| 2020-11-13 13:20:08 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT-20100983 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) LS-1.2 LISTS THE MULTIPURPOSE ROOM OCCUPANCY AS 18. |
| | SHEET M0.1 OUTSIDE AIR CALCULATIONS HAS THE OCCUPANCY |
| | FOR THE MULTIPURPOSE ROOM AT 8. PLEASE MAKE THE OUTSIDE |
| | AIR CALCULATIONS OCCUPANCY COUNT MATCH THE BUILDING |
| | OCCUPANCY COUNT FOR USE OF SPACE. FBC M TABLE 4.3.3.1.1 |
| | |
| | 2) PLEASE USE THE BUILDING OCCUPANT COUNT FOR USE OF |
| | SPACE AS THE ?ACTUAL OCCUPANT NO. OF PEOPLE IN THE |
| | OUTSIDE AIR CALCULATIONS. FBC TABLE 403.3.1.1 |
| | |
| | 3) PLEASE SHOW ON THE MECHANICAL DRAWINGS THAT THE |
| | AHU?S FOR THE LIVING QUARTERS ARE ACCESSIBLE. FBC M |
| | 306.3 APPLIANCES IN ATTICS |
| | |
| | 4) SHEET M2.1; THE WALL BETWEEN THE GAME ROOM AND THE |
| | RECEPTION AREAS APPEARS TO BE A RATED WALL. PLEASE SHOW |
| | THE PROTECTION AT THE PENETRATIONS OF THESE RATED WALLS |
| | FOR THE SUPPLY AND RETURN DUCTS FOR THE GAME ROOM. FBC |
| | M 607 |
| | |
| | 5) PLEASE PROVIDE SPECIFICATION SHEETS FOR THE COOKING |
| | EQUIPMENT IN THE KITCHEN. PLEASE PROVIDE A DETAIL OF |
| | THE SPECIFIC USE OF THIS KITCHEN AND TYPES OF FOOD |
| | BEING PREPARED. FBC 107.2 |
| | |
| | 6) PLEASE PROVIDE SPECIFICATIONS FOR THE KITCHEN HOOD. |
| | FBC M 507 |
| | |
| | 7) EXHAUST FANS IN THE BATHROOMS IN THE WORKOUT ROOM DO |
| | NOT HAVE A TAG ASSOCIATED WITH GENERAL FAN SCHEDULE ON |
| | SHEET M6.2 PLEASE CORRECTLY IDENTIFY THESE EXHAUST |
| | FANS. FBC 107.2 |
| | |
| | 8) PLEASE PROVIDE A DETAIL DRAWING OF THE BATH EXHAUST |
| | FANS AND THE FIRE DAMPER LOCATION AND ACCESS. FBC M |
| | 607.4 |
| | |
| | 9) PLEASE SHOW ACCESS FOR EACH FIRE SMOKE DAMPER. FBC |
| | M607.4 |
| | |
| | 10) PLEASE PROVIDE SPECIFICATION SHEETS FOR THE DRYERS |
| | IN THE LAUNDRY ROOM. FBC M 504 |
| | |
| | 11) SHEET M7.2 THE DETAIL DRAWING OF THE DRYER ROOF |
| | TERMINATION HAS A SCREEN AT THE EXHAUST TERMINATION. |
| | PLEASE REMOVE THE SCREEN AS IT IS NOT ALLOWED. FBC M |
| | 504.4 |
| | |
| | 12) SHEET M7.2 THE CEILING FIRE DAMPER DETAIL INDICATES |
| | THERE IS A CEILING BELOW THE RATED CEILING, PLEASE |
| | PROVIDE A SHEET NUMBER THAT SHOWS THE DETAIL OF THE TWO |
| | CEILINGS. FBC 107.2 |
| | |
| | 13) |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |