| 2020-11-03 10:33:32 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 20100901 |
| | ADD: 3590 VILLAGE BLVD. |
| | CONT: ALLIANCE RESIDENTIAL BUILDERS SOUTH FLORIDA, LLC. |
| | TEL: 561-756-8980 X204 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 1ST REVIEW |
| | DATE: TUES. NOV.03/2020 |
| | ACTION: DENIED |
| | |
| | 1) PLEASE NOTE A ADDRESSING STOP HAS BEEN ADDED TO THIS |
| | PROPOSED PERMIT. THE SITE ADDRESS FOR THIS PROPERTY IS |
| | BEING USED CURRENTLY BUT THIS IS A MULTIPLE BUILDING |
| | COMPLEX WITH ALL BUILDINGS REQUIRING THEIR OWN |
| | INDIVIDUAL ADDRESS FOR BUILDING INSPECTIONS, |
| | CERTIFICATE OF OCCUPANCIES AND RECORD RETENTION. THERE |
| | ARE 4 GAZEBOS ALONE THAT NEED SEPARATE ADDRESSES!!! |
| | SEE NOTE 4 SHEETGZ-1 GAZEBO PLAN. |
| | |
| | 2017 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED. |
| | 2017 FBC-B 501.2 ADDRESS IDENTIFICATION. NEW AND |
| | EXISTING BUILDINGS SHALL BE PROVIDED WITH APPROVED |
| | ADDRESS IDENTIFICATION. |
| | CITY MUNI CODE SEC.78-6 (1-7) |
| | (2) LOCATION, BUILDINGS CONTAINING MORE THAN ONE |
| | ADDRESS. ALL ADDRESSES SHALL BE POSTED ON THAT PORTION |
| | OF THE STRUCTURE FRONTING OR FACING UPON THE STREET OR |
| | PRINCIPAL VEHICULAR ACCESS TO THE PREMISES, SO AS TO BE |
| | READILY VISIBLE TO APPROACHING VEHICLES. OWNERS OR |
| | TENANTS OF ALL HOUSES AND BUILDINGS USING A SERVICE |
| | ALLEY SHALL ALSO POST A NUMBER ON THE SIDE OF THE |
| | BUILDINGS ADJACENT TO AND FACING SUCH ALLEY. IF THE |
| | HOUSE OR BUILDING IS OBSTRUCTED BY A FENCE, THEN THE |
| | NUMBER SHALL BE POSTED ON THE FENCE. THE PLACEMENT OF |
| | NUMBERS ON BUILDINGS OR FENCES, AS THE CASE MAY BE, |
| | SHALL BE SUBJECT TO THE DIRECTION OR APPROVAL OF THE |
| | CITY'S CONSTRUCTION SERVICES DEPARTMENT. BUILDINGS |
| | WHICH CONTAIN MORE THAN ONE RESIDENTIAL, COMMERCIAL, |
| | INDUSTRIAL, OR INSTITUTIONAL ADDRESS SHALL POST A |
| | SEPARATE ADDRESS MEETING THE REQUIREMENTS OF THIS |
| | SECTION AT THE EXTERIOR ENTRANCE TO EACH INDIVIDUAL |
| | ADDRESS OR COMMON EXTERIOR ENTRANCE TO SEVERAL |
| | ADDRESSES THEREIN, AND THE UNIT NUMBER SHALL ALSO BE |
| | POSTED ON THE EXTERIOR DOOR OF EACH UNIT SERVED BY SUCH |
| | A COMMON EXTERIOR ENTRANCE. |
| | (3) MONUMENT SIGNS. ALL MONUMENT SIGNS FOR MULTIPLE |
| | RESIDENTIAL, COMMERCIAL, INDUSTRIAL, OR INSTITUTIONAL |
| | DEVELOPMENTS SHALL POST THE ADDRESS RANGE FOR THE |
| | DEVELOPMENT. THE POSTED ADDRESS RANGE SHALL MEET THE |
| | REQUIREMENTS OF THIS SECTION. |
| | 2) NOTE, NO ACTION REQUIRED. FOR THE GAZEBO REVIEW THE |
| | ONLY (3) THREE SHEETS BEING REVIEWED ARE IN RELATION TO |
| | THE GAZEBO, SHEETS GZ-1, S-10 & S-GZ 1. |
| | 3) SHEET S-GZ_1: |
| | 3A) FOOTING SCHEDULE THE FOOTER FOR THE SLAB IS MARKED |
| | WF-8 AND 8 X 12 INCHES, OR 8 INCHES WIDE AND 12 INCHES |
| | HIGH WITH APPROX.. 3 TO 4 INCHES ABOVE GRADE. FOOTINGS, |
| | DEPTH AND WIDTH. 2017 FBC-B 1809.4. THE MINIMUM DEPTH |
| | OF FOOTINGS BELOW UNDISTURBED GROUND SURFACE SHALL BE |
| | 12 INCHES, THE MINIMUM WIDTH OF FOOTINGS SHALL BE 12 |
| | INCHES. |
| | 3B) THE WIND PRESSURES GIVEN FOR ROOF ZONES 1,2, & 3 |
| | ARE GIVEN BUT ON SHEET S-1 UNDER THE HEADING DESIGN |
| | LOADS (B) THE PARTIAL WIND DESIGN IS GIVEN, THE MEAN |
| | ROOF HEIGHT IS NOT GIVEN NOR WHAT IS THE APPLICABLE |
| | PRESSURE COEFFICIENT. 2017 FBC-B 1603.1.4 WIND DESIGN |
| | CRITERIA. |
| | 3C) SECTION 1/S-G.1THIS SECTION SHOWS THE CONCRETE BEAM |
| | AND TRUSSES AND A NOTE FOR THE TRUSS ANCHORS SEE METAL |
| | STRAP SEE PLAN. THE ROOF FRAMING PLAN SHOWS THE UPLIFT |
| | & REACTION LOADS BUT NO STRAP/ ANCHOR SCHEDULE. |
| | 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED. |
| | 4) SHEET GZ-1: |
| | 4A) THIS SHEET DOES SHOW MORE SECTIONS AND ELEVATIONS. |
| | ELEVATION LEGEND NOTE 5 INDICATES THE ROOF IS TO HAVE |
| | CONCRETE SPANISH S ROOF TILE. |
| | 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, THE |
| | CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND |
| | DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS, |
| | VENTING, FASTENING REQUIREMENTS, FLASHING REQUIREMENTS |
| | AND WIND RESISTANCE RATING THAT ARE REQUIRED TO BE |
| | INSTALLED. PRODUCT EVALUATION AND INSTALLATION SHALL |
| | INDICATE COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR |
| | THE SPECIFIC SITE. |
| | 4B) 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(C) TRUSS ANCHOR STRAPS AND OR ANCHORS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES, |
| | |
| | 4C) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE |
| | 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP |
| | DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD |
| | PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 4D) TRUSS SHOP DRAWINGS. FL 61G1-23.015 (2) THE |
| | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC. |
| | |
| | 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| | 19 |
| | IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| | 561-718-9724. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |