| Notes |
| Date |
Text |
| 2020-12-03 15:57:10 | GENERATOR | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) CONCRETE SLAB DETAILS NEED TO BE SIGNED AND SEALED | | | BY THE DESIGNER. | | | 2) PLEASE PROVIDE SIGNED AND SEALED SITE SPECIFIC | | | GENERATOR TIE DOWN DETAILS FROM AN ARCHITECT OR | | | ENGINEER TO COMPLY WITH WIND LOADS FBC 1609 | | | | | | FYI = SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO | | | BE DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR | | | ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW - OR - | | | IF YOUR ARCHITECT OR ENGINEER DOES NOT HAVE AN | | | ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN SUBMIT THE | | | ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS TO THE | | | BUILDING DIVISION AT CITY HALL. |
|