2020-11-20 10:42:59RESIDENTIAL (R2) BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- THE VALUE DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW BASED ON ALL THE BUILDING, ELECTRICAL AND PLUMBING
 SCOPE OF WORK SHOWN ON SKETCHES AND SUPPORTING
 DOCUMENTS SUBMITTED. VALUATION TO INCLUDE ALL LABOR,
 MATERIALS, CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. UPDATE VALUATION TO INCLUDE ALL COSTS OR
 PROVIDE COPY OF SIGNED CONTRACTS INCLUDING ALL LABOR,
 MATERIALS, DESIGN PROFESSIONAL FEES, ETC.
  
 2- NEED TO PROVIDE COMPLETE SET OF PLANS SHOWING ALL
 THE SCOPE OF WORK TO BE PERFORMED AND PLANS NEED TO BE
 SIGNED AND SEALED BY AN ARCHITECT AS REQUIRED BY
 CHAPTER 481 FLORIDA STATUTES AND 61G1 FLORIDA
 ADMINISTRATIVE CODE.
 A)BASED ON ALL THE BUILDING, ELECTRICAL AND PLUMBING
 SCOPE OF WORK SHOWN ON SKETCHES AND SUPPORTING
 DOCUMENTS SUBMITTED-AND THE OVERALL VALUE THE WORK IS
 NO EXEMPT FROM ARCHITECT'S LICENSURE. SEC. 481.229
 FLORIDA STATUTE.
 NOTE: PLANS TO SHOW THE EXISTING AND PROPOSED KITCHEN
 LAYOUT, DETAILS AND SPECIFICATIONS FOR THE NEW KITCHEN,
 BATHROOM AND HALL DROPPED CEILINGS, SPRINKLER HEADS
 LOCATION OR RELOCATION, FIRE ALARMS LOCATION, A/C
 CLOSET WALL DETAILS, ETC.
  
 B)THIS IS AN ALTERATION LEVEL 2. SEC. 504 FBC-EXISTING
 BUILDING. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE. SEC. 801.3 FBC-EXISTING
 BUILDING.
  
 3- THE SCOPE OF WORK SPECIFIED ON THE PERMIT
 APPLICATION WAS REVISED. BASED ON THE SCOPE OF WORK
 SUBMITTED THE DESCRIPTION WAS CHANGED TO REPLACE
 KITCHEN CABINETS(NEW LAYOUT)AND VANITIES IN BATHROOM.
 BEDROOM/DINING AND A/C CLOSET ALTERATION. SEC. 107.2.1
 CITY AMENDMENTS. REVISE SCOPE OF WORK IN PERMIT
 APPLICATION.
  
 4- FLOORING SOUND INSULATION MATERIAL:
 A) PROVIDE COPY OF THE FLAME SPREAD INDEX AND SMOKE
 DEVELOPED INDEX TEST DONE IN ACCORDANCE WITH ASTM E 84
 OR UL 723 AS REQUIRED BY SEC. 720.1 OF FBC 6TH EDITION
 (2017).
  
 B) PROVIDE COPY OF THE SOUND TRANSMISSION CLASS (STC)
 TEST DONE IN ACCORDANCE WITH ASTM E 90 AS REQUIRED BY
 SEC. 1207.2 OF FBC 6TH EDITION (2017).
  
 C) PROVIDE COPY OF THE IMPACT INSULATION CLASS (IIC)
 TEST DONE IN ACCORDANCE WITH ASTM E 492 AS REQUIRED BY
 SEC. 1207.3 OF FBC 6TH EDITION (2017).
  
 NOTE: TEST SAMPLES TO MATCH BUILDING FLOOR/CEILING
 CONSTRUCTION AND PROPOSED FLOOR FINISH. ALSO, THERE ARE
 TESTS FOR 6" OR 8" CONCRETE SLABS WITH OR WITHOUT
 ACOUSTICAL CEILING. TYPICALLY THERE ARE NOT SUSPENDED
 ACOUSTICAL CEILINGS IN THESE BUILDINGS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,