2020-11-03 10:33:32WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20100901
 ADD: 3590 VILLAGE BLVD.
 CONT: ALLIANCE RESIDENTIAL BUILDERS SOUTH FLORIDA, LLC.
 TEL: 561-756-8980 X204
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: TUES. NOV.03/2020
 ACTION: DENIED
  
 1) PLEASE NOTE A ADDRESSING STOP HAS BEEN ADDED TO THIS
 PROPOSED PERMIT. THE SITE ADDRESS FOR THIS PROPERTY IS
 BEING USED CURRENTLY BUT THIS IS A MULTIPLE BUILDING
 COMPLEX WITH ALL BUILDINGS REQUIRING THEIR OWN
 INDIVIDUAL ADDRESS FOR BUILDING INSPECTIONS,
 CERTIFICATE OF OCCUPANCIES AND RECORD RETENTION. THERE
 ARE 4 GAZEBOS ALONE THAT NEED SEPARATE ADDRESSES!!!
 SEE NOTE 4 SHEETGZ-1 GAZEBO PLAN.
  
 2017 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED.
 2017 FBC-B 501.2 ADDRESS IDENTIFICATION. NEW AND
 EXISTING BUILDINGS SHALL BE PROVIDED WITH APPROVED
 ADDRESS IDENTIFICATION.
 CITY MUNI CODE SEC.78-6 (1-7)
 (2) LOCATION, BUILDINGS CONTAINING MORE THAN ONE
 ADDRESS. ALL ADDRESSES SHALL BE POSTED ON THAT PORTION
 OF THE STRUCTURE FRONTING OR FACING UPON THE STREET OR
 PRINCIPAL VEHICULAR ACCESS TO THE PREMISES, SO AS TO BE
 READILY VISIBLE TO APPROACHING VEHICLES. OWNERS OR
 TENANTS OF ALL HOUSES AND BUILDINGS USING A SERVICE
 ALLEY SHALL ALSO POST A NUMBER ON THE SIDE OF THE
 BUILDINGS ADJACENT TO AND FACING SUCH ALLEY. IF THE
 HOUSE OR BUILDING IS OBSTRUCTED BY A FENCE, THEN THE
 NUMBER SHALL BE POSTED ON THE FENCE. THE PLACEMENT OF
 NUMBERS ON BUILDINGS OR FENCES, AS THE CASE MAY BE,
 SHALL BE SUBJECT TO THE DIRECTION OR APPROVAL OF THE
 CITY'S CONSTRUCTION SERVICES DEPARTMENT. BUILDINGS
 WHICH CONTAIN MORE THAN ONE RESIDENTIAL, COMMERCIAL,
 INDUSTRIAL, OR INSTITUTIONAL ADDRESS SHALL POST A
 SEPARATE ADDRESS MEETING THE REQUIREMENTS OF THIS
 SECTION AT THE EXTERIOR ENTRANCE TO EACH INDIVIDUAL
 ADDRESS OR COMMON EXTERIOR ENTRANCE TO SEVERAL
 ADDRESSES THEREIN, AND THE UNIT NUMBER SHALL ALSO BE
 POSTED ON THE EXTERIOR DOOR OF EACH UNIT SERVED BY SUCH
 A COMMON EXTERIOR ENTRANCE.
 (3) MONUMENT SIGNS. ALL MONUMENT SIGNS FOR MULTIPLE
 RESIDENTIAL, COMMERCIAL, INDUSTRIAL, OR INSTITUTIONAL
 DEVELOPMENTS SHALL POST THE ADDRESS RANGE FOR THE
 DEVELOPMENT. THE POSTED ADDRESS RANGE SHALL MEET THE
 REQUIREMENTS OF THIS SECTION.
 2) NOTE, NO ACTION REQUIRED. FOR THE GAZEBO REVIEW THE
 ONLY (3) THREE SHEETS BEING REVIEWED ARE IN RELATION TO
 THE GAZEBO, SHEETS GZ-1, S-10 & S-GZ 1.
 3) SHEET S-GZ_1:
 3A) FOOTING SCHEDULE THE FOOTER FOR THE SLAB IS MARKED
 WF-8 AND 8 X 12 INCHES, OR 8 INCHES WIDE AND 12 INCHES
 HIGH WITH APPROX.. 3 TO 4 INCHES ABOVE GRADE. FOOTINGS,
 DEPTH AND WIDTH. 2017 FBC-B 1809.4. THE MINIMUM DEPTH
 OF FOOTINGS BELOW UNDISTURBED GROUND SURFACE SHALL BE
 12 INCHES, THE MINIMUM WIDTH OF FOOTINGS SHALL BE 12
 INCHES.
 3B) THE WIND PRESSURES GIVEN FOR ROOF ZONES 1,2, & 3
 ARE GIVEN BUT ON SHEET S-1 UNDER THE HEADING DESIGN
 LOADS (B) THE PARTIAL WIND DESIGN IS GIVEN, THE MEAN
 ROOF HEIGHT IS NOT GIVEN NOR WHAT IS THE APPLICABLE
 PRESSURE COEFFICIENT. 2017 FBC-B 1603.1.4 WIND DESIGN
 CRITERIA.
 3C) SECTION 1/S-G.1THIS SECTION SHOWS THE CONCRETE BEAM
 AND TRUSSES AND A NOTE FOR THE TRUSS ANCHORS SEE METAL
 STRAP SEE PLAN. THE ROOF FRAMING PLAN SHOWS THE UPLIFT
 & REACTION LOADS BUT NO STRAP/ ANCHOR SCHEDULE.
 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
 4) SHEET GZ-1:
 4A) THIS SHEET DOES SHOW MORE SECTIONS AND ELEVATIONS.
 ELEVATION LEGEND NOTE 5 INDICATES THE ROOF IS TO HAVE
 CONCRETE SPANISH S ROOF TILE.
 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, THE
 CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND
 DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS,
 VENTING, FASTENING REQUIREMENTS, FLASHING REQUIREMENTS
 AND WIND RESISTANCE RATING THAT ARE REQUIRED TO BE
 INSTALLED. PRODUCT EVALUATION AND INSTALLATION SHALL
 INDICATE COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR
 THE SPECIFIC SITE.
 4B) 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(C) TRUSS ANCHOR STRAPS AND OR ANCHORS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES,
  
 4C) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP
 DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD
 PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 4D) TRUSS SHOP DRAWINGS. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.
  
 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER