Plan Review Notes
Plan Review Notes For Permit 20100899
Permit Number 20100899
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2020-11-10 16:02:36THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) ONLY ONE EXIT IS INDICATED IN SOME OF THE INDIVIDUAL
 UNITS.
  
 PER NFPA 101, CH 42
  
 42.8 SPECIAL PROVISIONS FOR PARKING STRUCTURES.
  
 42.8.1 GENERAL REQUIREMENTS
  
 42.8.1.1 APPLICATION. THE PROVISIONS OF 42.8.1 THROUGH
 42.8.5.4
 SHALL APPLY TO PARKING STRUCTURES OF THE CLOSED OR OPEN
 TYPE, ABOVE
 OR BELOW GRADE PLANE, BUT SHALL NOT APPLY TO ASSISTED
 MECHANICALTYPE
 OR AUTOMATED-TYPE PARKING FACILITIES THAT ARE NOT
 OCCUPIED BY
 CUSTOMERS. THE REQUIREMENTS OF SECTIONS 42.1 THROUGH
 42.7 SHALL
 NOT APPLY.
  
 42.8.2.2.2.3 AN OPENING FOR THE PASSAGE OF AUTOMOBILES
 SHALL BE
 PERMITTED TO SERVE AS AN EXIT FROM A STREET FLOOR,
 PROVIDED THAT NO
 DOOR OR SHUTTER IS INSTALLED THEREIN.
  
 42.8.2.4.1 NOT LESS THAN TWO MEANS OF EGRESS SHALL BE
 PROVIDED
 FROM EVERY FLOOR OR SECTION OF EVERY PARKING STRUCTURE.
  
 PLEASE CORRECT OF JUSTIFY WITH SPECIFIC CODE REFERENCES
 AND NARRATIVE.
  
  
  
 2) THERE IS AN EXHAUST FAN INDICATED; HOWEVER, IT DOES
 NOT APPEAR TO MEET THE REQUIREMENT.
  
 NFPA 88A
  
 6.3 VENTILATION.
 6.3.1* ALL ENCLOSED PARKING STRUCTURES SHALL BE
 VENTILATED BY
 A MECHANICAL SYSTEM CAPABLE OF PROVIDING A MINIMUM OF
 300 L/MIN PER M2 OF FLOOR AREA (1 FT3/MIN PER FT2 OF
 FLOOR
 AREA) DURING HOURS OF NORMAL OPERATION.
  
 6.3.3 MECHANICAL VENTILATING SYSTEMS SHALL BE INSTALLED
 IN ACCORDANCE
 WITH NFPA 90A. DUCTWORK SHALL BE CONSTRUCTED OF
 NONCOMBUSTIBLE MATERIAL.
  
 PLEASE REVIEW AND EXPLAIN COMPLIANCE WITH THE CODE.
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]