2020-11-25 09:48:28CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: FAILED, SEE COMMENTS BELOW.
  
 1) GARAGE POWER RISER SHOWS PANEL G1A BEING FED FROM
 UTILITY TRANSFORMER. PANEL G1A IS DESCRIBED AS MLO
 TYPE. PLEASE PROVIDE SERVICE EQUIPMENT DISCONNECT AND
 OVERCURRENT PROTECTION TO COMPLY WITH NEC 230.
 2) SEE BUILDING COMMENTS REGARDING FLOOD ZONE
 REQUIREMENTS. PLEASE SHOW COMPLIANCE WITH THESE
 REQUIREMENTS.
 2) SCOPE OF WORK IS LIMITED TO DETACHED GARAGE TYPE I
 STRUCTURES. SITE LIGHTING, FIRE ALARM, AND LOW VOLTAGE
 WORK REQUIRES SEPARATE PERMITS.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  