2020-10-30 10:05:52PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE HORIZONTAL SLIDING WIDOWS WITH THE DESIGN
 PRESSURES OF +/- 40 PSF DO NOT APPEAR TO MEET THE
 WINDLOAD PRESSURES THAT ARE REQUIRED FOR THE OPENINGS.
 THIS IS A TWO STOREY STRUCTURE WITH A MEAN ROOF HEIGHT
 OF AROUND 24 FEET. THE WIND SPEED IS 170 MPH VULT. THE
 DEFAULT EXPOSURE CATEGORY IS "EXPOSURE C". IT IS NOT
 SPECIFIED WHICH WALL ZONE THE WINDOWS ARE LOCATED IN.
 THE LARGEST OF THESE WINDOWS HAS AN AREA OF LESS THAN
 20 SQFT. THE REQUIRED DESIGN PRESSURES IN ZONE 4
 (INTERIOR) FOR A 20SQFT TRIBURARY AREA IS +39.8, -43.4
 PSF. THE PRESSURES ARE GREATER IN WALL ZONE 5 (CORNER)
 AND FOR THE SMALLER WINDOWS. SUBMIT PRODUCT APPROVALS
 FOR WINDOWS THAT HAVE ADEQUATE DESIGN PRESSURES.
  
 2) SOME OF THE WINDOWS ARE NOT IMPACT RESISTANT. ARE
 THERE EXISTING PERMITTED AND APPROVED IMPACT PROTECTION
 DEVICES? SHOW HOW THE REQUIREMENTS OF FBC EXISTING
 BUILDINGS 707.4 REPLACEMENT OF WINDOWS AND DOORS WILL
 BE MET.