| 2020-12-02 11:29:09 | NEW COMMERCIAL BUILDING |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected]. |
| | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 |
| | AMENDMENTS |
| | |
| | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 |
| | 1) EXISTING BUILDING DEMO NEEDS TO BE A SEPARATE |
| | PERMIT. |
| | 2) PLEASE SHOW THE STC RATING FOR THE WALLS AROUND THE |
| | SLEEPING AREAS TO COMPLY WITH FBC 1207.2 AIR-BORNE |
| | SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS AND SLEEPING UNITS FROM EACH |
| | OTHER OR FROM PUBLIC OR SERVICE AREAS SHALL HAVE A |
| | SOUND TRANSMISSION CLASS OF NOT LESS THAN 50, OR NOT |
| | LESS THAN 45 IF FIELD TESTED, FOR AIR-BORNE NOISE WHEN |
| | TESTED IN ACCORDANCE WITH ASTM E90. |
| | 3) PLEASE SHOW THE FIRE RATED CORRIDOR TO CONTINUE TO |
| | THE EXIT TO COMPLY WITH FBC 1020.6 CORRIDOR CONTINUITY. |
| | FIRE-RESISTANCE-RATED CORRIDORS SHALL BE CONTINUOUS |
| | FROM THE POINT OF ENTRY TO AN EXIT, AND SHALL NOT BE |
| | INTERRUPTED BY INTERVENING ROOMS. |
| | 4) PLEASE SHOW DOORS (137, 138, 139, 130, 143, 146, |
| | 147) OPENING INTO THE FIRE RATED CORRIDOR TO BE FIRE |
| | RATED PER FBC 716.5 |
| | 5) PLEASE SHOW FIRE RATED GLAZING IN FIRE RATED |
| | CORRIDOR WALLS AND DOORS TO COMPLY WITH FBC 716.5 |
| | 6) PLEASE SHOW THE ATTIC ACCESS SIZE AND LOCATION TO |
| | COMPLY WITH FBC 1209.2 |
| | 7) PLEASE PROVIDE COMPLETE MIAMI DADE OR FLORIDA STATE |
| | PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS, DOORS, |
| | LOUVERS ETC. - ALL PRODUCT APPROVALS NEED TO BE |
| | REVIEWED AND MARKED APPROVED BY THE BUILDING DESIGNER |
| | OF RECORD OR BE LISTED BY PRODUCT APPROVAL NUMBER ON |
| | THE DRAWINGS. |
| | 8) PLEASE PROVIDE COMPLETE MIAMI DADE OR FLORIDA STATE |
| | PRODUCT APPROVALS FOR THE ROOFING SYSTEM TO BE USED. |
| | 9) PLEASE SHOW THE LOCATION AND REQUIREMENT FOR GRAB |
| | BAR BACKING AT THE TOILETS AND ALL WALLS OF THE SHOWERS |
| | IN THE ROOM TYPE A AND B PER FBC FHA - REQUIREMENT 6 - |
| | REINFORCED WALLS FOR GRAB BARS. REINFORCED BATHROOM |
| | WALLS TO ALLOW LATER INSTALLATION OF GRAB BARS AROUND |
| | THE TOILET, TUB, SHOWER STALL AND SHOWER SEAT, WHERE |
| | SUCH FACILITIES ARE PROVIDED, WOULD MEET SECTION |
| | 100.205(C)(3)(III) IF REINFORCED AREAS ARE PROVIDED AT |
| | LEAST AT THOSE POINTS WHERE GRAB BARS WILL BE MOUNTED. |
| | 10) PLEASE SHOW LAUNDRY AREA CLEAR FLOOR SPACE AND |
| | APPLIANCES TO COMPLY WITH FBC FHA - REQUIREMENT 2. |
| | ACCESSIBLE AND USABLE PUBLIC AND COMMON USE AREAS.IF |
| | PROVIDED IN THE FACILITY OR AT THE SITE, AT LEAST ONE |
| | OR EACH TYPE OF APPLIANCES PROVIDED IN EACH LAUNDRY |
| | AREA, EXCEPT THAT LAUNDRY ROOMS SERVING COVERED |
| | MULTIPLE-FAMILY DWELLINGS WOULD NOT BE REQUIRED TO HAVE |
| | FRONT-LOADING WASHERS IN ORDER TO MEET THE REQUIREMENTS |
| | OF 100.205(C)(1). (WHERE FRONT-LOADING WASHERS ARE NOT |
| | PROVIDED, MANAGEMENT WILL BE EXPECTED TO PROVIDE |
| | ASSISTIVE DEVICES ON REQUEST IF NECESSARY TO PERMIT A |
| | RESIDENT TO USE A TOP LOADING WASHER.) |
| | 11) PLEASE SHOW THE CLEAR SPACE DIMENSION BETWEEN |
| | KITCHEN COUNTER AND COUNTER OR APPLIANCES TO COMPLY |
| | WITH FBC FHA - REQUIREMENT 7 - USABLE KITCHENS AND |
| | BATHROOMS. (B) CLEARANCE BETWEEN COUNTERS AND ALL |
| | OPPOSING BASE CABINETS, COUNTERTOPS, APPLIANCES OR |
| | WALLS IS AT LEAST 40 INCHES. |
| | |