Plan Review Notes
Plan Review Notes For Permit 20100899
Permit Number 20100899
Review Stop B
Sequence Number 3
Notes
Date Text
2021-06-14 16:24:37****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 3RD BUILDING REVIEW DENIED:
  
 1) OK PER PAGE GA1A.
 2) APPROVED
 3) APPROVED
 4) FAILED, PROVIDE A CLARIFICATION AS THE FOUNDATION
 PLANS INDICATE FOOTINGS AT A DEPTH OF 16" BELOW GRADE
 AND THE GEO TECH REPORT STATES THAT THE FOOTINGS SHOULD
 BOTTOM AT 18" BELOW GRADE.
 5) APPROVED
 6) APPROVED
 7) APPROVED
 8) & 9) THE SUBMITTED PRODUCT APPROVALS NEED TO BE
 REVIEW STAMPED BY DESIGNER OF RECORD. IF THESE PRODUCT
 APPROVALS ARE TO BE DEFERRED, PLEASE PROVIDE A LIST ON
 PLANS (APPROVED BY DESIGNER OF RECORD) OF THOSE
 SUBMITTALS THAT ARE TO BE DEFERRED.
 10) APPROVED
 11) APPROVED
 12) APPROVED
 13) APPROVED
  