| 2020-11-02 16:42:47 | 1ST REVIEW FBC-2017 RES. FUEL GAS |
| | PERMIT- 20100957 |
| | 11/2/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) GAS RISER DRAWING: PLEASE PROVIDE A COMPLETE RISER |
| | DRAWING THAT INCLUDES THE INTERIOR GAS APPLIANCES AND |
| | BRANCH PIPING INSTALLED UNDER PERMIT- 01030466 AND THE |
| | GAS GENERATOR INSTALLED UNDER PERMIT- 06040973. PERMIT- |
| | 0130466 INDICATES A TOTAL LOAD OF 675,000 BTUH, AND |
| | PERMIT- 06040973 INDICATES A LOAD OF 550,000 BTUH FOR |
| | THE GENERATOR- SECTION 107.2.1 WPB AND SECTIONS G2412.3 |
| | & G2412.4 FBC RES. |
| | |
| | A) SHOW THE CORRECT TOTAL LOAD AND THE INDIVIDUAL LOADS |
| | OF THE SYSTEM- SECTIONS G2412.3, G2412.4, & G2413.2 FBC |
| | RES. |
| | |
| | B) PROVIDE THE TOTAL LENGTH DEVELOPED LENGTH OF THE |
| | PIPING FROM THE METER TO THE MOST REMOTE OUTLET, AND |
| | THE INDIVIDUAL BRANCH LENGTHS- SECTIONS G2413.4.1 AND |
| | G2413.4.2 FBC RES. |
| | |
| | C) SHOW THE REQUIRED PIPE UNIONS FOR RIGID PIPING |
| | WITHIN 1 FT. OF EITHER SIDE THE REGULATOR- SECTION |
| | G2421.2(7) FBC RES. |
| | |
| | D) THE 1 IN. SCH 40 METALLIC PIPE IS UNDERSIZED FOR THE |
| | 638,000 BTUH IS UNDERSIZED ACCORDING TO SIZING TABLE |
| | 402.4(2) FBC FG THAT IS LISTED ON THE RISER. |
| | |
| | 2) THE SURVEY SHOWS A 5 FT. CLEARANCE FROM THE |
| | GENERATOR EXHAUST TO OPENINGS INTO THE HOUSE HOWEVER A |
| | MINIMUM 10 FT. CLEARANCE IS REQUIRED TO MECHANICAL AND |
| | GRAVITY AIR INTAKES INTO THE BUILDING- SECTION-R303.5.1 |
| | FBC RES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |