |
|