| 2020-10-28 13:07:47 | 1ST REVIEW FBC-2017 RES. FUEL GAS |
| | PERMIT- 20100816 |
| | 10/28/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) GAS RISER DRAWING: PLEASE INCLUDE THE 55,000 BTUH |
| | BBQ GRILL IN THE EXISTING APPLIANCE LIST, AND CORRECT |
| | THE MAX BTUH LOAD TOTAL TO INDICATE 991,000 BTUH. THE |
| | GRILL WAS INCLUDED WITH THE APPROVED PLANS UNDER |
| | PERMIT- 15110671 - SECTIONS G2412.3, G2412.4 & G2413.2 |
| | FBC RES. |
| | |
| | A) USING PIPE SIZING TABLE 402.4(3) FBC FG THAT YOU |
| | SHOW ON THE RISER, THE 1 IN. MAIN RISER PIPE IS |
| | UNDERSIZED FOR A 911,000 BTUH LOAD AT A TOTAL DEVELOPED |
| | LENGTH OF 110 FT. THE MINIMUM SIZE PER THE TABLE IS |
| | 1-1/4 IN. |
| | |
| | 2) THE CONTRACTOR OR QUALIFIER WHO PREPARED THE RISER |
| | DRAWING SHALL PROVIDE HIS/HER SIGNATURE ON IT- SECTION |
| | 107.2.1 WPB, AND FLORIDA STATUTES 471.003(2)(H) & |
| | 471.025. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |