| Date |
Text |
| 2020-11-10 16:02:36 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) ONLY ONE EXIT IS INDICATED IN SOME OF THE INDIVIDUAL |
| | UNITS. |
| | |
| | PER NFPA 101, CH 42 |
| | |
| | 42.8 SPECIAL PROVISIONS FOR PARKING STRUCTURES. |
| | |
| | 42.8.1 GENERAL REQUIREMENTS |
| | |
| | 42.8.1.1 APPLICATION. THE PROVISIONS OF 42.8.1 THROUGH |
| | 42.8.5.4 |
| | SHALL APPLY TO PARKING STRUCTURES OF THE CLOSED OR OPEN |
| | TYPE, ABOVE |
| | OR BELOW GRADE PLANE, BUT SHALL NOT APPLY TO ASSISTED |
| | MECHANICALTYPE |
| | OR AUTOMATED-TYPE PARKING FACILITIES THAT ARE NOT |
| | OCCUPIED BY |
| | CUSTOMERS. THE REQUIREMENTS OF SECTIONS 42.1 THROUGH |
| | 42.7 SHALL |
| | NOT APPLY. |
| | |
| | 42.8.2.2.2.3 AN OPENING FOR THE PASSAGE OF AUTOMOBILES |
| | SHALL BE |
| | PERMITTED TO SERVE AS AN EXIT FROM A STREET FLOOR, |
| | PROVIDED THAT NO |
| | DOOR OR SHUTTER IS INSTALLED THEREIN. |
| | |
| | 42.8.2.4.1 NOT LESS THAN TWO MEANS OF EGRESS SHALL BE |
| | PROVIDED |
| | FROM EVERY FLOOR OR SECTION OF EVERY PARKING STRUCTURE. |
| | |
| | PLEASE CORRECT OF JUSTIFY WITH SPECIFIC CODE REFERENCES |
| | AND NARRATIVE. |
| | |
| | |
| | |
| | 2) THERE IS AN EXHAUST FAN INDICATED; HOWEVER, IT DOES |
| | NOT APPEAR TO MEET THE REQUIREMENT. |
| | |
| | NFPA 88A |
| | |
| | 6.3 VENTILATION. |
| | 6.3.1* ALL ENCLOSED PARKING STRUCTURES SHALL BE |
| | VENTILATED BY |
| | A MECHANICAL SYSTEM CAPABLE OF PROVIDING A MINIMUM OF |
| | 300 L/MIN PER M2 OF FLOOR AREA (1 FT3/MIN PER FT2 OF |
| | FLOOR |
| | AREA) DURING HOURS OF NORMAL OPERATION. |
| | |
| | 6.3.3 MECHANICAL VENTILATING SYSTEMS SHALL BE INSTALLED |
| | IN ACCORDANCE |
| | WITH NFPA 90A. DUCTWORK SHALL BE CONSTRUCTED OF |
| | NONCOMBUSTIBLE MATERIAL. |
| | |
| | PLEASE REVIEW AND EXPLAIN COMPLIANCE WITH THE CODE. |
| | |
| | |
| | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |