| 2020-11-03 20:14:19 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE RISER DIAGRAM OF EXISTING SERVICE TO VERIFY |
| | EXISTING SERVICE IS ADEQUATE. DIAGRAM PROVIDED IS |
| | MISSING CONDUCTOR SIZES AND OCP SIZES, ONLY STATES |
| | "EXISTING" FBC 107.2.1 NEC 220 |
| | |
| | 2. MAINS MUST BE GROUPED PER NEC 230.72A. 1 EXISTING |
| | DISCONNECT IS SHOWN WITH 3 NEW DISCONNECTS (2,200AMP |
| | AND 1, 400AMP) THE ANOTHER METER IS SHOWN WITHOUT A |
| | DISCONNECT FOR EXISTING PANEL "HP" PROVIDE CORRECTION. |
| | |
| | 3. PROVIDE ACCURATE LOAD CALCULATION OF EXISTING |
| | SERVICE TO VERIFY EXISTING SERVICE IS ADEQUATE NEC 220 |
| | FBC 107.2.1 LOAD CALCULATION PROVIDED ONLY SHOWS PANELS |
| | "1B" AND "2A". A LOAD STUDY OF 30 DAYS FROM THE POWER |
| | UTILITY WILL ALSO SUFFICE PER NEC 220.87 |
| | |
| | 4. NORMALLY THE POWER UTILITY ONLY ALLOWS 1 METER PER |
| | SPACE FOR A TENANT. 2 METERS SHOWN IN 1 SPACE. 1 FOR |
| | PANEL "1B" AND 1 FOR "2A". PROVIDE DOCUMENTATION FROM |
| | POWER UTILITY "FLORIDA POWER AND LIGHT (FPL)" |
| | |
| | 4. SHOW COMPLETE GROUNDING ELECTRODE SYSTEM TO INCLUDE |
| | CONDUCTOR SIZES. FBC 107.2.1 NEC 250. |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| | UILDING-PERMIT-FORMS |
| | |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | FRANK GIAQUINTO III |
| | ELECTRICAL INSPECTOR |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |