Plan Review Notes
Plan Review Notes For Permit 20100804
Permit Number 20100804
Review Stop B
Sequence Number 1
Notes
Date Text
2020-11-03 17:11:35WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20100804
 ADD: 7038 OKEECHOBEE BLVD.
 CONT: ELE8 CONSTRUCTION, INC.
 TEL: 561-430-4870
 E-MAIL: BOB#MWARCHITECTURE.COM
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: TUES. NOV. 03RD/2020
 ACTION: DENIED
  
 1) SHEET A-0.1 LIST THE PROJECT SPECIFIC CODE SUMMARY,
 LISTING A PRIMARY OCCUPANCY MERCANTILE AND SECONDARY
 OCCUPANCY BUSINESS. THIS PERMIT IS FOR A RESTRAINT
 UNTIL A LIFE SAFETY PLAN AND CODE ANALYSIS IS PROVIDED
 A OCCUPANCY TYPE CAN NOT BE DETERMINED? 107.2.1.2.
 2) WITHIN THE SUBMITTED PLANS THERE IS NO LIFE SAFETY
 SHEET FOR EITHER OF THE TENANT SPACES NOR CHAPTER 10
 MEANS OF EGRESS.107.3.5 MINIMUM PLAN REVIEW
 CRITERIA.2017 FLORIDA BUILDING CODE W 2017 WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER
 1, ADMINISTRATIVE CODE SECTION:
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS AND
 OR STRUCTURES.
 107.3.5.1 COMMERCIAL BUILDINGS
 107.3.5.1.1. BUILDING
  
 MISSING CODE DATA:
 LIFE SAFETY PLANS SHALL DETERMINE AND SHALL INCLUDE THE
 FOLLOWING:
 WALLS
 FURNITURE LAYOUT
 OCCUPANT LOAD AND EGRESS CAPACITIES
 GROSS OR NET
 DEAD END CORRIDORS
 DOOR SWING
 MEANS OF EGRESS EXIT ACCESS
 EXIT
 EXIT DISCHARGE / HOW MANY REQUIRED/ HOW MANY PROVIDED
  
 3) SHEET A-0.1 INDICATES UNDER THE HEADING OF DEFERRED
 SUBMITTALS DESIGN PRESSURES FOR ALUMINUM STOREFRONT
 DOOR AND A DRIVE THROUGH PICK UP WINDOW. THERE ARE
 DESIGN PRESSURES PROVIDED, BUT THERE IS NO WIND DESIGN
 CRITERIA PROVIDED FOR THE PRESSURES.
 2017 FBC-B 1603.1.4 WIND DESIGN DATA. THE FOLLOWING
 INFORMATION RELATED TO WIND LOADS SHALL BE SHOWN,
 REGARDLESS OF WHETHER WIND LOADS GOVERN THE DESIGN OF
 THE LATERAL FORCE-RESISTING SYSTEM OF THE STRUCTURE:
  
 3.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS
 DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1.
  
 3.2. RISK CATEGORY.
  
 3.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE. ASCE 7-10 TABLE 30.3.1.
  
 3.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 3.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED
 BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR
 THE DESIGN OF THE STRUCTURE, PSF.
  
 3.6. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING. ASCE 7-10 TABLE 30.3.1. 1609.3.1 WIND SPEED
 CONVERSION VULT TO VASD.
  
 4) SHEET CHIPOLTE_7000 MWIENER_7 MODEL (1) IS LOADED
 SIDEWAYS (VERTICALLY) PLEASE CORRECT FOR PLAN REVIEW
 AND RECORD RETENTION. 107.2.1.3. QUALITY OF PLANS. THE
 BUILDING OFFICIAL MAY ESTABLISH THROUGH DEPARTMENT
 POLICY OTHER STANDARDS FOR THE PLANS AND SPECIFICATIONS
 IN ORDER TO PROVIDE CONFORMITY TO ITS RECORD RETENTION
 PROGRAM. THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM
 SIZE, SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED
 TO RECORD MANAGEMENT. ELECTRONIC MEDIA MUST BE
 COMPATIBLE WITH THE ARCHIVE REQUIREMENTS OF FLORIDA
 STATUTES.
  
 5) WITHIN THE SUBMITTED PLANS THERE IS NO LIFE SAFETY
 SHEET OR FLOOR PLAN SHOWING COMPLIANCE WITH INTERIOR
 ENVIRONMENTS 107.3.5 MINIMUM PLAN REVIEW CRITERIA.2017
 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH AMENDMENTS
 TO THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATIVE
 CODE SECTION:
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS AND
 OR STRUCTURES.
 107.3.5.1 COMMERCIAL BUILDINGS
 107.3.5.1.1. BUILDING
 MISSING CODE DATA:
 RESTROOMS. 2017 FBC-B 1210.2.2. WALLS & PARTITIONS.
 THIS COMMENT IS A RESULT OF THE BUILDING OFFICIAL
 INTERPRETATION. IN RESTROOMS EPOXY PAINT IS NO LONGER
 CONSIDERED A SMOOTH HARD, NON-ABSORBENT SURFACE.
 WALLS & PARTITIONS WITHIN SHEET 2 FEET OF SERVICE
 SINKS, URINALS, AND WATER CLOSETS SHALL HAVE A SMOOTH,
 HARD, NON-ABSORBENT SURFACE TO A HEIGHT OF NOT LESS
 THAN 4 FEET ABOVE THE FLOOR, EXCEPT FOR STRUCTURAL
 ELEMENTS, THE MATERIAL USED IN SUCH WALLS SHALL BE OF A
 TYPE THAT IS NOT ADVERSELY AFFECTED BY MOISTURE.
  
 2509.1. WET AREAS. SHOWERS AND PUBLIC TOILET WALLS
 SHALL COMPLY WITH 1210.2.
 1210.2. FINISH MATERIALS. WALLS, BASE, FLOORS AND
 PARTITIONS IN TOILET AND BATHROOMS SHALL COMPLY WITH
 SECTIONS 1210.1 THROUGH 1210.4.
  
 6) WITHIN THE SUBMITTED PLANS THERE IS NO LIFE SAFETY
 SHEET OR FLOOR PLAN SHOWING COMPLIANCE WITH INTERIOR
 ENVIRONMENTS 107.3.5 MINIMUM PLAN REVIEW CRITERIA.2017
 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH AMENDMENTS
 TO THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATIVE
 CODE SECTION:
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS AND
 OR STRUCTURES.
 107.3.5.1 COMMERCIAL BUILDINGS
 107.3.5.1.1. BUILDING
 MISSING CODE DATA:
 ACCESSIBILITY / RESTROOMS
 NO RESTROOM FLOOR PLAN, WALL ELEVATIONS WITH ACCESSIBLE
 ELEMENTS AND DIMENSIONS., 2017 FBC-ACCESSIBILITY CODE
 CHAPTER 6, NO DRINKING FOUNTAIN.
  
 7) WITHIN THE SUBMITTED PLANS THERE IS NO LIFE SAFETY
 SHEET OR FLOOR PLAN SHOWING COMPLIANCE WITH INTERIOR
 ENVIRONMENTS 107.3.5 MINIMUM PLAN REVIEW CRITERIA.2017
 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH AMENDMENTS
 TO THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATIVE
 CODE SECTION:
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS AND
 OR STRUCTURES.
 107.3.5.1 COMMERCIAL BUILDINGS
 107.3.5.1.1. BUILDING
 MISSING CODE DATA:
 ACCESSIBILITY FOOD SERVING ESTABLISHMENTS.
 ACCESSIBILITY CODE/ DINING SURFACES.
 THE LIFE SAFETY SHEET DOES NOT SHOW COMPLIANCE WITH THE
 2017 FBC-ACCESSIBILITY CODE;
 7A) 226.1 WHERE DINING SURFACES ARE PROVIDED FOR THE
 CONSUMPTION OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE
 SEATING SPACES AND STANDING SPACES AT THE DINING
 SURFACES SHALL COMPLY WITH 902.
  
 7B) 226.2 DISPERSION. DINING SURFACES AND WORK SURFACES
 REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED
 THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING
 SURFACES AND WORK SURFACES.
  
 7C) 206.2.5 206.2.5 RESTAURANTS AND CAFETERIAS. IN
 RESTAURANTS AND CAFETERIAS, AN ACCESSIBLE ROUTE SHALL
 BE PROVIDED TO ALL DINING AREAS, INCLUDING RAISED OR
 SUNKEN DINING AREAS, AND OUTDOOR SEASONAL DINING AREAS.
  
 7D) 902.1. DINING SURFACES AND WORK SURFACES SHALL
 COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL.
 DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS,
 TABLES, LUNCH COUNTERS, AND BOOTHS. EXAMPLES OF WORK
 SURFACES INCLUDE CHECK WRITING SURFACES.
  
 7D)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 7D)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 8) BOTH SHEET A-2.20 AND M1 INDICATE THERE IS TO BE
 ADDITIONAL ROOF WORK REQUIRING ROOF TOP CURBS FOR
 INTAKE AND EXHAUST AS WELL AS NEW ROOF TOP RTU UNITS.
 THE IS A GENERIC ROOF TOP CURB DETAIL, BUT THE DETAIL
 IS LACKING INFORMATION AS TO THE ADDITIONAL STEEL ANGLE
 USED TO STRENGTHEN THE LOAD BETWEEN BAR JOIST. THE PLAN
 DOES NOT INDICATE THE TYPE OF WELDS FOR THE INFILL
 STEEL ANGLES, NOR DOES THE PLAN PROVIDE HOW TO
 STRENGTHEN THE BAR JOIST FOR THE ADDITIONAL POINT
 LOADING PLEASE ALSO NOTE SHEET M1 DETAIL 2 DOES HAVE A
 NOTE PROVIDE AND INSTALL WIND LOADING CLIPS PER
 STRUCTURAL ENGINEER.
 SYSTEMS SHALL WITHSTAND WIND LOADING FORCES AS REQUIRED
 BY LOCAL CODES. REFER TO STRUCTURAL PLANS BY OTHER FOR
 STRUCTURAL DETAILS.
 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, THE
 CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND
 DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS,
 VENTING, FASTENING REQUIREMENTS, FLASHING REQUIREMENTS
 AND WIND RESISTANCE RATING THAT ARE REQUIRED TO BE
 INSTALLED. PRODUCT EVALUATION AND INSTALLATION SHALL
 INDICATE COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR
 THE SPECIFIC SITE.
  
 2017 FBC-M- 301.15 WIND RESISTANCE.
 MECHANICAL EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE
 EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO
 RESIST THE WIND PRESSURES DETERMINED IN ACCORDANCE WITH
 THE FLORIDA BUILDING CODE, BUILDING.
 FBC-B-1609.6.4.4.1 COMPONENTS AND CLADDING. WIND
 PRESSURE FOR EACH COMPONENT OR CLADDING ELEMENT IS TO
 BE DESIGNED FOR WIND PRESSURES COMPONENTS AND
 ATTACHMENTS.
  
 LATERAL FORCE-RESISTING SYSTEM
 FOR ALL ROOF TOP EQUIPMENT, CURBS, FANS OR A/C STANDS,
 AND OR VENTS, DETAILED ATTACHMENT TO THE ROOF FRAMING &
 DECK AS WELL AS FROM THE CURB OR ROOF STAND TO THE
 EQUIPMENT ABOVE.
  
 2017 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
  
 9) WELDED OR BOLTED CONNECTIONS (ROOF TOP CURBS TO ROOF
 FRAMING/ BAR JOIST). THE CONTRACTOR IS REQUIRED TO
 PROVIDE WELD PROCEDURE SPECIFICATIONS & WELDER OPERATOR
 PERFORMANCE QUALIFICATION RECORDS IN ACCORDANCE WITH
 THE REFERENCED STANDARDS AT TIME OF INSPECTION FOR
 FIELD WIELDING, ON THE JOB-SITE WIELDING. THIRD PARTY
 CERTIFICATION WILL BE REQUIRED. REPORTS SUBMITTED TO
 BUILDING INSPECTOR AT TIME OF FRAMING INSPECTION.
 2017 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD
 AT
 561-805-6666.
  
 10) DEFERRED SUBMITTALS: STOREFRONT FRONT DOOR AND
 DRIVE UP WINDOW. 107.3.4.2 DEFERRED SUBMITTALS. FOR THE
 PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE
 TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
  
 11) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
2020-11-03 10:58:57IN REVIEW/ JW/ 11/03