| 2020-10-26 08:45:18 | 1ST REVIEW FBC-2017 FUEL GAS |
| | PERMIT- 20100843 |
| | 10/23/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE SUBMITTED APPLICATION IS FOR GAS PIPING |
| | INSTALLATIONS. PLEASE REMOVE THE PLUMBING SHEETS THAT |
| | ARE NOT ASSOCIATED WITH THE GAS WORK- SECTION 107.2.1 |
| | WPB. |
| | |
| | 2) COPIES OF PREVIOUSLY APPROVED PLAN SHEETS UNDER A |
| | SEPARATE PERMIT HAVE BEEN SUBMITTED WHICH ARE NOT |
| | ACCEPTABLE. PROVIDE ORIGINAL, UP TO DATE, |
| | ELECTRONICALLY SIGNED AND SEALED PLANS FOR GAS PERMIT |
| | REVIEW- SECTION 107.2.1 WPB, FL. STATUTE 471.025, AND |
| | SECTION 61G15-23.005. FAC. |
| | |
| | 3) PROVIDE A VALUE ON THE PERMIT APPLICATION THAT IS |
| | CONSISTENT WITH THE SCOPE OF WORK SHOWN ON THE PLANS- |
| | SECTION 109.3 WPB. IT APPEARS THAT THE PIPING |
| | INSTALLATION COMPRISES MORE THAN JUST THE POOL PAVILION |
| | BBG GRILLS. PLEASE PROVIDE AN ITEMIZED SCOPE OF WORK |
| | AND PLANS THAT REFLECT THAT WORK. PLEASE SUBMIT COPIES |
| | OF SIGNED CONTRACT AND/OR ESTIMATES AND INVOICES THAT |
| | VERIFY THE TOTAL COSTS OF LABOR, MATERIALS, AND |
| | EQUIPMENT. |
| | |
| | 4) SHEET P-2.1 GAS RISER: |
| | A) PROVIDE REVISED CIVIL PLANS SHOWING THE POINT OF |
| | CONNECTION TO THE EXISTING MAIN GAS LINE AND THE |
| | LOCATION OF THE NEW METER- SECTION 107.2.1 WPB. |
| | B) SHOW THE DELIVERY PRESSURE AT THE METER- SECTION |
| | 401.1 FBC FG. |
| | C) SHOW THE TYPE AND SIZE OF RISER PIPES CONNECTING THE |
| | UG PE TO THE REGULATOR AND THE METER- SECTIONS 401.8 & |
| | 402.2 FBC FG. |
| | D) SUBMIT MANUFACTURER'S SPECS FOR THE REGULATOR MARKED |
| | OR HIGHLIGHTED UP TO SHOW THE SELECTED MODEL, INLET AND |
| | OUTLET PIPE SIZES AND PRESSURES, AND ORIFICE SIZE- |
| | SECTION 410.1 & 410.2 FBC FG. |
| | E) SHOW THE LOCATIONS OF THE REQUIRED PIPE UNIONS AT |
| | EACH SIDE OF THE REGULATOR- SECTION 410.2 (7). |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |