Plan Review Notes
Plan Review Notes For Permit 20100803
Permit Number 20100803
Review Stop SIGNATURE
Sequence Number 1
Notes
Date Text
2020-11-03 20:14:19ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE RISER DIAGRAM OF EXISTING SERVICE TO VERIFY
 EXISTING SERVICE IS ADEQUATE. DIAGRAM PROVIDED IS
 MISSING CONDUCTOR SIZES AND OCP SIZES, ONLY STATES
 "EXISTING" FBC 107.2.1 NEC 220
  
 2. MAINS MUST BE GROUPED PER NEC 230.72A. 1 EXISTING
 DISCONNECT IS SHOWN WITH 3 NEW DISCONNECTS (2,200AMP
 AND 1, 400AMP) THE ANOTHER METER IS SHOWN WITHOUT A
 DISCONNECT FOR EXISTING PANEL "HP" PROVIDE CORRECTION.
  
 3. PROVIDE ACCURATE LOAD CALCULATION OF EXISTING
 SERVICE TO VERIFY EXISTING SERVICE IS ADEQUATE NEC 220
 FBC 107.2.1 LOAD CALCULATION PROVIDED ONLY SHOWS PANELS
 "1B" AND "2A". A LOAD STUDY OF 30 DAYS FROM THE POWER
 UTILITY WILL ALSO SUFFICE PER NEC 220.87
  
 4. NORMALLY THE POWER UTILITY ONLY ALLOWS 1 METER PER
 SPACE FOR A TENANT. 2 METERS SHOWN IN 1 SPACE. 1 FOR
 PANEL "1B" AND 1 FOR "2A". PROVIDE DOCUMENTATION FROM
 POWER UTILITY "FLORIDA POWER AND LIGHT (FPL)"
  
 4. SHOW COMPLETE GROUNDING ELECTRODE SYSTEM TO INCLUDE
 CONDUCTOR SIZES. FBC 107.2.1 NEC 250.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  