Plan Review Notes
Plan Review Notes For Permit 20100804
Permit Number 20100804
Review Stop M
Sequence Number 1
Notes
Date Text
2020-11-03 11:23:411ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20100804
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE A SCOPE OF WORK FOR THIS PERMIT. THE
 APPLICATION INDICATES THIS PERMIT IS FOR AN INTERIOR
 BUILD OUT. THE A SHEETS INDICATE A FUTURE RESTAURANT.
 THE M SHEETS INDICATE RTU#1 (7.5 TON UNIT) AND RTU#2
 (10 TONS UNIT) BUT DOES NOT SHOW ANY DUCT WORK. THERE
 IS NO ENERGY CALCULATIONS OR EQUIPMENT SIZING
 CALCULATIONS SUBMITTED WITH THIS PACKAGE. FBC 107.2;
 FBC EC C403.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  